Division of Petroleum & Chemical Safety

 
Pay Tank Fees Online Print Detail Page Export to Excel

Facility Details

Facility Number: 2000692
Status: Active
Facility Name: Dyana, LLC
Address: 8401 N. Milwaukee Niles, IL 60714
County: Cook
Property Parcel: 09-24-114-042-0000
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y002141
Green Tag Issue Date: 1/31/2024
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: Dyana, LLC
Owner Address: 8401 North Milwaukee Avenue Niles, IL 60714
Owner Status: Current Owner
Purchase Date: 5/5/2017
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 8/31/2024

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 1/31/2024 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0039133 Dyana, LLC Current Owner 5/5/2017
U0038699 Zabadneh, Mohammed Former Owner 1/30/2017
U0037584 Palli Enterprises Corp. Former Owner 11/15/2014
U0007968 Joe's Service, Inc. Former Owner 8/1/1983

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020252801 (Pending)    Issue Date: 10/22/2025    Expiration Date: 12/21/2025    View NOV Form

Tanks Violations
Facility A/B operator retraining required as a result of issuance of the Notice of Violation - Primary A / B certified operator shall be retrained as a result of this NOV being issued.
Facility Annual Emergency Stop Inspection not completed or inspection report not available. - All emergency shutoff switches shall be tested annually to verify they shut down all STPs or dispensers. Perform test, complete form (form is available at www.sfm.illinois.gov) and maintain 2 years on site with other annual testing documentation.
14 Annual leak detection certification not completed (Required annually). - Annual leak detection certification (interstitial sensors/ATG) not completed. Testing shall be completed and submitted to OSFM.
14 Annual leak detection certification not completed (Required annually). - Annual leak detection certification (leak detectors and/or interstitial sensors) not completed. Testing shall be performed.
15 Annual leak detection certification not completed (Required annually). - Annual leak detection certification (interstitial sensors/ATG) not completed. Testing shall be completed and submitted to OSFM.
15 Annual leak detection certification not completed (Required annually). - Annual leak detection certification (leak detectors and/or interstitial sensors) not completed. Testing shall be performed.
16 Annual leak detection certification not completed (Required annually). - Annual leak detection certification (interstitial sensors/ATG) not completed. Testing shall be completed and submitted to OSFM.
16 Annual leak detection certification not completed (Required annually). - Annual leak detection certification (leak detectors and/or interstitial sensors) not completed. Testing shall be performed.
17 Annual leak detection certification not completed (Required annually). - Annual leak detection certification (interstitial sensors/ATG) not completed. Testing shall be completed and submitted to OSFM.
17 Annual leak detection certification not completed (Required annually). - Annual leak detection certification (leak detectors and/or interstitial sensors) not completed. Testing shall be performed.
Facility Financial responsibility must be reported yearly - Financial Responsibility shall be declared annually, and must be maintained until the tanks are removed or properly abandoned in place by a licensed UST decommissioning contractor. The form can be found at: https://webapps.sfm.illinois.gov/USTPortal/Forms/FinancialResponsibility.
14, 16 Line interstitial sensors have been raised and rendered inoperational. - Interstitial sensor(s) has/have been raised rendering it/them ineffective. Repair/replace sensor(s) into proper location so that it can function as designed.
Facility Miscellaneous - EMERGENGENCY STOP SWITCH AT CONTROL STATION NOT PROPERLY MARKED. Provide and install appropriate sign identifying emergency shutoff switch location.
Facility Missing copies of 30 day Walkthrough Inspection Report. - 30-day Walkthrough Inspection shall be completed, and 2 years of documentation maintained on site. 30-Day Walkthrough Inspection form available at www.sfm.illinois.gov. The form must be filled out by an A/B Operator, you must, initial each box that applies, date the form each month to ensure it is being done every 30 days, and the A/B operator must print and sign their name at the bottom. If more than one A/B operator fills out the form, then each must print and sign name at the bottom.
Facility Missing copies of Annual Walkthrough Inspection Report. - Annual Walkthrough by a licensed contractor shall be conducted and 2 years documentation maintained on site.
14, 15, 16, 17 Monthly line interstitial sensor records not available. - Maintain one NORMAL report per LINE, per month, from ATG. Must maintain 24 months’ worth.
14, 15, 16, 17 Precision tank test required. - Precision tank test is required on tank(s) if you cannot provide 24 months’ worth of tank “NORMAL” from ATG.
14, 15, 16, 17 Required monthly tank interstitial sensor records not available. - Maintain one NORMAL report per TANK, per month, from ATG. Must maintain 24 months’ worth.
14, 15, 16, 17 Shear valve inspection report not completed (Required during Annual Walkthrough Inspection). - Provide documentation that annual testing of all shear valves has been conducted and passed. Must maintain 2 years of inspection reports.
14, 16, 17 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry.
14, 16 Stick inserted in drop tube overfill device rendering it inoperative - Remove stick. - A tank depth gauge stick is in the drop tube: remove stick to maintain proper operation of drop tube valve.
15, 16, 17 Tank monitor does not appear to function properly and requires maintenance. - Interstitial sensor in alarm on ATG; Repair/replace sensor as necessary clear alarm. L6 : SENSOR OUT ALARM ( INTERSTITIAL SENSOR ON SPLIT TANK).
14, 15, 16, 17 Triennial spill prevention equipment testing not completed. - Triennial inspection/testing of spill bucket(s) has not been completed. Testing shall be completed with passing results uploaded to OSFM.
14, 15, 16, 17 Triennial testing for qualifying piping containment sump not completed (Required every 3 years). - Triennial testing for qualifying STP/dispenser piping containment sump(s) not completed. Testing shall be completed and submitted to OSFM.
14, 16 Water in containment with required interstitial sensors - Remove water and repair containments to prevent water ingress. - STP sumps contain liquid, sensors raised out of liqid. Remove liquid and repair containment to prevent further liquid ingress. Replace sensors to proper position.

