Notice of Violations (Current)
NOV Number:
E0020261763
(Pending)
Issue Date:
7/9/2026
Expiration Date:
9/7/2026
View NOV Form
| Tanks |
Violations |
| Facility |
Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable - The attendant shall always be able to communicate with people in the dispensing area. Repair or replace intercom. Dispensers 3/4 and 7/8. |
NOV Number:
E0020261764
(Pending)
Issue Date:
7/9/2026
Expiration Date:
9/7/2026
View NOV Form
| Tanks |
Violations |
| 4, 5 |
Precision tank test required. - Cannot provide 24 months worth of tank PASS from ATG. |
| 4, 5 |
Required monthly tank interstitial sensor records not available. - Maintain one normal report per tank, per month from ATG,must have 24 months worth. |
| 4, 5 |
Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. - Remove Liquid |
IEMA Numbers Associated with the Facility
| IEMA Number |
Inspection Date |
Inspection Type |
Permit Number |
| 99-0990 |
4/21/1999 |
Removal Log |
00862-1999REM |
LUST
Fund Eligibility and Deductibility Determinations
| IEMA Number |
Status |
OSFM Received Date |
OSFM Response Date |
Deductible |
Letter |
| 99-0990 |
Eligible |
5/23/2001
|
6/20/2001
|
$10,000
|
|
Tank Number 1
| Capacity: |
10000 |
|
Petroleum Use: |
|
| Product: |
Gasoline |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
4/21/1999 |
|
OSFM
First Notify Date: |
1/30/1986 |
|
Abandoned Material: |
|
| Current Age: |
17 |
|
Abandoned Date: |
|
| Install Date: |
7/1/1981 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
12/14/1998 |
|
Fee Due: |
$0.00 |
| Product Date: |
7/1/1981 |
|
|
|
Equipment Information
No Equipment Listed
Additional Tests
No Tests Listed
Tank Number 2
| Capacity: |
10000 |
|
Petroleum Use: |
|
| Product: |
Gasoline |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
4/21/1999 |
|
OSFM
First Notify Date: |
1/30/1986 |
|
Abandoned Material: |
|
| Current Age: |
17 |
|
Abandoned Date: |
|
| Install Date: |
7/1/1981 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
12/14/1998 |
|
Fee Due: |
$0.00 |
| Product Date: |
7/1/1981 |
|
|
|
Equipment Information
No Equipment Listed
Additional Tests
No Tests Listed
Tank Number 3
| Capacity: |
10000 |
|
Petroleum Use: |
|
| Product: |
Gasoline |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
4/21/1999 |
|
OSFM
First Notify Date: |
1/30/1986 |
|
Abandoned Material: |
|
| Current Age: |
17 |
|
Abandoned Date: |
|
| Install Date: |
7/1/1981 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
12/14/1998 |
|
Fee Due: |
$0.00 |
| Product Date: |
7/1/1981 |
|
|
|
Equipment Information
No Equipment Listed
Additional Tests
No Tests Listed
Tank Number 4
| Capacity: |
12000 |
|
Petroleum Use: |
|
| Product: |
Gasoline - Regular |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
8/23/1999 |
|
Abandoned Material: |
|
| Current Age: |
27 |
|
Abandoned Date: |
|
| Install Date: |
5/1/1999 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
7/19/1999 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Flexible Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Mechanical Pressurized Line Leak Detection |
10/30/2025 |
10/30/2026 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 350 |
10/30/2025 |
10/30/2026 |
|
Leak Detect - Tank
|
Non-Discriminating Interstitial Monitoring Sensors |
10/30/2025 |
10/30/2026 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
11/14/2024 |
11/14/2027 |
|
Piping
|
Flexible Double Wall OPW Flexworks |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
1/8/2024 |
1/8/2027 |
Leak Detect - Piping
|
Sump Sensor |
1/8/2024 |
1/8/2027 |
|
Spill Contain Device
|
Single Wall Spill Bucket |
11/14/2024 |
11/14/2027 |
|
Tank
|
Fiberglass Double Wall XERXES |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Flexible Double Wall OPW Flexworks
|
Precision Test (Piping)
|
Pass
|
1/14/2025
|
|
Leak Detect - Piping
|
Sump Sensor
|
Sensor Functional
|
Pass
|
8/17/2009
|
Tank Number 5
| Capacity: |
10000 |
|
Petroleum Use: |
|
| Product: |
Gasoline - Premium |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
8/23/1999 |
|
Abandoned Material: |
|
| Current Age: |
27 |
|
Abandoned Date: |
|
| Install Date: |
5/1/1999 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
7/19/1999 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Flexible Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Mechanical Pressurized Line Leak Detection |
10/30/2025 |
10/30/2026 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 350 |
10/30/2025 |
10/30/2026 |
|
Leak Detect - Tank
|
Non-Discriminating Interstitial Monitoring Sensors |
10/30/2025 |
10/30/2026 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
11/14/2024 |
11/14/2027 |
|
Piping
|
Flexible Double Wall OPW Flexworks |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
1/8/2024 |
1/8/2027 |
Leak Detect - Piping
|
Sump Sensor |
1/8/2024 |
1/8/2027 |
|
Spill Contain Device
|
Double Wall Spill Bucket |
11/14/2024 |
11/14/2027 |
|
Tank
|
Fiberglass Double Wall XERXES |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Flexible Double Wall OPW Flexworks
|
Precision Test (Piping)
|
Pass
|
1/14/2025
|
|
Leak Detect - Piping
|
Sump Sensor
|
Sensor Functional
|
Pass
|
8/17/2009
|
Failed test = the latest test has failed.
Not applicable = a test does not apply to this equipment type or configuration.
No passing test found = a passing test is expected but was not found from the source data.
Dispenser Information
Name\ID 1/2
| Status: |
Active |
|
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Dispenser
|
Single Wall UDC Sump |
Not applicable
|
Not applicable
|
Leak Detect - Piping
|
Piping Sump Sensors Not Regulated Not Required |
Not applicable
|
Not applicable
|
Name\ID 3/4
| Status: |
Active |
|
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Dispenser
|
Single Wall UDC Sump |
Not applicable
|
Not applicable
|
Leak Detect - Piping
|
Piping Sump Sensors Not Regulated Not Required |
Not applicable
|
Not applicable
|
Name\ID 5/6
| Status: |
Active |
|
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Dispenser
|
Single Wall UDC Sump |
Not applicable
|
Not applicable
|
Leak Detect - Piping
|
Piping Sump Sensors Not Regulated Not Required |
Not applicable
|
Not applicable
|
Name\ID 7/8
| Status: |
Active |
|
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Dispenser
|
Single Wall UDC Sump |
Not applicable
|
Not applicable
|
Leak Detect - Piping
|
Piping Sump Sensors Not Regulated Not Required |
Not applicable
|
Not applicable
|
Failed test = the latest test has failed.
Not applicable = a test does not apply to this equipment type or configuration.
No passing test found = a passing test is expected but was not found from the source data.
MFD
Motorfuel Dispensing Forms
No Forms Found