Division of Petroleum & Chemical Safety

 
Pay Tank Fees Online Print Detail Page Export to Excel

Facility Details

Facility Number: 2000179
Status: Active
Facility Name: H & Sons, Inc.
Address: 72 Kimball Street Elgin, IL 60120
County: Kane
Property Parcel: 06-14-234-007
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Z001461
Green Tag Issue Date: 7/3/2024
Green Tag Expiration Date: 12/31/2026

Owner Details

Owner Name: Otto Engineering, Inc.
Owner Address: 2 E. Main St. Carpentersville, IL 60110
Owner Status: Current Owner
Purchase Date: 12/27/2007
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 5/5/2026

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 7/3/2024 12/31/2026

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0035803 Otto Engineering, Inc. Current Owner 12/27/2007
U0033792 H & Sons, Inc. Former Owner 4/1/2004
U0029661 Home State Bank Former Owner
U0016773 Zagone, George Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020252107 (Pending)    Issue Date: 8/14/2025    Expiration Date: 10/13/2025    View NOV Form

Tanks Violations
Facility Annual Emergency Stop Inspection not completed or inspection report not available. - All emergency shutoff switches shall be tested annually to verify they shut down all STPs or dispensers. Perform test, complete form (form is available at www.sfm.illinois.gov) and maintain 2 years on site with other annual testing documentation.
1, 2, 3 Annual leak detection certification not completed (Required annually). - Annual leak detection certification (interstitial sensors/ATG) not completed. Testing shall be completed and submitted to OSFM.
1, 2, 3 Flex connector sacrificial anode system not tested (required every 3 years) - Test anodes and replace as needed - Three-year third-party testing required on sacrificial anode/cathodic protection system. Perform testing and maintain passing documentation on site for review by OSFM Inspector.
1, 2, 3 Mechanical line leak detector requires annual functional test. - Annual third-party precision line and leak detector test is required.
Facility Missing copies of Annual Walkthrough Inspection Report. - Annual Walkthrough by a licensed contractor shall be conducted and 2 years documentation maintained on site.
1, 2, 3 Shear valve inspection report not completed (Required during Annual Walkthrough Inspection). - Provide documentation that annual testing of all shear valves has been conducted and passed. Must maintain 2 years of inspection reports.

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
00-1376 7/17/2000 Removal Log 01048-2000REM
2022-0624 12/12/2022 Abandonment Log 01255-2022ABN

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
00-1376 Eligible 3/27/2001 4/5/2001 $10,000
Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 10000 Gasoline - Regular Currently in use Federal $0.00
2 10000 Gasoline - Premium Currently in use Federal $0.00
3 6000 Diesel Fuel Currently in use Federal $0.00
4 6000 Ultra Low Sulfur Diesel Abandoned in place Federal $0.00 12/12/2022 - ABN
5 2000 Heating Oil Removed State 07/17/2000 - REM
6 2000 Used Oil Removed Exempt 07/17/2000 - REM

Dispenser Information

Name\ID Status
1/2 Active
3/4 Active
5/6 Active
7 Active

MFD Motorfuel Dispensing Forms