Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2000204
Status: Active
Facility Name: Urmi Properties, LLC / Mobil
Address: 14030 S. Western Ave. Posen, IL 60469
County: Cook
Property Parcel: 29-06-303-004-0000
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y000226
Green Tag Issue Date: 2/6/2024
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: Urmi Properties, LLC
Owner Address: 14030 S. Western Avenue Posen, IL 60469
Owner Status: Current Owner
Purchase Date: 10/20/2014
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 7/28/2026

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 2/6/2024 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0038843 Urmi Properties, LLC Current Owner 10/20/2014
U0037915 LAXMI 10, Inc. Former Owner 8/1/2014
U0035501 VBS Petroleum Former Owner 9/3/2009
U0023719 Nash Petroleum Inc. Former Owner 6/14/1988
U0014345 St Demetrios Church Former Owner 12/31/1967

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020252478 (Pending)    Issue Date: 9/22/2025    Expiration Date: 11/21/2025    View NOV Form

Tanks Violations
Facility Facility Operation and Maintenance Plan not completed or available. - Need to fill it out completely.
Facility Miscellaneous - Inside Emergency stop is blocked. Need to have an easily accessible emergency stop.
5 Miscellaneous - Equipment in disrepair 176.410
6 Miscellaneous - Need to verify positive shutdown is programmed and tested. Reference 175.640 a)1)
Facility Missing copies of 30 day Walkthrough Inspection Report. - Shall be completed, and documentation maintained on site. 30-Day Walkthrough Inspection form available at https://sfm.illinois.gov/content/dam/soi/en/web/sfm/sfmdocuments/documents/30-day-walkthrough-inspection-report.pdf
Facility Missing copy of emergency instructions or emergency procedures plan - Need to fill out completely.
Facility Missing list of designated Class A/B & C Operators - Need to fill out.
5, 6 Monthly line interstitial sensor records not available. - Maintain one NORMAL report per LINE, per month, from ATG. (Liquid Status)
6 Open electrical conduit or junction boxes. - Premium Tank Interstial junction box cap is missing exposing wires. Need to replace junction box cap.
5, 6 Piping interstitial must be open in all sumps - The dispenser product piping sump jumper tubes shall be removed or the product piping test boots pulled back after testing to allow the interstice to be open to the sump sensors. 175.420 b)
5, 6 Precision tank test required. - Due to missing monthly interstial tapes and multiple failing tank test tapes.
5, 6 Required monthly tank interstitial sensor records not available. - Maintain one NORMAL report per TANK, per month, from ATG. (Liquid Status)
5, 6 Required monthly tank leak test records not available. - Missing monthly passing Tank tapes.
5, 6 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. - Spill buckets need to be clean and dry.
Facility Submit Notification Form for Facility Information Change - The Notification Form is available at https://webapps.sfm.illinois.gov/USTPortal/NotificationForm. The name of the new OPERATOR is Laxmi 10, INC.
Facility Submit Notification Form For Ownership Change - The Notification Form is available at https://webapps.sfm.illinois.gov/USTPortal/NotificationForm. Select “New Owner” as the type of notification form. ( Urmi Properties, LLC was dissolved in 2021)
5, 6 Water in containment with required interstitial sensors - Remove water and repair containments to prevent water ingress. - Rul STP has a small amount of water.

NOV Number: E0020252479 (Pending)    Issue Date: 9/22/2025    Expiration Date: 11/21/2025    View NOV Form

Tanks Violations
Facility Code complying instruction/warning signs are not properly mounted at each dispenser island - Minimum signage is not up to code. Reference 175.210 o)
Facility Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable - Intercom system not functional; repair/replace as necessary to provide communication at dispensers. Reference 175.210 h)

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
98-1962 11/23/1998 Removal Log 4646-98

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
98-1962 Partial Eligible 6/25/1999 7/8/1999 $10,000
19981962 Partial Eligible 8/7/2017 8/8/2017 $10,000 Letter
Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 12000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 11/23/1998
OSFM First Notify Date: 1/6/1986 Abandoned Material:
Current Age: 20 Abandoned Date:
Install Date: 1/1/1979 Red Tag Issue Date:
Last Used Date: 10/10/1998 Fee Due: $0.00
Product Date: 1/1/1978

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 2

Capacity: 6000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 11/23/1998
OSFM First Notify Date: 1/6/1986 Abandoned Material:
Current Age: 20 Abandoned Date:
Install Date: 1/1/1978 Red Tag Issue Date:
Last Used Date: 10/10/1998 Fee Due: $0.00
Product Date: 1/1/1978

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 3

Capacity: 12000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Exempt Removed Date: 11/23/1998
OSFM First Notify Date: 6/25/1999 Abandoned Material:
Current Age: Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: 1/1/1972 Fee Due:
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 4

Capacity: 4000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Exempt Removed Date: 11/23/1998
OSFM First Notify Date: 6/25/1999 Abandoned Material:
Current Age: Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: 1/1/1972 Fee Due:
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 5

Capacity: 12000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 6/25/1999 Abandoned Material:
Current Age: 26 Abandoned Date:
Install Date: 2/2/1999 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 2/2/1999

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 1/3/2025 1/3/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 300 1/3/2025 1/3/2026
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 1/3/2025 1/3/2026
Overfill Prev Device Overfill Drop Tube Valve 2/1/2024 2/1/2027
Piping Flexible Double Wall Environ Geo Flex N/A N/A
Piping Single Wall STP/Tanktop Sump 12/19/2023 12/19/2026
Leak Detect - Piping Sump Sensor 1/3/2025 1/3/2026
Spill Contain Device Double Wall Spill Bucket 2/1/2024 2/1/2027
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall Environ Geo Flex Precision Test (Piping) Pass 1/3/2025
Tank Fiberglass Double Wall XERXES Precision Test (Tank) Pass 9/4/2019



Tank Number 6

Capacity: 6000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 6/25/1999 Abandoned Material:
Current Age: 26 Abandoned Date:
Install Date: 2/2/1999 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 2/2/1999

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 1/3/2025 1/3/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 300 1/3/2025 1/3/2026
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 1/3/2025 1/3/2026
Overfill Prev Device Overfill Drop Tube Valve 2/1/2024 2/1/2027
Piping Flexible Double Wall Environ Geo Flex N/A N/A
Piping Single Wall STP/Tanktop Sump 12/19/2023 12/19/2026
Leak Detect - Piping Sump Sensor 1/3/2025 1/3/2026
Spill Contain Device Double Wall Spill Bucket 2/1/2024 2/1/2027
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall Environ Geo Flex Precision Test (Piping) Pass 1/3/2025
Tank Fiberglass Double Wall XERXES Precision Test (Tank) Pass 9/4/2019

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 12/19/2023 12/19/2026
Leak Detect - Piping Sump Sensor 1/3/2025 1/3/2026



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 12/19/2023 12/19/2026
Leak Detect - Piping Sump Sensor 1/3/2025 1/3/2026

MFD Motorfuel Dispensing Forms

No Forms Found