Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2006865
Status: Active
Facility Name: Amoco #2253
Address: 2351 W. Schaumburg Rd.
Schaumburg, IL 60194
County: Cook
Property Parcel:
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y001475
Green Tag Issue Date: 5/1/2023
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: 2351 Shaumburg Rd., LLC
Owner Address: 2351 W. Schaumburg Rd.
Schaumburg, IL 60194
Owner Status: Current Owner
Purchase Date: 5/10/2018
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 3/2/2026

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 4/17/2023 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0039188 2351 Shaumburg Rd., LLC Current Owner 5/10/2018
U0032360 Angel Associates, LP Former Owner 12/14/2009
U0027493 Amoco Oil Company Former Owner 1/1/1987
U0000552 BP Products North America, Inc. Former Owner 1/1/1987
U0000565 Amoco Oil Co Former Owner 12/31/1967
U0038736 CIMA Developers, LP Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violations (Current)

NOV Number: E0020251015 (Pending)    Issue Date: 4/15/2025    Expiration Date: 6/14/2025    View NOV Form

Tanks Violation
Facility Electrical Does Not Comply - Open electrical under dispenser 5/6
Facility Missing copies of 30 day Walkthrough Inspection Report.
Facility Missing copies of current testing certificates for operator training
Facility Missing copy of emergency instructions or emergency procedures plan
Facility Missing list of designated Class A/B & C Operators
1, 2, 3 Monthly line interstitial sensor records not available.
1, 2, 3 Precision tank test required. - Precision tank test is required on tank(s) if you cannot provide 24 months’ worth of tank “PASS” from ATG.
1, 2, 3 Required monthly tank leak test records not available.
2, 3 Shear valve(s) not properly mounted and/or not at proper height. - Shear valve mount rusted away and no longer supporting it
1, 2, 3 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry.
1 Water in containment with required interstitial sensors - Remove water and repair containments to prevent water ingress. - Dispenser 3/4 sensor raised and liquid in the UDC. Provide documentation of repair
1 Water in containment with required interstitial sensors - Remove water and repair containments to prevent water ingress. - Tank top sump contains liquid in contact woith sensor and exposed metal. Provide documentation of repair
2, 3 Water in containment with required interstitial sensors - Remove water and repair containments to prevent water ingress. - Dispenser 3/4 sensor raised and liquid in the UDC. Provide documentation of repair

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
04-1413 Eligible 11/22/2004 12/15/2004 $10,000
04-1413 Eligible 11/7/2011 12/27/2011 $10,000
Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 10000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 11/17/1987 Abandoned Material:
Current Age: 37 Abandoned Date:
Install Date: 10/30/1987 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 10/30/1987

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank STIP3 Cathodic Protection with Dielectric Coating 10/31/2024 10/31/2027
Leak Detect - Piping Electronic Pressurized Line Leak Detection 10/31/2024 10/31/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350R with CSLD 10/31/2024 10/31/2025
Overfill Prev Device Ball Only Removed Ball Float Vent Valve N/A N/A
Overfill Prev Device Overfill Drop Tube Valve 3/7/2023 3/7/2026
Piping Flexible Double Wall Environ Geo Flex N/A N/A
Piping Single Wall STP/Tanktop Sump 10/31/2024 10/31/2027
Leak Detect - Piping Sump Sensor 10/31/2024 10/31/2025
Spill Contain Device Single Wall Spill Bucket 10/31/2024 10/31/2027
Tank STIP3 Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Tank STIP3 Single Wall Precision Test (Tank) Pass 7/17/2019



Tank Number 2

Capacity: 10000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 11/17/1987 Abandoned Material:
Current Age: 37 Abandoned Date:
Install Date: 10/30/1987 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 10/30/1987

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank STIP3 Cathodic Protection with Dielectric Coating 10/31/2024 10/31/2027
Leak Detect - Piping Electronic Pressurized Line Leak Detection 10/31/2024 10/31/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350R with CSLD 10/31/2024 10/31/2025
Overfill Prev Device Ball Only Removed Ball Float Vent Valve N/A N/A
Overfill Prev Device Overfill Drop Tube Valve 9/12/2024 9/12/2027
Piping Flexible Double Wall Environ Geo Flex N/A N/A
Piping Single Wall STP/Tanktop Sump 10/31/2024 10/31/2027
Leak Detect - Piping Sump Sensor 10/31/2024 10/31/2025
Spill Contain Device Double Wall Spill Bucket 10/31/2024 10/31/2027
Tank STIP3 Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Tank STIP3 Single Wall Precision Test (Tank) Pass 5/2/2025



Tank Number 3

Capacity: 12000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 11/17/1987 Abandoned Material:
Current Age: 37 Abandoned Date:
Install Date: 10/30/1987 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 10/30/1987

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank STIP3 Cathodic Protection with Dielectric Coating 10/31/2024 10/31/2027
Leak Detect - Piping Mechanical Other Non-vented check valve N/A N/A
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350R with CSLD 10/31/2024 10/31/2025
Overfill Prev Device Ball Only Removed Ball Float Vent Valve N/A N/A
Overfill Prev Device Overfill Drop Tube Valve 3/7/2023 3/7/2026
Piping Flexible Double Wall Environ Geo Flex N/A N/A
Piping Single Wall STP/Tanktop Sump 10/31/2024 10/31/2027
Leak Detect - Piping Sump Sensor 10/31/2024 10/31/2025
Spill Contain Device Double Wall Spill Bucket 10/31/2024 10/31/2027
Tank STIP3 Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Tank STIP3 Single Wall Precision Test (Tank) Pass 7/17/2019

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 10/31/2024 10/31/2027
Leak Detect - Piping Sump Sensor 10/31/2024 10/31/2025



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 10/31/2024 10/31/2027
Leak Detect - Piping Sump Sensor 10/31/2024 10/31/2025



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 10/31/2024 10/31/2027
Leak Detect - Piping Sump Sensor 10/31/2024 10/31/2025



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 10/31/2024 10/31/2027
Leak Detect - Piping Sump Sensor 10/31/2024 10/31/2025

MFD Motorfuel Dispensing Forms