NOV Number: E0020252802 (Pending)    Issue Date: 10/22/2025    Expiration Date: 12/21/2025    View NOV Form

Tanks Violations
Facility Fire Extinguishers - 2 4A:60BC extinguishers not provided - Provide min of 2 fire extinguishers (4A:60 BC rated), installed to provide access to both employees and customers.

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
18-0296 3/28/2018 Removal Log 00130-2018REM
18-0296 3/29/2018 Removal Log 00130-2018REM
18-0296 3/30/2018 Emergency Response

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
19912913 Eligible 3/10/2017 3/10/2017 $15,000 Letter
20180296 Eligible 4/10/2018 4/16/2018 $5,000 Letter
Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 8000 Gasoline Removed Federal $0.00 03/29/2018 - REM
2 8000 Gasoline Removed Federal $0.00 03/28/2018 - REM
3 8000 Gasoline Removed Federal $0.00 03/28/2018 - REM
4 6000 Diesel Fuel Removed Federal $0.00 03/28/2018 - REM
8 1000 Used Oil Removed Federal $0.00 03/29/2018 - REM
9 500 Used Oil Removed Federal $0.00 03/29/2018 - REM
10 6000 Gasoline Removed Exempt 09/01/1987 - REM
11 6000 Gasoline Removed Exempt 09/01/1987 - REM
12 6000 Gasoline Removed Exempt 09/01/1987 - REM
13 6000 Gasoline Removed Federal $0.00 03/29/2018 - REM
14 15000 Gasoline - Regular Currently in use Federal $0.00
15 4000 Gasoline - Premium Currently in use Federal $0.00
16 4000 Diesel Fuel Currently in use Federal $0.00
17 4000 E85 Currently in use Federal $0.00

Dispenser Information

Name\ID Status
1/2 Active
3/4 Active
5/6 Active
7/8 Active
9/10 Active

MFD Motorfuel Dispensing Forms

No Forms Found