Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2002419
Status: Active
Facility Name: 300 West Galena, LLC
Address: 300 W. Galena Blvd.
Aurora, IL 60506
County: Kane
Property Parcel: 15-21-286-006
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Z000110
Green Tag Issue Date: 3/21/2024
Green Tag Expiration Date: 12/31/2026

Owner Details

Owner Name: 300 West Galena, LLC
Owner Address: 26 Mill Plain Road
Danbury, CT 06811
Owner Status: Current Owner
Purchase Date: 8/30/2023
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 10/22/2025

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 3/21/2024 12/31/2026

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0041007 300 West Galena, LLC Current Owner 8/30/2023
U0039400 Galena Car Wash & Service, Inc. Former Owner 4/23/2018
U0027493 Amoco Oil Company Former Owner 12/2/1989
U0000552 BP Products North America, Inc. Former Owner 12/2/1989
U0011618 Rudigier, William Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violations (Current)

NOV Number: E0020250112 (Pending)    Issue Date: 1/14/2025    Expiration Date: 3/15/2025    View NOV Form

Tanks Violation
6, 7, 8, 9, 10 Annual leak detection certification not completed (Required annually). - Annual leak detection is required. Passing results shall be entered on OSFM portal.
6, 7, 8, 9, 10 Annual tank impressed current system test not completed. - Annual impressed current testing is required. Passing results shall be entered on OSFM portal.
6, 7, 8, 9, 10 Triennial spill prevention equipment testing not completed. - Triannual testing of spill buckets is required. Passing results shall be entered on OSFM portal.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
20180517 Eligible 8/30/2018 9/6/2018 $5,000 Letter
20180517 Eligible 8/30/2018 9/6/2018 $5,000 Letter
Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 6000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 10/3/1988
OSFM First Notify Date: 3/19/1986 Abandoned Material:
Current Age: Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: 10/1/1988 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 2

Capacity: 6000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 10/3/1988
OSFM First Notify Date: 3/19/1986 Abandoned Material:
Current Age: Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: 10/1/1988 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 3

Capacity: 6000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 10/3/1988
OSFM First Notify Date: 3/19/1986 Abandoned Material:
Current Age: Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: 10/1/1988 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 4

Capacity: 6000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 10/3/1988
OSFM First Notify Date: 3/19/1986 Abandoned Material:
Current Age: Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: 10/1/1988 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 5

Capacity: 6000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 10/3/1988
OSFM First Notify Date: 3/19/1986 Abandoned Material:
Current Age: Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: 10/1/1988 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 6

Capacity: 12000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 6/28/1996 Abandoned Material:
Current Age: 35 Abandoned Date:
Install Date: 11/15/1989 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 11/15/1989

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Impressed Current Cathodic Protection 3/6/2025 3/6/2026
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 2/5/2025 2/5/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 2/5/2025 2/5/2026
Overfill Prev Device Overfill Alarm 11/16/2023 11/16/2026
Overfill Prev Device Overfill Drop Tube Valve 11/16/2023 11/16/2026
Piping Fiberglass Single Wall Piping A.O. Smith N/A N/A
Piping Single Wall STP/Tanktop Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A
Spill Contain Device Single Wall Spill Bucket 3/6/2025 3/6/2028
Tank Steel Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Single Wall Piping A.O. Smith Precision Test (Piping) Pass 2/5/2025
Tank Steel Single Wall Precision Test (Tank) Pass 11/16/2023



Tank Number 7

Capacity: 12000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 6/28/1996 Abandoned Material:
Current Age: 35 Abandoned Date:
Install Date: 11/15/1989 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 11/15/1989

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Impressed Current Cathodic Protection 3/6/2025 3/6/2026
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 2/5/2025 2/5/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 2/5/2025 2/5/2026
Overfill Prev Device Overfill Alarm 11/16/2023 11/16/2026
Overfill Prev Device Overfill Drop Tube Valve 2/14/2024 2/14/2027
Piping Fiberglass Single Wall Piping A.O. Smith N/A N/A
Piping Single Wall STP/Tanktop Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A
Spill Contain Device Single Wall Spill Bucket 3/6/2025 3/6/2028
Tank Steel Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Single Wall Piping A.O. Smith Precision Test (Piping) Pass 2/5/2025
Tank Steel Single Wall Precision Test (Tank) Pass 11/16/2023



Tank Number 8

Capacity: 12000 Petroleum Use:
Product: E85 CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 6/28/1996 Abandoned Material:
Current Age: 35 Abandoned Date:
Install Date: 11/15/1989 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 11/15/1989

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Impressed Current Cathodic Protection 3/6/2025 3/6/2026
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 2/5/2025 2/5/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 3/6/2025 3/6/2026
Overfill Prev Device Overfill Alarm 11/16/2023 11/16/2026
Overfill Prev Device Overfill Drop Tube Valve 2/23/2024 2/23/2027
Piping Fiberglass Single Wall Piping A.O. Smith N/A N/A
Piping Single Wall STP/Tanktop Sump 2/28/2024 2/28/2027
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A
Spill Contain Device Single Wall Spill Bucket 3/6/2025 3/6/2028
Tank Steel Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Single Wall Piping A.O. Smith Precision Test (Piping) Pass 2/5/2025
Tank Steel Single Wall Precision Test (Tank) Pass 11/16/2023



Tank Number 9

Capacity: 12000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 6/28/1996 Abandoned Material:
Current Age: 35 Abandoned Date:
Install Date: 11/15/1989 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 11/15/1989

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Impressed Current Cathodic Protection 3/6/2025 3/6/2026
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 2/5/2025 2/5/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 3/6/2025 3/6/2026
Overfill Prev Device Overfill Alarm 11/16/2023 11/16/2026
Overfill Prev Device Overfill Drop Tube Valve 11/16/2023 11/16/2026
Piping Fiberglass Single Wall Piping A.O. Smith N/A N/A
Piping Single Wall STP/Tanktop Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A
Spill Contain Device Single Wall Spill Bucket 3/6/2025 3/6/2028
Tank Steel Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Single Wall Piping A.O. Smith Precision Test (Piping) Pass 2/5/2025
Tank Steel Single Wall Precision Test (Tank) Pass 11/16/2023



Tank Number 10

Capacity: 12000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 6/28/1996 Abandoned Material:
Current Age: 35 Abandoned Date:
Install Date: 11/15/1989 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 11/15/1989

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Impressed Current Cathodic Protection 3/6/2025 3/6/2026
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 2/5/2025 2/5/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 2/5/2025 2/5/2026
Overfill Prev Device Overfill Alarm 11/16/2023 11/16/2026
Piping Fiberglass Single Wall Piping A.O. Smith N/A N/A
Piping Single Wall STP/Tanktop Sump 2/28/2024 2/28/2027
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A
Spill Contain Device Single Wall Spill Bucket 3/6/2025 3/6/2028
Tank Steel Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Single Wall Piping A.O. Smith Precision Test (Piping) Pass 2/5/2025
Tank Steel Single Wall Precision Test (Tank) Pass 3/5/2024

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 11/12

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 2/28/2024 2/28/2027
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 9/10

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 2/28/2024 2/28/2027
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A

MFD Motorfuel Dispensing Forms

No Forms Found