Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2000428
Status: Active
Facility Name: Mohsen Oil, Inc.
Address: 24001 W. Lorenzo Road Wilmington, IL 60481
County: Will
Property Parcel: 03-17-16-200-011-0000
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Z000597
Green Tag Issue Date: 12/9/2024
Green Tag Expire Date: 12/31/2026
MFD Type: N/A

Owner Details

Owner Name: Mohsen, Inc.
Owner Address: 3213 Mission Avenue Oceanside, CA 92058
Owner Status: Current Owner
Purchase Date: 12/17/2018
Type of Financial Responsibility: Guarantee
Financial Responsibility Reporting Due Date: 10/1/2026

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0039608 Mohsen, Inc. Current Owner 12/17/2018
U0029432 Shazad, Inc. Former Owner 3/20/2000
U0035760 Mobil Truck Stop, Inc. Former Owner
U0012800 Karnezis River Restaurant Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violations (Current)

NOV Number: E0020262275 (Pending)    Issue Date: 9/11/2026    Expiration Date: 11/10/2026    View NOV Form

Tanks Violations
8 Annual line precision and mechanical line leak detector functional test not completed. - Equipment: Leak Detect - Piping - Mechanical Pressurized Line Leak Detection Last tested 8/11/2025
Facility Facility Operation and Maintenance Plan not completed or available.
Facility Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable
Facility Missing copies of 30 day Walkthrough Inspection Report.
Facility Missing copies of Annual Walkthrough Inspection Report.
Facility Missing copy of emergency instructions or emergency procedures plan
Facility Missing list of designated Class A/B & C Operators
8 Precision line test required. - Equipment: Leak Detect - Piping - Mechanical Pressurized Line Leak Detection
13, 14 Tank interstitial sensor functional test not accomplished (Required annually). - Equipment: Leak Detect - Tank - Non-Discriminating Interstitial Monitoring Sensors Last test 8/11/2025
7, 12 Triennial spill prevention equipment testing not completed. - Equipment: Spill Contain Device - Single Wall Spill Bucket Tank 7 last test was 6/19/2023 Tank 12 last test was 9/5/2019

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
07-0417 3/31/2008 Removal Log 01958-2007REM

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
08-0417 Eligible 5/8/2015 6/3/2015 $15,000
Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 6000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 3/31/2008
OSFM First Notify Date: 1/13/1986 Abandoned Material:
Current Age: 19 Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment Information

No Equipment Listed


Additional Tests

No Tests Listed




Tank Number 2

Capacity: 6000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 3/31/2008
OSFM First Notify Date: 1/13/1986 Abandoned Material:
Current Age: 31 Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment Information

No Equipment Listed


Additional Tests

No Tests Listed




Tank Number 3

Capacity: 6000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 3/31/2008
OSFM First Notify Date: 1/13/1986 Abandoned Material:
Current Age: 31 Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment Information

No Equipment Listed


Additional Tests

No Tests Listed




Tank Number 4

Capacity: 6000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 3/31/2008
OSFM First Notify Date: 1/13/1986 Abandoned Material:
Current Age: 31 Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment Information

No Equipment Listed


Additional Tests

No Tests Listed




Tank Number 5

Capacity: 12000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 11/1/1987
OSFM First Notify Date: 1/13/1986 Abandoned Material:
Current Age: 27 Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: 10/1/1987 Fee Due: $0.00
Product Date:

Equipment Information

No Equipment Listed


Additional Tests

No Tests Listed




Tank Number 6

Capacity: 12000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 3/31/2008
OSFM First Notify Date: 1/22/1991 Abandoned Material:
Current Age: 20 Abandoned Date:
Install Date: 11/6/1987 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment Information

No Equipment Listed


Additional Tests

No Tests Listed




Tank Number 7

Capacity: 12000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 4/3/2008 Abandoned Material:
Current Age: 18 Abandoned Date:
Install Date: 2/1/2007 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 2/1/2008

Equipment Information

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive Not applicable Not applicable
Corrosion Prot - Tank Fiberglass Non-Corrosive Not applicable Not applicable
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 8/12/2026 8/12/2027
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 Plus 8/12/2026 8/12/2027
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 8/12/2026 8/12/2027
Overfill Prev Device Overfill Drop Tube Valve 8/12/2026 8/12/2029
Piping Flexible Double Wall A.P.T. Poly Tech P175SC Not applicable Not applicable
Piping Flexible Double Wall A.P.T. Poly Tech XP 1500 Not applicable Not applicable
Piping Single Wall STP/Tanktop Sump 8/12/2026 8/12/2029
Leak Detect - Piping Sump Sensor 8/12/2026 8/12/2029
Spill Contain Device Single Wall Spill Bucket 10/30/2026 10/30/2029
Tank Fiberglass Double Wall XERXES Not applicable Not applicable

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall A.P.T. Poly Tech P175SC Precision Test (Piping) Pass 8/12/2026
Piping Flexible Double Wall A.P.T. Poly Tech XP 1500 Precision Test (Piping) Pass 11/16/2023
Tank Fiberglass Double Wall XERXES Precision Test (Tank) Pass 9/5/2019



