Division of Petroleum & Chemical Safety

 
Print Detail Page Export to Excel

Facility Details

Facility Number: 2002988
Status: Active
Facility Name: City of Wheaton
Address: 821 W. Liberty Drive
Wheaton, IL 60189
County: Du Page
Property Parcel:
Facility Type: City / Town
Owner Type: Municipal
Green Tag Decal: W004951
Green Tag Issue Date: 9/28/2021
Green Tag Expiration Date: 12/31/2023

Owner Details

Owner Name: City of Wheaton
Owner Address: 303 E. Wesley
Wheaton, IL 60187
Owner Status: Current Owner
Purchase Date: 6/1/1969
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 11/15/2022

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Fleet 9/28/2021 12/31/2023

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0016303 City of Wheaton Current Owner 6/1/1969

Permits (Unexpired)

Click for permit history

No Active Permits Found

Deficiencies (Current)

NOV Number: E0020213349 (Pending)    Issue Date: 12/16/2021    Expiration Date: 2/14/2022    View NOV Form

Tanks Deficiency
7, 8 Annual electronic line leak detector test not completed.
7, 8 Annual leak detection certification not completed (Required annually).
7 Line interstitial sensor functional test not accomplished (Required annually). - Dispenser Sumps
7 Line interstitial sensor functional test not accomplished (Required annually). - STP's
8 Line interstitial sensor functional test not accomplished (Required annually). - Dispenser Sumps
8 Line interstitial sensor functional test not accomplished (Required annually). - STP's
7 Triennial spill prevention equipment testing not completed. - Dispenser Sumps
7 Triennial spill prevention equipment testing not completed. - STP's
8 Triennial spill prevention equipment testing not completed. - Dispenser Sumps
8 Triennial spill prevention equipment testing not completed. - Drop tube
8 Triennial spill prevention equipment testing not completed. - STP's

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
97-2136 11/6/1997 Removal Log

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
89-1555 Eligible 2/1/1994 2/8/1994 $10,000

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 10000 Gasoline Removed Federal $0.00 08/11/1989 - REM
2 10000 Gasoline Removed Federal $0.00 08/11/1989 - REM
3 2000 Diesel Fuel Removed Federal $0.00 08/11/1989 - REM
4 1000 Used Oil Removed Federal $0.00 10/06/1997 - REM
5 10000 Diesel Fuel Removed Federal $0.00 10/28/1998 - REM
6 15000 Gasoline Removed Federal $0.00 10/14/1998 - REM
7 15000 Gasoline - Regular Currently in use Federal $0.00
8 10000 Diesel Fuel Currently in use Federal $0.00

Dispenser Information

Name\ID Status Sensor Shuts Down Product Pump
1/2 Active Unknown
3/4 Active Unknown
5/6 Active Unknown

MFD Motorfuel Dispensing Forms