Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 1046844
Status: Active
Facility Name: Benny's Corner Market
Address: 601 Flagg Road Rochelle, IL 61068
County: Ogle
Property Parcel: 24-13-177-010
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y003336
Green Tag Issue Date: 9/7/2023
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: HP Rochelle Real Estate, LLC
Owner Address: P.O. Box 67 Rochelle, IL 61068
Owner Status: Current Owner
Purchase Date: 6/11/2019
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 5/30/2026

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 9/7/2023 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0039519 HP Rochelle Real Estate, LLC Current Owner 6/11/2019

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020252044 (Pending)    Issue Date: 8/12/2025    Expiration Date: 10/11/2025    View NOV Form

Tanks Violations
1, 2, 3 Annual electronic line leak detector test not completed.
Facility Annual Emergency Stop Inspection not completed or inspection report not available.
1, 2, 3 Annual leak detection certification not completed (Required annually).
1, 2, 3 Document that emergency shut-off (shear valves) are in proper working order
1, 2, 3 Line interstitial sensor functional test not accomplished (Required annually).
1, 2, 3 Line interstitial sensors have been raised and rendered inoperational. - Dispenser 1/2, 11 and 11 Sat. Contain liquid. Sensors are required to be set at the lowest point in the containment.
Facility Missing copies of Annual Walkthrough Inspection Report. - All testing was due 8/05/2025, contractor was onsite and conducted the annual testing. No results were able to be reviewed and updated.
1, 2, 3 Tank interstitial sensor functional test not accomplished (Required annually).

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 20000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 10/10/2019 Abandoned Material:
Current Age: 6 Abandoned Date:
Install Date: 6/11/2019 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 8/5/2025 8/5/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 Plus 8/5/2025 8/5/2026
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 8/5/2025 8/5/2026
Overfill Prev Device Overfill Alarm 8/16/2022 8/16/2025
Overfill Prev Device Overfill Drop Tube Valve 8/16/2022 8/16/2025
Piping Flexible Double Wall A.P.T. Poly Tech P175SC N/A N/A
Piping Single Wall STP/Tanktop Sump 8/16/2022 8/16/2025
Leak Detect - Piping Sump Sensor with positive shutdown 8/5/2024 8/5/2025
Spill Contain Device Single Wall Spill Bucket 8/16/2022 8/16/2025
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall A.P.T. Poly Tech P175SC Precision Test (Piping) Pass 9/13/2021
Tank Fiberglass Double Wall XERXES Precision Test (Tank) Pass 10/4/2019



Tank Number 2

Capacity: 12000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 10/10/2019 Abandoned Material:
Current Age: 6 Abandoned Date:
Install Date: 6/11/2019 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 8/5/2025 8/5/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 Plus 8/5/2025 8/5/2026
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 8/5/2025 8/5/2026
Overfill Prev Device Overfill Alarm 8/16/2022 8/16/2025
Overfill Prev Device Overfill Drop Tube Valve 8/16/2022 8/16/2025
Piping Flexible Double Wall A.P.T. Poly Tech P175SC N/A N/A
Piping Single Wall STP/Tanktop Sump 8/16/2022 8/16/2025
Leak Detect - Piping Sump Sensor with positive shutdown 8/5/2024 8/5/2025
Spill Contain Device Single Wall Spill Bucket 8/16/2022 8/16/2025
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall A.P.T. Poly Tech P175SC Precision Test (Piping) Pass 9/13/2021
Tank Fiberglass Double Wall XERXES Precision Test (Tank) Pass 10/4/2019



Tank Number 3

Capacity: 8000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 10/10/2019 Abandoned Material:
Current Age: 6 Abandoned Date:
Install Date: 6/11/2019 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 8/5/2025 8/5/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 Plus 8/5/2025 8/5/2026
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 8/5/2025 8/5/2026
Overfill Prev Device Overfill Alarm 8/16/2022 8/16/2025
Overfill Prev Device Overfill Drop Tube Valve 8/16/2022 8/16/2025
Piping Flexible Double Wall A.P.T. Poly Tech P175SC N/A N/A
Piping Single Wall STP/Tanktop Sump 8/16/2022 8/16/2025
Leak Detect - Piping Sump Sensor with positive shutdown 8/5/2024 8/5/2025
Spill Contain Device Single Wall Spill Bucket 8/16/2022 8/16/2025
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall A.P.T. Poly Tech P175SC Precision Test (Piping) Pass 9/13/2021
Tank Fiberglass Double Wall XERXES Precision Test (Tank) Pass 10/4/2019

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 8/16/2022 8/16/2025
Leak Detect - Piping Sump Sensor with positive shutdown 8/5/2024 8/5/2025



Name\ID 11

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 8/16/2022 8/16/2025
Leak Detect - Piping Sump Sensor with positive shutdown 8/5/2024 8/5/2025



Name\ID 11 Satellite

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 8/16/2022 8/16/2025
Leak Detect - Piping Sump Sensor with positive shutdown 8/5/2024 8/5/2025



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 8/16/2022 8/16/2025
Leak Detect - Piping Sump Sensor with positive shutdown 8/5/2024 8/5/2025



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 8/16/2022 8/16/2025
Leak Detect - Piping Sump Sensor with positive shutdown 8/5/2024 8/5/2025



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 8/16/2022 8/16/2025
Leak Detect - Piping Sump Sensor with positive shutdown 8/5/2024 8/5/2025



Name\ID 9/10

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 8/16/2022 8/16/2025
Leak Detect - Piping Sump Sensor with positive shutdown 8/5/2024 8/5/2025

MFD Motorfuel Dispensing Forms

Facility Number Name City Received Date Letter
1046844 Benny's Corner Market Rochelle 10/03/2019 Letter Form