Tank Number 8

Capacity: 8000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 4/3/2008 Abandoned Material:
Current Age: 18 Abandoned Date:
Install Date: 2/1/2007 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 2/1/2008

Equipment Information

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive Not applicable Not applicable
Corrosion Prot - Tank Fiberglass Non-Corrosive Not applicable Not applicable
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 10/30/2026 10/30/2027
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 Plus 8/12/2026 8/12/2027
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 8/12/2026 8/12/2027
Overfill Prev Device Overfill Drop Tube Valve 8/12/2026 8/12/2029
Piping Flexible Double Wall A.P.T. Poly Tech P175SC Not applicable Not applicable
Piping Flexible Double Wall A.P.T. Poly Tech XP 1500 Not applicable Not applicable
Piping Single Wall STP/Tanktop Sump 8/12/2026 8/12/2029
Leak Detect - Piping Sump Sensor 8/12/2026 8/12/2029
Spill Contain Device Single Wall Spill Bucket 8/12/2026 8/12/2029
Tank Fiberglass Double Wall XERXES Not applicable Not applicable

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall A.P.T. Poly Tech P175SC Precision Test (Piping) Pass 8/12/2026
Piping Flexible Double Wall A.P.T. Poly Tech XP 1500 Precision Test (Piping) Pass 11/16/2023
Tank Fiberglass Double Wall XERXES Precision Test (Tank) Pass 9/5/2019



Tank Number 9

Capacity: 500 Petroleum Use:
Product: Heating Oil CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: State Removed Date: 9/19/2006
OSFM First Notify Date: Abandoned Material:
Current Age: Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: 12/1/1973 Fee Due:
Product Date:

Equipment Information

No Equipment Listed


Additional Tests

No Tests Listed




Tank Number 10

Capacity: 8000 Petroleum Use:
Product: E85 CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 4/3/2008 Abandoned Material:
Current Age: 18 Abandoned Date:
Install Date: 2/1/2007 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 2/1/2008

Equipment Information

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive Not applicable Not applicable
Corrosion Prot - Tank Fiberglass Non-Corrosive Not applicable Not applicable
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 8/12/2026 8/12/2027
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 Plus 8/12/2026 8/12/2027
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 8/12/2026 8/12/2027
Overfill Prev Device Overfill Drop Tube Valve 8/12/2026 8/12/2029
Piping Flexible Double Wall A.P.T. Poly Tech P175SC Not applicable Not applicable
Piping Single Wall STP/Tanktop Sump 8/12/2026 8/12/2029
Leak Detect - Piping Sump Sensor 8/12/2026 8/12/2029
Spill Contain Device Single Wall Spill Bucket 8/12/2026 8/12/2029
Tank Fiberglass Double Wall XERXES Not applicable Not applicable

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall A.P.T. Poly Tech P175SC Precision Test (Piping) Pass 8/12/2026
Tank Fiberglass Double Wall XERXES Precision Test (Tank) Pass 9/5/2019



Tank Number 11

Capacity: 4000 Petroleum Use: None
Product: Kerosene CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 4/3/2008 Abandoned Material:
Current Age: 18 Abandoned Date:
Install Date: 2/1/2007 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 2/1/2008

Equipment Information

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive Not applicable Not applicable
Corrosion Prot - Tank Fiberglass Non-Corrosive Not applicable Not applicable
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 8/12/2026 8/12/2027
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 Plus 8/12/2026 8/12/2027
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 8/12/2026 8/12/2027
Overfill Prev Device Overfill Drop Tube Valve 8/12/2026 8/12/2029
Piping Flexible Double Wall A.P.T. Poly Tech P175SC Not applicable Not applicable
Piping Single Wall STP/Tanktop Sump 8/12/2026 8/12/2029
Leak Detect - Piping Sump Sensor 8/12/2026 8/12/2029
Spill Contain Device Double Wall Spill Bucket 8/12/2026 8/12/2029
Tank Fiberglass Double Wall XERXES Not applicable Not applicable

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall A.P.T. Poly Tech P175SC Precision Test (Piping) Pass 8/12/2026
Tank Fiberglass Double Wall XERXES Precision Test (Tank) Pass 7/13/2023



Tank Number 12

Capacity: 4000 Petroleum Use: None
Product: Racing Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 4/3/2008 Abandoned Material:
Current Age: 18 Abandoned Date:
Install Date: 2/1/2007 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 2/1/2008

Equipment Information

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive Not applicable Not applicable
Corrosion Prot - Tank Fiberglass Non-Corrosive Not applicable Not applicable
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 8/12/2026 8/12/2027
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 Plus 8/12/2026 8/12/2027
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 8/12/2026 8/12/2027
Overfill Prev Device Overfill Drop Tube Valve 8/12/2026 8/12/2029
Piping Flexible Double Wall A.P.T. Poly Tech P175SC Not applicable Not applicable
Piping Single Wall STP/Tanktop Sump 8/12/2026 8/12/2029
Leak Detect - Piping Sump Sensor with positive shutdown 8/12/2026 8/12/2029
Spill Contain Device Double Wall Spill Bucket 8/12/2026 8/12/2029
Spill Contain Device Single Wall Spill Bucket 9/5/2019 9/5/2022
Tank Fiberglass Double Wall XERXES Not applicable Not applicable

