Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2006372
Status: Active
Facility Name: Woodlake Specialty Hospital
Address: 1225 Lake Street Melrose Park, IL 60160
County: Cook
Property Parcel: 15-10-211-019-0000
Facility Type: Private Institution
Owner Type: Private
Green Tag Decal: Z004092
Green Tag Issue Date: 7/10/2024
Green Tag Expire Date: 12/31/2026
MFD Type: N/A

Owner Details

Owner Name: Woodlake Pacific Holdings, LLC
Owner Address: 1225 W. Lake Street Melrose Park, IL 60610
Owner Status: Current Owner
Purchase Date: 9/15/2021
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 12/12/2026

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0040393 Woodlake Pacific Holdings, LLC Current Owner 9/15/2021
U0016271 Westlake Community Hospital Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violations (Current)

NOV Number: E0020260592 (Pending)    Issue Date: 3/9/2026    Expiration Date: 5/8/2026    View NOV Form

Tanks Violations
Facility Missing copies of 30 day Walkthrough Inspection Report.
2 Tank monitor does not appear to function properly and requires maintenance. - Bulb out

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
N/A 12/6/2023 Abandonment Log 01375-2023ABN

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 3000 Petroleum Use: Back-up Generator
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 3/10/1986 Abandoned Material:
Current Age: 58 Abandoned Date:
Install Date: 3/10/1968 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment Information

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive Not applicable Not applicable
Corrosion Prot - Tank Lining Materials Internal 4/7/2022 4/7/2027
Leak Detect - Piping European with No Test Req Suction Not applicable Not applicable
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 300c 6/20/2025 6/20/2026
Overfill Prev Device Overfill Drop Tube Valve 1/16/2025 1/16/2028
Piping Flexible Double Wall Environ Geo Flex Not applicable Not applicable
Piping Single Wall STP/Tanktop Sump Not applicable Not applicable
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required Not applicable Not applicable
Spill Contain Device Single Wall Spill Bucket 1/16/2025 1/16/2028
Tank Steel Single Wall Not applicable Not applicable

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall Environ Geo Flex Precision Test (Piping) Pass 12/3/2021
Tank Steel Single Wall Precision Test (Tank) Pass 4/8/2022



Tank Number 2

Capacity: 4000 Petroleum Use: Back-up Generator
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 3/10/1986 Abandoned Material:
Current Age: 43 Abandoned Date:
Install Date: 3/10/1983 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment Information

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive Not applicable Not applicable
Corrosion Prot - Tank Fiberglass Non-Corrosive Not applicable Not applicable
Leak Detect - Piping European with No Test Req Suction Not applicable Not applicable
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 300c 6/18/2024 6/18/2025
Overfill Prev Device Overfill Drop Tube Valve 1/16/2025 1/16/2028
Piping Fiberglass Double Wall A.O. Smith Not applicable Not applicable
Piping Single Wall STP/Tanktop Sump Not applicable Not applicable
Leak Detect - Piping Piping Sump Sensors Not Regulated Not applicable Not applicable
Spill Contain Device Single Wall Spill Bucket 1/16/2025 1/16/2028
Tank Fiberglass Single Wall Not applicable Not applicable

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall A.O. Smith Precision Test (Piping) Pass 12/3/2021
Tank Fiberglass Single Wall Precision Test (Tank) Pass 12/3/2021



Tank Number 3

Capacity: 20000 Petroleum Use: Consumptive Use on Premises for Heating
Product: Diesel Fuel CERCLA Substance:
Status: Abandoned in place CAS Code:
Regulated Status: State Removed Date:
OSFM First Notify Date: 8/17/1987 Abandoned Material: Inert material mixed with portland cement
Current Age: 43 Abandoned Date: 12/6/2023
Install Date: 8/12/1982 Red Tag Issue Date:
Last Used Date: 3/2/2022 Fee Due: $0.00
Product Date:

Equipment Information

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive Not applicable Not applicable
Corrosion Prot - Tank Fiberglass Non-Corrosive Not applicable Not applicable
Leak Detect - Piping American with Annual Prec Line Testing Suction No passing test found No passing test found
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 300c 3/13/2023 3/13/2024
Overfill Prev Device Overfill Drop Tube Valve 11/17/2021 11/17/2024
Piping Fiberglass Single Wall Piping Not applicable Not applicable
Piping Single Wall STP/Tanktop Sump Not applicable Not applicable
Leak Detect - Piping Piping Sump Sensors Not Regulated Not applicable Not applicable
Spill Contain Device Single Wall Spill Bucket 11/17/2021 11/17/2024
Tank Fiberglass Single Wall Not applicable Not applicable

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Leak Detect - Piping American with Annual Prec Line Testing Suction Functional Pass 3/13/2023
Piping Fiberglass Single Wall Piping Precision Test (Piping) Fail 12/3/2021
Tank Fiberglass Single Wall Precision Test (Tank) Pass 3/2/2022

Failed test = the latest test has failed.

Not applicable = a test does not apply to this equipment type or configuration.

No passing test found = a passing test is expected but was not found from the source data.


Dispenser Information




Failed test = the latest test has failed.

Not applicable = a test does not apply to this equipment type or configuration.

No passing test found = a passing test is expected but was not found from the source data.


MFD Motorfuel Dispensing Forms