Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2000851
Status: Active
Facility Name: Ozinga Bros, Inc
Address: 1819 N. Dot Street
McHenry, IL 600506586
County: McHenry
Property Parcel:
Facility Type: Industrial / Manufacturing
Owner Type: Private
Green Tag Decal: Y003963
Green Tag Issue Date: 6/12/2023
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: Meyer Material Company
Owner Address: 1300 S. IL Route 31
South Elgin, IL 60050
Owner Status: Current Owner
Purchase Date: 4/1/1996
Type of Financial Responsibility: Certificate of Deposit
Financial Responsibility Reporting Due Date: 4/2/2026

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Fleet 3/28/2025 12/31/2027

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0010204 Meyer Material Company Current Owner 4/1/1996
U0009991 Mchenry Sand & Gravel Co Inc Former Owner 12/31/1967

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violations (Current)

NOV Number: E0020250890 (Pending)    Issue Date: 3/28/2025    Expiration Date: 5/27/2025    View NOV Form

Tanks Violation
Facility Fire Extinguishers - 2 4A:60BC extinguishers not provided - Provide min of 2 fire extinguishers (4A:60 BC rated), installed to provide access to both employees and customers.

NOV Number: E0020250891 (Pending)    Issue Date: 4/2/2025    Expiration Date: 6/1/2025    View NOV Form

Tanks Violation
Facility Emergency contact information for A/B & C Operators not posted at unmanned facility - Contact information is not up to date, has previous AB Operator and phone#.
Facility Financial responsibility must be reported yearly - Financial Responsibility shall be declared annually; The form can be found at https://webapps.sfm.illinois.gov/USTPortal/Forms/FinancialResponsibility.
Facility Missing copies of 30 day Walkthrough Inspection Report. - 30-day Walkthrough Inspection shall be completed, and 2 years of documentation maintained on site. 30-Day Walkthrough Inspection form available at www.sfm.illinois.gov. The form must be filled out by an A/B Operator, you must, initial each box that applies, date the form each month to ensure it is being done every 30 days, and the A/B operator must print and sign their name at the bottom. If more than one A/B operator fills out the form, then each must print and sign name at the bottom.
Facility Missing list of designated Class A/B & C Operators - LIST NOT UPDATED
9 Monthly line interstitial sensor records not available. - Maintain one NORMAL report per LINE, per month, from ATG. Must maintain 24 months’ worth.
9 Precision tank test required. - Precision tank test is required on tank(s) if you cannot provide 24 months’ worth of tank “NORMAL” from ATG.
9 Required monthly tank interstitial sensor records not available. - Maintain one PASSing report per TANK, per month, from ATG. Must maintain 24 months’ worth.

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
96-0447 3/28/1996 Removal Log
96-0477 3/29/1996 Removal Log

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
96-0494 Eligible 6/19/2000 7/7/2000 $10,000
96-0449 Eligible 6/19/2000 7/7/2000 $10,000
Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 15000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 3/19/1996
OSFM First Notify Date: 1/16/1986 Abandoned Material:
Current Age: 16 Abandoned Date:
Install Date: 4/1/1979 Red Tag Issue Date:
Last Used Date: 3/1/1996 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 2

Capacity: 15000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 3/19/1996
OSFM First Notify Date: 1/16/1986 Abandoned Material:
Current Age: 16 Abandoned Date:
Install Date: 4/1/1979 Red Tag Issue Date:
Last Used Date: 3/1/1996 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 3

Capacity: 15000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 3/19/1996
OSFM First Notify Date: 1/16/1986 Abandoned Material:
Current Age: 16 Abandoned Date:
Install Date: 4/1/1979 Red Tag Issue Date:
Last Used Date: 3/1/1996 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 4

Capacity: 8000 Petroleum Use: Back-up Generator
Product: Diesel Fuel CERCLA Substance:
Status: Abandoned in place CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 1/16/1986 Abandoned Material: Inert material mixed with portland cement
Current Age: 46 Abandoned Date: 7/29/1996
Install Date: 4/1/1979 Red Tag Issue Date:
Last Used Date: 3/27/1996 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 5

Capacity: 8000 Petroleum Use: Back-up Generator
Product: Diesel Fuel CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 3/28/1996
OSFM First Notify Date: 1/16/1986 Abandoned Material:
Current Age: 16 Abandoned Date:
Install Date: 4/1/1979 Red Tag Issue Date:
Last Used Date: 3/1/1996 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 6

Capacity: 3000 Petroleum Use:
Product: Used Oil CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 3/28/1996
OSFM First Notify Date: 1/16/1986 Abandoned Material:
Current Age: 16 Abandoned Date:
Install Date: 4/1/1979 Red Tag Issue Date:
Last Used Date: 3/1/1996 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 7

Capacity: 3000 Petroleum Use:
Product: Used Oil CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 3/28/1996
OSFM First Notify Date: 1/16/1986 Abandoned Material:
Current Age: 16 Abandoned Date:
Install Date: 4/1/1979 Red Tag Issue Date:
Last Used Date: 3/1/1996 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 8

Capacity: 10000 Petroleum Use: Consumptive Use on Premises for Heating
Product: Heating Oil CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: State Removed Date: 3/29/1996
OSFM First Notify Date: 1/16/1986 Abandoned Material:
Current Age: 16 Abandoned Date:
Install Date: 4/1/1979 Red Tag Issue Date:
Last Used Date: 1/1/1986 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 9

Capacity: 15000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 5/9/1996 Abandoned Material:
Current Age: 29 Abandoned Date:
Install Date: 4/1/1996 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 4/1/1996

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 5/9/2025 5/9/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 300c 5/10/2024 5/10/2025
Leak Detect - Tank Hydrostatic Reservoir Interstitial Monitoring Sensors 5/10/2024 5/10/2025
Overfill Prev Device Overfill Drop Tube Valve 5/11/2023 5/11/2026
Piping Fiberglass Double Wall N/A N/A
Piping Single Wall STP/Tanktop Sump 5/10/2024 5/10/2027
Leak Detect - Piping Sump Sensor 5/10/2024 5/10/2025
Spill Contain Device Single Wall Spill Bucket 5/10/2024 5/10/2027
Tank Fiberglass Brine Filled Double Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Precision Test (Piping) Pass 5/9/2025

Dispenser Information



Name\ID 1

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A

MFD Motorfuel Dispensing Forms

No Forms Found