Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 1046826
Status: Active
Facility Name: Thorntons #331
Address: 13555 Willowbrook Rd
Roscoe, IL 61073
County: Winnebago
Property Parcel: 04-15-300-024
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y001252
Green Tag Issue Date: 1/4/2023
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: Thorntons, LLC
Owner Address: 2600 James Thornton Way
Louisville, KY 40245
Owner Status: Current Owner
Purchase Date:
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 2/18/2026

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 1/4/2023 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0039521 Thorntons, LLC Current Owner
U0014995 Thornton's, Inc. - DO NOT USE THIS OWNER ID Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violations (Current)

NOV Number: E0020250703 (Pending)    Issue Date: 3/18/2025    Expiration Date: 5/17/2025    View NOV Form

Tanks Violation
1, 2 Line leak detection equipment in alarm or failed test, must repair or replace. - Leak detector(s) failed annual testing. Repair/replace as necessary. Repaired/replaced leak detector(s) shall be retested to show passing results. FAILED TEST REPORT 3/17/2025
1, 2 Overfill prevention equipment does not appear to function properly. - Overfill device ( overfill alarm) failed inspection. Repair/replace as necessary; FAILED TEST REPORT 3/17/2015

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 30000 Petroleum Use: None
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 8/16/2019 Abandoned Material:
Current Age: 5 Abandoned Date:
Install Date: 5/16/2019 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Other Non-vented check valve N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 3/19/2024 3/17/2025
Leak Detect - Piping Siphon Bar N/A N/A
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 3/17/2025 3/17/2026
Manway At Grade Accessible Manway Accessible at Grade N/A N/A
Overfill Prev Device Overfill Alarm 3/22/2022 3/17/2025
Overfill Prev Device Overfill Drop Tube Valve 3/18/2025 3/18/2028
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 3/17/2025 3/17/2028
Leak Detect - Piping Sump Sensor with positive shutdown 3/17/2025 3/17/2026
Piping Single Wall Transition Sump 3/17/2025 3/17/2028
Leak Detect - Piping Sump Sensor with positive shutdown 3/17/2025 3/17/2026
Spill Contain Device Double Wall Spill Bucket 3/17/2025 3/17/2028
Tank Fiberglass Brine Filled Double Wall Containment Solutions N/A N/A
Vent, Riser, Fill Piping Steel risers N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Leak Detect - Piping Siphon Bar Functional Pass 6/15/2020
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test (Piping) Pass 3/17/2025
Tank Fiberglass Brine Filled Double Wall Containment Solutions Precision Test (Tank) Pass 9/18/2019



Tank Number 2

Capacity: 30000 Petroleum Use: None
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 8/16/2019 Abandoned Material:
Current Age: 5 Abandoned Date:
Install Date: 5/16/2019 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Other Non-vented check valve N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 3/19/2024 3/17/2025
Leak Detect - Piping Siphon Bar N/A N/A
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 3/17/2025 3/17/2026
Manway At Grade Accessible Manway Accessible at Grade N/A N/A
Overfill Prev Device Overfill Alarm 3/22/2022 3/17/2025
Overfill Prev Device Overfill Drop Tube Valve 3/18/2025 3/18/2028
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 3/17/2025 3/17/2028
Leak Detect - Piping Sump Sensor with positive shutdown 3/17/2025 3/17/2026
Piping Single Wall Transition Sump 3/17/2025 3/17/2028
Leak Detect - Piping Sump Sensor with positive shutdown 3/17/2025 3/17/2026
Spill Contain Device Double Wall Spill Bucket 3/17/2025 3/17/2028
Tank Fiberglass Brine Filled Double Wall Containment Solutions N/A N/A
Vent, Riser, Fill Piping Steel risers N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Leak Detect - Piping Siphon Bar Functional Pass 6/15/2020
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test (Piping) Pass 3/17/2025
Tank Fiberglass Brine Filled Double Wall Containment Solutions Precision Test (Tank) Pass 9/18/2019



Tank Number 3

Capacity: 20000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 8/16/2019 Abandoned Material:
Current Age: 5 Abandoned Date:
Install Date: 5/16/2019 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 3/17/2025 3/17/2026
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 3/17/2025 3/17/2026
Manway At Grade Accessible Manway Accessible at Grade N/A N/A
Overfill Prev Device Overfill Alarm 3/18/2025 3/18/2028
Overfill Prev Device Overfill Drop Tube Valve 3/18/2025 3/18/2028
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 3/17/2025 3/17/2028
Leak Detect - Piping Sump Sensor with positive shutdown 3/17/2025 3/17/2026
Spill Contain Device Double Wall Spill Bucket 3/17/2025 3/17/2028
Tank Fiberglass Brine Filled Double Wall Containment Solutions N/A N/A
Vent, Riser, Fill Piping Steel risers N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test (Piping) Pass 9/18/2019
Tank Fiberglass Brine Filled Double Wall Containment Solutions Precision Test (Tank) Pass 9/18/2019



Tank Number 4

Capacity: 6000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 8/16/2019 Abandoned Material:
Current Age: 5 Abandoned Date:
Install Date: 5/16/2019 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 3/17/2025 3/17/2026
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 3/17/2025 3/17/2026
Manway At Grade Accessible Manway Accessible at Grade N/A N/A
Overfill Prev Device Overfill Alarm 3/18/2025 3/18/2028
Overfill Prev Device Overfill Drop Tube Valve 3/18/2025 3/18/2028
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 3/17/2025 3/17/2028
Leak Detect - Piping Sump Sensor with positive shutdown 3/17/2025 3/17/2026
Spill Contain Device Double Wall Spill Bucket 3/17/2025 3/17/2028
Tank Fiberglass Brine Filled Double Wall Containment Solutions N/A N/A
Vent, Riser, Fill Piping Steel risers N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test (Piping) Pass 9/18/2019
Tank Fiberglass Brine Filled Double Wall Containment Solutions Precision Test (Tank) Pass 9/18/2019



