Owner Summary
Click for Facility/Tank Ownership history
| Owner Number |
Owner Name |
Owner Status |
Purchase Date |
| U0035671 |
RDK Ventures LLC |
Current Owner |
1/7/2010 |
| U0027449 |
Equilon Enterprises, LLC |
Former Owner |
1/7/2000 |
| U0013849 |
Shell Oil Products |
Former Owner |
12/31/1967 |
| U0031151 |
Shell Oil Products US c/o Gilbarco Veeder-Root |
Former Owner |
|
Notice of Violations (Current)
NOV Number:
E0020261741
(Pending)
Issue Date:
7/8/2026
Expiration Date:
9/6/2026
View NOV Form
| Tanks |
Violations |
| 2 |
Line leak detection equipment in alarm or failed test, must repair or replace. - Leak detector(s) failed annual testing. Repair/replace as necessary. Repaired/replaced leak detector(s) shall be retested to show passing results. Per Tanknology test 6/16/2026 ;
"RUL 2 LD failed to stop the motor when put into pldd shutdown. Required manipulating the breakers to turn the motor on and off to catch the LD." |
IEMA Numbers Associated with the Facility
No IEMA Numbers Found
LUST
Fund Eligibility and Deductibility Determinations
| IEMA Number |
Status |
OSFM Received Date |
OSFM Response Date |
Deductible |
Letter |
| 03-0393 |
Eligible |
5/1/2003
|
5/19/2003
|
$10,000
|
|
Tank Number 1
| Capacity: |
12000 |
|
Petroleum Use: |
|
| Product: |
Gasoline - Regular |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
2/13/1986 |
|
Abandoned Material: |
|
| Current Age: |
41 |
|
Abandoned Date: |
|
| Install Date: |
2/13/1985 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
|
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Sacrificial Anode Flex Connector |
10/17/2025 |
10/17/2028 |
|
Corrosion Prot - Piping
|
Sacrificial Anode Flex Connector |
10/17/2025 |
10/17/2028 |
|
Corrosion Prot - Piping
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Electronic Pressurized Line Leak Detection |
6/16/2026 |
6/16/2027 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 350 with CSLD |
6/16/2026 |
6/16/2027 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
5/8/2025 |
5/8/2028 |
|
Piping
|
Fiberglass Single Wall Piping |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
Not applicable |
Not applicable |
Leak Detect - Piping
|
Piping Sump Sensors Not Regulated |
Not applicable |
Not applicable |
|
Spill Contain Device
|
Double Wall Spill Bucket |
5/8/2025 |
5/8/2028 |
|
Tank
|
Fiberglass Single Wall |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Fiberglass Single Wall Piping
|
Precision Test (Piping)
|
Pass
|
6/16/2026
|
|
Tank
|
Fiberglass Single Wall
|
Precision Test (Tank)
|
Pass
|
6/6/2025
|
Tank Number 2
| Capacity: |
12000 |
|
Petroleum Use: |
|
| Product: |
Gasoline - Regular |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
2/13/1986 |
|
Abandoned Material: |
|
| Current Age: |
41 |
|
Abandoned Date: |
|
| Install Date: |
2/13/1985 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
|
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Sacrificial Anode Flex Connector |
10/17/2025 |
10/17/2028 |
|
Corrosion Prot - Piping
|
Sacrificial Anode Flex Connector |
10/17/2025 |
10/17/2028 |
|
Corrosion Prot - Piping
|
Sacrificial Anode Flex Connector |
10/17/2025 |
10/17/2028 |
|
Corrosion Prot - Piping
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Electronic Pressurized Line Leak Detection |
6/30/2025 |
6/16/2026 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 350 with CSLD |
6/16/2026 |
6/16/2027 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
6/10/2025 |
6/10/2028 |
|
Piping
|
Fiberglass Single Wall Piping |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
Not applicable |
Not applicable |
Leak Detect - Piping
|
Piping Sump Sensors Not Regulated |
Not applicable |
Not applicable |
|
Spill Contain Device
|
Double Wall Spill Bucket |
7/16/2024 |
7/16/2027 |
|
Tank
|
Fiberglass Single Wall |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Fiberglass Single Wall Piping
|
Precision Test (Piping)
|
Pass
|
6/16/2026
|
|
Tank
|
Fiberglass Single Wall
|
Precision Test (Tank)
|
Pass
|
6/6/2025
|
Tank Number 3
| Capacity: |
12000 |
|
Petroleum Use: |
|
| Product: |
Gasoline - Premium |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
2/13/1986 |
|
Abandoned Material: |
|
| Current Age: |
41 |
|
Abandoned Date: |
|
| Install Date: |
2/13/1985 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
|
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Sacrificial Anode Flex Connector |
10/17/2025 |
10/17/2028 |
|
Corrosion Prot - Piping
|
Sacrificial Anode Flex Connector |
10/17/2025 |
10/17/2028 |
|
Corrosion Prot - Piping
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Electronic Pressurized Line Leak Detection |
6/16/2026 |
6/16/2027 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 350 with CSLD |
6/16/2026 |
6/16/2027 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
7/16/2024 |
7/16/2027 |
|
Piping
|
Fiberglass Single Wall Piping |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
Not applicable |
Not applicable |
Leak Detect - Piping
|
Piping Sump Sensors Not Regulated |
Not applicable |
Not applicable |
|
Spill Contain Device
|
Double Wall Spill Bucket |
7/16/2024 |
7/16/2027 |
|
Tank
|
Fiberglass Single Wall |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Fiberglass Single Wall Piping
|
Precision Test (Piping)
|
Pass
|
6/16/2026
|
|
Tank
|
Fiberglass Single Wall
|
Precision Test (Tank)
|
Pass
|
6/6/2025
|
Failed test = the latest test has failed.
Not applicable = a test does not apply to this equipment type or configuration.
No passing test found = a passing test is expected but was not found from the source data.
Dispenser Information
Name\ID 1/2
| Status: |
Active |
|
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Dispenser
|
Single Wall UDC Sump |
Not applicable
|
Not applicable
|
Leak Detect - Piping
|
Piping Sump Sensors Not Regulated Not Required |
Not applicable
|
Not applicable
|
Name\ID 3/4
| Status: |
Active |
|
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Dispenser
|
Single Wall UDC Sump |
Not applicable
|
Not applicable
|
Leak Detect - Piping
|
Piping Sump Sensors Not Regulated Not Required |
Not applicable
|
Not applicable
|
Name\ID 5/6
| Status: |
Active |
|
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Dispenser
|
Single Wall UDC Sump |
Not applicable
|
Not applicable
|
Leak Detect - Piping
|
Piping Sump Sensors Not Regulated Not Required |
Not applicable
|
Not applicable
|
Name\ID 7/8
| Status: |
Active |
|
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Dispenser
|
Single Wall UDC Sump |
Not applicable
|
Not applicable
|
Leak Detect - Piping
|
Piping Sump Sensors Not Regulated Not Required |
Not applicable
|
Not applicable
|
Failed test = the latest test has failed.
Not applicable = a test does not apply to this equipment type or configuration.
No passing test found = a passing test is expected but was not found from the source data.
MFD
Motorfuel Dispensing Forms
No Forms Found