Notice of Violations (Current)
NOV Number:
E0020250364
(Pending)
Issue Date:
2/11/2025
Expiration Date:
4/12/2025
View NOV Form
Tanks |
Violation |
1 |
Install corrosion protection under dispensers to protect exposed flex connectors and other metal portions of product piping. - Containment under the dispenser is full of water high enough to cover exposed metal piping. An alternative to installing corrosion protection would be to remove the water and repair the containment for it to remain dry. See attached paperwork in regards to regulation change taking effect October 2028 and using corrosion protection. If containment is to be repaired please provide associated paperwork. |