Division of Petroleum & Chemical Safety

 
Pay Tank Fees Online Print Detail Page Export to Excel

Facility Details

Facility Number: 2005308
Status: Active
Facility Name: Milen's Amoco
Address: 3144 West 147th Street Posen, IL 60469
County: Cook
Property Parcel: 28-12-117-020-0000
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y002472
Green Tag Issue Date: 11/3/2023
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: Kedzie Services, Inc.
Owner Address: 3144 W. 147th Street Posen, IL 60469
Owner Status: Current Owner
Purchase Date: 4/4/1979
Type of Financial Responsibility: Designated Savings Account
Financial Responsibility Reporting Due Date: 4/7/2026

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 1/17/2024 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0029143 Kedzie Services, Inc. Current Owner 4/4/1979
U0010341 Milen Edward S Former Owner 12/31/1967
U0027493 Amoco Oil Company Former Owner
U0000552 BP Products North America, Inc. Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020251685 (Pending)    Issue Date: 7/3/2025    Expiration Date: 9/1/2025    View NOV Form

Tanks Violations
Facility Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable - Intercom system not functional; repair/replace as necessary to provide communication at dispensers. Reference 175.210 h)
Facility Fire Extinguishers - Past due for annual testing - Have annual testing performed and tag all fire extinguishers accordingly. (Nov. 2023)

NOV Number: E0020251686 (Pending)    Issue Date: 7/3/2025    Expiration Date: 9/1/2025    View NOV Form

Tanks Violations
Facility Annual Emergency Stop Inspection not completed or inspection report not available. - All emergency shutoff switches shall be tested annually to verify they shut down all STPs and dispensers. Form can be found at https://sfm.illinois.gov to download and complete.
5, 6, 7 Annual leak detection certification not completed (Required annually). - (ATG. Cert)
Facility Facility Operation and Maintenance Plan not updated to new requirements. - Facility Operations and Maintenance Plan does not meet requirements of new rules or is not available. Go to https://sfm.illinois.gov/content/dam/soi/en/web/sfm/sfmdocuments/documents/oandmtemplate.pdf to download and complete O & M template and maintain completed form on site.
5, 6, 7 Mechanical line leak detector requires annual functional test.
5 Miscellaneous - Equipment in disrepair- Reference 176.410
Facility Missing copies of Annual Walkthrough Inspection Report. - Annual Walkthrough by a licensed contractor shall be conducted and documentation maintained on site.
Facility Missing copy of emergency instructions or emergency procedures plan - Form can be found at https://sfm.illinois.gov to download and complete.
5, 6, 7 Precision line test required. - Annual third-party precision line test is required.
5, 6, 7 Shear valve inspection report not completed (Required during Annual Walkthrough Inspection). - Provide documentation that annual testing of all shear valves has been conducted and passed. Go to https://sfm.illinois.gov to print out the Shear Valve inspection form.
5 Shear valve(s) not properly mounted and/or not at proper height. - All shear valves are required to be anchored. One or more shear valves in the above listed dispenser is not appropriately anchored.
5 Shear valve(s) not properly mounted and/or not at proper height. - Shear vavle to low.
6 Shear valve(s) not properly mounted and/or not at proper height. - All shear valves are required to be anchored. One or more shear valves in the above listed dispenser is not appropriately anchored.
6 Shear valve(s) not properly mounted and/or not at proper height. - Shear vavle to low.
5, 7 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry.
5, 7 Water in containment without required sensors – install cathodic protection on all exposed steel piping or make containment watertight. By 10/13/28, all containments must be watertight and any CP installed in containments must be removed.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 8000 Gasoline Removed Federal $0.00 08/01/1988 - REM
2 6000 Gasoline Removed Federal $0.00 08/01/1988 - REM
3 6000 Gasoline Removed Federal $0.00 08/01/1988 - REM
4 500 Used Oil Removed Federal $0.00 08/01/1988 - REM
5 10000 Gasoline - Regular Currently in use Federal $0.00
6 10000 Gasoline - Premium Currently in use Federal $0.00
7 10000 Diesel Fuel Currently in use Federal $0.00
8 550 Used Oil Removed Federal $0.00 03/12/2001 - REM

Dispenser Information

Name\ID Status
1/2 Active
3/4 Active
5/6 Active
7/8 Active

MFD Motorfuel Dispensing Forms

No Forms Found