Annual Emergency Stop Inspection not completed or inspection report not available. - All emergency shutoff switches shall be tested annually to verify they shut down all STPs or dispensers. Perform test, complete form (form is available at www.sfm.illinois.gov) and maintain 2 years on site with other annual testing documentation. |
1, 2, 3 |
Annual leak detection certification not completed (Required annually). - Annual leak detection certification (interstitial sensors/ATG) not completed. Testing shall be completed and submitted to OSFM. |
1, 2, 3 |
Flex connector sacrificial anode system not tested (required every 3 years) - Test anodes and replace as needed - Three-year third-party testing required on sacrificial anode/cathodic protection system. Perform testing and maintain passing documentation on site for review by OSFM Inspector. |
1, 2, 3 |
Mechanical line leak detector requires annual functional test. - Annual third-party precision line and leak detector test is required. |
Facility |
Missing copies of Annual Walkthrough Inspection Report. - Annual Walkthrough by a licensed contractor shall be conducted and 2 years documentation maintained on site. |
1, 2, 3 |
Shear valve inspection report not completed (Required during Annual Walkthrough Inspection). - Provide documentation that annual testing of all shear valves has been conducted and passed. Must maintain 2 years of inspection reports. |