Notice of Violatlions (Current)
NOV Number:
E0020251341
(Pending)
Issue Date:
5/23/2025
Expiration Date:
7/22/2025
View NOV Form
Tanks |
Violations |
1 |
Failed to Empty the Tank to 1" or Less - Tank has been out of service since 7/31/2023. |
1 |
Remove tank(s) - Single-Walled, Over 30 Years Old and OOS Over One Year - Randall Wright 708-895-7400 (Lieutenant Village of Lansing Fire Department / A/b Operator) stated taht tank 1 has not been used since 7/31/2023) |
1 |
Submit Notification Form For Tank Status Change - The Notification Form is available at https://webapps.sfm.illinois.gov/USTPortal/NotificationForm. This form is required to be submitted within 30 days of a tank status change. |
NOV Number:
E0020251342
(Pending)
Issue Date:
5/23/2025
Expiration Date:
7/22/2025
View NOV Form
Tanks |
Violations |
Facility |
Fire Extinguishers - Minimum 4A:60BC are not present at each island and at an emergency shutoff switch |
NOV Number:
E0020251343
(Pending)
Issue Date:
5/23/2025
Expiration Date:
7/22/2025
View NOV Form
Tanks |
Violations |
Facility |
Annual Emergency Stop Inspection not completed or inspection report not available. - All emergency shutoff switches shall be tested annually to verify they shut down all STPs and dispensers. Form can be found at https://sfm.illinois.gov to download and complete. |
2 |
Annual leak detection certification not completed (Required annually). - ATG Cert. |
Facility |
Missing copies of Annual Walkthrough Inspection Report. - Annual Walkthrough by a licensed contractor shall be conducted and documentation maintained on site. |
2 |
Overfill prevention equipment inspection(s) not completed (Required every 3 years). |
2 |
Triennial spill prevention equipment testing not completed. |