Notice of Violations (Current)
NOV Number:
E0020261673
(Pending)
Issue Date:
6/26/2026
Expiration Date:
8/25/2026
View NOV Form
| Tanks |
Violations |
| 2, 5 |
Line interstitial sensors have been raised and rendered inoperational. - 175.640 a) 2) All new and existing sump sensors must be installed so as to detect liquid per manufacturer's specifications or, if not specified by the manufacturer, at the lowest point in the sump. |
| 1 |
Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. - 175.405 a) 1) A) Spill containment equipment that will prevent release of product to
the environment when the transfer hose is detached from the fill
pipe (e.g., a spill catch basin). Spill containment equipment shall
be maintained in a dry, clean state. |
| 2, 5 |
Water in containment with required interstitial sensors - Remove water and repair containments to prevent water ingress. - Both STP sumps have liquid in them. Remove liquid.
Section 175.410 Submersible, Under-dispenser, Transition and Other Containment Sumps
a) All containment sumps must consist of a factory manufactured containment that is
liquid-tight on its sides, bottom and at any penetrations and is compatible with the
substance conveyed by the piping. Such containment shall also have a factory
manufactured protective cover and supporting components that are properly
maintained. If the protective cover or its supporting components are cracked,
deteriorated or missing, the cover and supporting components that are defective
shall be replaced. |
IEMA Numbers Associated with the Facility
| IEMA Number |
Inspection Date |
Inspection Type |
Permit Number |
| 97-0765 |
11/7/1997 |
Removal Log |
|
| 98-1501 |
6/23/1998 |
Removal Log |
|
LUST
Fund Eligibility and Deductibility Determinations
| IEMA Number |
Status |
OSFM Received Date |
OSFM Response Date |
Deductible |
Letter |
| 97-0765 |
Eligible |
9/24/1998
|
11/24/1998
|
$10,000
|
|
Tank Number 1
| Capacity: |
8000 |
|
Petroleum Use: |
|
| Product: |
Gasoline - Regular |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
3/3/1986 |
|
Abandoned Material: |
|
| Current Age: |
41 |
|
Abandoned Date: |
|
| Install Date: |
3/3/1985 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
|
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Mechanical Pressurized Line Leak Detection |
6/9/2026 |
6/9/2027 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 300c |
6/9/2026 |
6/9/2027 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
6/12/2024 |
6/12/2027 |
|
Piping
|
Fiberglass Double Wall Ameron Dualoy 3000/LCX |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
6/5/2024 |
6/5/2027 |
Leak Detect - Piping
|
Sump Sensor with positive shutdown |
6/5/2024 |
6/5/2027 |
|
Spill Contain Device
|
Single Wall Spill Bucket |
6/5/2024 |
6/5/2027 |
|
Tank
|
Fiberglass Single Wall |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Fiberglass Double Wall Ameron Dualoy 3000/LCX
|
Precision Test (Piping)
|
Pass
|
6/9/2026
|
Tank Number 2
| Capacity: |
4000 |
|
Petroleum Use: |
|
| Product: |
Gasoline - Regular |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
3/3/1986 |
|
Abandoned Material: |
|
| Current Age: |
41 |
|
Abandoned Date: |
|
| Install Date: |
3/3/1985 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
|
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Mechanical Pressurized Line Leak Detection |
6/9/2026 |
6/9/2027 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 300c |
6/9/2026 |
6/9/2027 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
6/5/2024 |
6/5/2027 |
|
Piping
|
Fiberglass Double Wall Ameron Dualoy 3000/LCX |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
6/5/2024 |
6/5/2027 |
Leak Detect - Piping
|
Sump Sensor with positive shutdown |
6/5/2024 |
6/5/2027 |
|
Spill Contain Device
|
Single Wall Spill Bucket |
6/5/2024 |
6/5/2027 |
|
Tank
|
Fiberglass Single Wall |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Fiberglass Double Wall Ameron Dualoy 3000/LCX
|
Precision Test (Piping)
|
Pass
|
6/9/2026
|
Tank Number 3
| Capacity: |
2000 |
|
Petroleum Use: |
|
| Product: |
Diesel Fuel |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
6/23/1998 |
|
OSFM
First Notify Date: |
3/3/1986 |
|
Abandoned Material: |
|
| Current Age: |
12 |
|
Abandoned Date: |
|
| Install Date: |
1/1/1986 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
6/23/1998 |
|
Fee Due: |
$0.00 |
| Product Date: |
1/1/1986 |
|
|
|
Equipment Information
No Equipment Listed
Additional Tests
No Tests Listed
Tank Number 4
| Capacity: |
500 |
|
Petroleum Use: |
|
| Product: |
Used Oil |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
11/7/1997 |
|
OSFM
First Notify Date: |
3/3/1986 |
|
Abandoned Material: |
|
| Current Age: |
11 |
|
Abandoned Date: |
|
| Install Date: |
1/1/1986 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
11/12/1997 |
|
Fee Due: |
$0.00 |
| Product Date: |
1/1/1986 |
|
|
|
Equipment Information
No Equipment Listed
Additional Tests
No Tests Listed
Tank Number 5
| Capacity: |
6000 |
|
Petroleum Use: |
None |
| Product: |
Diesel Fuel |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
9/24/1998 |
|
Abandoned Material: |
|
| Current Age: |
28 |
|
Abandoned Date: |
|
| Install Date: |
6/29/1998 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
|
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Mechanical Pressurized Line Leak Detection |
6/9/2026 |
6/9/2027 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 300c |
6/9/2026 |
6/9/2027 |
|
Leak Detect - Tank
|
Non-Discriminating Interstitial Monitoring Sensors |
6/9/2026 |
6/9/2027 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
6/5/2024 |
6/5/2027 |
|
Piping
|
Fiberglass Double Wall Ameron Dualoy 3000/LCX |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
6/5/2024 |
6/5/2027 |
Leak Detect - Piping
|
Sump Sensor with positive shutdown |
6/5/2024 |
6/5/2027 |
|
Spill Contain Device
|
Single Wall Spill Bucket |
6/5/2024 |
6/5/2027 |
|
Tank
|
Fiberglass Double Wall |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Fiberglass Double Wall Ameron Dualoy 3000/LCX
|
Precision Test (Piping)
|
Pass
|
6/9/2026
|
Failed test = the latest test has failed.
Not applicable = a test does not apply to this equipment type or configuration.
No passing test found = a passing test is expected but was not found from the source data.
Dispenser Information
Name\ID 1/2
| Status: |
Active |
|
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Dispenser
|
Single Wall UDC Sump |
Not applicable
|
Not applicable
|
Leak Detect - Piping
|
Piping Sump Sensors Not Regulated Not Required |
Not applicable
|
Not applicable
|
Name\ID 3/4
| Status: |
Active |
|
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Dispenser
|
Single Wall UDC Sump |
Not applicable
|
Not applicable
|
Leak Detect - Piping
|
Piping Sump Sensors Not Regulated Not Required |
Not applicable
|
Not applicable
|
Failed test = the latest test has failed.
Not applicable = a test does not apply to this equipment type or configuration.
No passing test found = a passing test is expected but was not found from the source data.
MFD
Motorfuel Dispensing Forms
No Forms Found