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall A.P.T. Poly Tech P175SC Precision Test (Piping) Pass 8/12/2026
Tank Fiberglass Double Wall XERXES Precision Test (Tank) Pass 1/21/2026



Tank Number 13

Capacity: 9000 Petroleum Use: None
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 4/6/2010 Abandoned Material:
Current Age: 18 Abandoned Date:
Install Date: 5/29/2008 Red Tag Issue Date:
Last Used Date: Fee Due:
Product Date: 10/24/2008

Equipment Information

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive Not applicable Not applicable
Corrosion Prot - Tank Composite Non-Corrosive Not applicable Not applicable
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 8/12/2026 8/12/2027
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 Plus 8/12/2026 8/12/2027
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 10/30/2026 10/30/2027
Overfill Prev Device Overfill Drop Tube Valve 8/12/2026 8/12/2029
Piping Flexible Double Wall A.P.T. Poly Tech P200SC Not applicable Not applicable
Piping Single Wall STP/Tanktop Sump 8/12/2026 8/12/2029
Leak Detect - Piping Sump Sensor 8/12/2026 8/12/2029
Spill Contain Device Single Wall Spill Bucket 8/12/2026 8/12/2029
Tank Composite Double Wall Lannon Not applicable Not applicable

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall A.P.T. Poly Tech P200SC Precision Test (Piping) Pass 8/12/2026
Tank Composite Double Wall Lannon Precision Test (Tank) Pass 9/5/2019



Tank Number 14

Capacity: 11000 Petroleum Use: None
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 4/6/2010 Abandoned Material:
Current Age: 18 Abandoned Date:
Install Date: 5/29/2008 Red Tag Issue Date:
Last Used Date: Fee Due:
Product Date: 10/24/2008

Equipment Information

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive Not applicable Not applicable
Corrosion Prot - Tank Composite Non-Corrosive Not applicable Not applicable
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 8/12/2026 8/12/2027
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 Plus 8/12/2026 8/12/2027
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 10/30/2026 10/30/2027
Overfill Prev Device Overfill Drop Tube Valve 8/12/2026 8/12/2029
Piping Flexible Double Wall A.P.T. Poly Tech P200SC Not applicable Not applicable
Piping Single Wall STP/Tanktop Sump 8/12/2026 8/12/2029
Leak Detect - Piping Sump Sensor 8/12/2026 8/12/2029
Spill Contain Device Double Wall Spill Bucket 8/12/2026 8/12/2029
Tank Composite Double Wall Lannon Not applicable Not applicable

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall A.P.T. Poly Tech P200SC Precision Test (Piping) Pass 8/12/2026
Tank Composite Double Wall Lannon Precision Test (Tank) Pass 7/13/2023



Tank Number 15

Capacity: 500 Petroleum Use: Consumptive Use on Premises for Heating
Product: Heating Oil CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Exempt Removed Date: 9/12/2008
OSFM First Notify Date: Abandoned Material:
Current Age: Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: 12/31/1973 Fee Due: $0.00
Product Date:

Equipment Information

No Equipment Listed


Additional Tests

No Tests Listed


Failed test = the latest test has failed.

Not applicable = a test does not apply to this equipment type or configuration.

No passing test found = a passing test is expected but was not found from the source data.


Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 8/12/2026 8/12/2029
Leak Detect - Piping Sump Sensor 8/12/2026 8/12/2027



Name\ID 11

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 6/19/2023 6/19/2026
Leak Detect - Piping Sump Sensor 8/11/2025 8/11/2026



Name\ID 12

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 8/12/2026 8/12/2029
Leak Detect - Piping Sump Sensor 8/12/2026 8/12/2027



Name\ID 13

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 8/12/2026 8/12/2029
Leak Detect - Piping Sump Sensor 8/12/2026 8/12/2027



Name\ID 14

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 8/12/2026 8/12/2029
Leak Detect - Piping Sump Sensor 8/12/2026 8/12/2027



Name\ID 15

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 8/12/2026 8/12/2029
Leak Detect - Piping Sump Sensor 8/12/2026 8/12/2027



Name\ID 16

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 8/12/2026 8/12/2029
Leak Detect - Piping Sump Sensor 8/12/2026 8/12/2027



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 8/12/2026 8/12/2029
Leak Detect - Piping Sump Sensor 8/12/2026 8/12/2027



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 8/12/2026 8/12/2029
Leak Detect - Piping Sump Sensor 8/12/2026 8/12/2027



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 8/12/2026 8/12/2029
Leak Detect - Piping Sump Sensor 8/12/2026 8/12/2027



Name\ID 9/10

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 8/12/2026 8/12/2029
Leak Detect - Piping Sump Sensor 8/12/2026 8/12/2027

Failed test = the latest test has failed.

Not applicable = a test does not apply to this equipment type or configuration.

No passing test found = a passing test is expected but was not found from the source data.


MFD Motorfuel Dispensing Forms

No Forms Found