Division of Petroleum & Chemical Safety

 
Pay Tank Fees Online Print Detail Page Export to Excel

Facility Details

Facility Number: 2001195
Status: Active
Facility Name: Village of Hanover Park
Address: 2121 W. Lake street Hanover Park, IL 60103
County: Du Page
Property Parcel: 01-13-206-016
Facility Type: City / Town
Owner Type: Municipal
Green Tag Decal: Z003438
Green Tag Issue Date: 6/4/2024
Green Tag Expire Date: 12/31/2026
MFD Type: Fleet

Owner Details

Owner Name: Village of Hanover Park
Owner Address: 2121 W. Lake Street Hanover Park, IL 60103
Owner Status: Current Owner
Purchase Date:
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 3/2/2027

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0006425 Village of Hanover Park Current Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violations (Current)

NOV Number: E0020261673 (Pending)    Issue Date: 6/26/2026    Expiration Date: 8/25/2026    View NOV Form

Tanks Violations
2, 5 Line interstitial sensors have been raised and rendered inoperational. - 175.640 a) 2) All new and existing sump sensors must be installed so as to detect liquid per manufacturer's specifications or, if not specified by the manufacturer, at the lowest point in the sump.
1 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. - 175.405 a) 1) A) Spill containment equipment that will prevent release of product to the environment when the transfer hose is detached from the fill pipe (e.g., a spill catch basin). Spill containment equipment shall be maintained in a dry, clean state.
2, 5 Water in containment with required interstitial sensors - Remove water and repair containments to prevent water ingress. - Both STP sumps have liquid in them. Remove liquid. Section 175.410 Submersible, Under-dispenser, Transition and Other Containment Sumps a) All containment sumps must consist of a factory manufactured containment that is liquid-tight on its sides, bottom and at any penetrations and is compatible with the substance conveyed by the piping. Such containment shall also have a factory manufactured protective cover and supporting components that are properly maintained. If the protective cover or its supporting components are cracked, deteriorated or missing, the cover and supporting components that are defective shall be replaced.

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
97-0765 11/7/1997 Removal Log
98-1501 6/23/1998 Removal Log

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
97-0765 Eligible 9/24/1998 11/24/1998 $10,000
Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 8000 Gasoline - Regular Currently in use Federal $0.00
2 4000 Gasoline - Regular Currently in use Federal $0.00
3 2000 Diesel Fuel Removed Federal $0.00 06/23/1998 - REM
4 500 Used Oil Removed Federal $0.00 11/07/1997 - REM
5 6000 Diesel Fuel Currently in use Federal $0.00


Dispenser Information

Name\ID Status
3/4 Active
1/2 Active


MFD Motorfuel Dispensing Forms

No Forms Found