Tank Number 5

Capacity: 10000 Petroleum Use: None
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 8/16/2019 Abandoned Material:
Current Age: 5 Abandoned Date:
Install Date: 5/16/2019 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 3/17/2025 3/17/2026
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 3/17/2025 3/17/2026
Manway At Grade Accessible Manway Accessible at Grade N/A N/A
Overfill Prev Device Overfill Alarm 3/18/2025 3/18/2028
Overfill Prev Device Overfill Drop Tube Valve 3/18/2025 3/18/2028
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 3/17/2025 3/17/2028
Leak Detect - Piping Sump Sensor with positive shutdown 3/17/2025 3/17/2026
Spill Contain Device Double Wall Spill Bucket 3/17/2025 3/17/2028
Tank Fiberglass Brine Filled Double Wall Containment Solutions N/A N/A
Vent, Riser, Fill Piping Steel risers N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test (Piping) Pass 9/18/2019
Tank Fiberglass Brine Filled Double Wall Containment Solutions Precision Test (Tank) Pass 9/18/2019



Tank Number 6

Capacity: 8000 Petroleum Use:
Product: Diesel Exhaust Fluid (Non-Regulated) CERCLA Substance:
Status: Unknown CAS Code:
Regulated Status: Non-Regulated Removed Date:
OSFM First Notify Date: 8/16/2019 Abandoned Material:
Current Age: 5 Abandoned Date:
Install Date: 5/16/2019 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors
Manway At Grade Accessible Manway Accessible at Grade N/A N/A
Overfill Prev Device Overfill Alarm
Overfill Prev Device Overfill Drop Tube Valve
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump
Spill Contain Device Double Wall Spill Bucket
Tank Fiberglass Brine Filled Double Wall Containment Solutions N/A N/A
Vent, Riser, Fill Piping Steel risers N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 7

Capacity: 6000 Petroleum Use:
Product: E85 CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 8/16/2019 Abandoned Material:
Current Age: 5 Abandoned Date:
Install Date: 5/16/2019 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 3/17/2025 3/17/2026
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 3/17/2025 3/17/2026
Manway At Grade Accessible Manway Accessible at Grade N/A N/A
Overfill Prev Device Overfill Alarm 3/18/2025 3/18/2028
Overfill Prev Device Overfill Drop Tube Valve 3/18/2025 3/18/2028
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 3/17/2025 3/17/2028
Leak Detect - Piping Sump Sensor with positive shutdown 3/17/2025 3/17/2026
Spill Contain Device Double Wall Spill Bucket 3/17/2025 3/17/2028
Tank Fiberglass Brine Filled Double Wall Containment Solutions N/A N/A
Vent, Riser, Fill Piping Steel risers N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test (Piping) Pass 9/18/2019
Tank Fiberglass Brine Filled Double Wall Containment Solutions Precision Test (Tank) Pass 9/18/2019

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 3/17/2025 3/17/2028
Leak Detect - Piping Sump Sensor with positive shutdown 3/17/2025 3/17/2026



Name\ID 11/12

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 3/17/2025 3/17/2028
Leak Detect - Piping Sump Sensor with positive shutdown 3/17/2025 3/17/2026



Name\ID 13/14

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 3/17/2025 3/17/2028
Leak Detect - Piping Sump Sensor with positive shutdown 3/17/2025 3/17/2026



Name\ID 15/16

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 3/17/2025 3/17/2028
Leak Detect - Piping Sump Sensor with positive shutdown 3/17/2025 3/17/2026



Name\ID 17/18

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 3/17/2025 3/17/2028
Leak Detect - Piping Sump Sensor with positive shutdown 3/17/2025 3/17/2026



Name\ID 17M/18S

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/17/2019 9/17/2022



Name\ID 18M/19S

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/17/2019 9/17/2022



Name\ID 19/20

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 3/17/2025 3/17/2028
Leak Detect - Piping Sump Sensor with positive shutdown 3/17/2025 3/17/2026



Name\ID 19M/20S

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/17/2019 9/17/2022



Name\ID 20M/21S

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/17/2019 9/17/2022



Name\ID 21M/22S

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/17/2019 9/17/2022



Name\ID 22M/23S

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/17/2019 9/17/2022



Name\ID 23M

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/17/2019 9/17/2022



Name\ID 24/25

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/17/2019 9/17/2022



Name\ID 25/26

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/17/2019 9/17/2022
Leak Detect - Piping Sump Sensor with positive shutdown 3/17/2025 3/17/2026



Name\ID 26/27

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/17/2019 9/17/2022
Leak Detect - Piping Sump Sensor with positive shutdown 3/17/2025 3/17/2026



Name\ID 27/28

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/17/2019 9/17/2022
Leak Detect - Piping Sump Sensor with positive shutdown 3/17/2025 3/17/2026



Name\ID 28/29

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/17/2019 9/17/2022
Leak Detect - Piping Sump Sensor with positive shutdown 3/17/2025 3/17/2026



Name\ID 29

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 3/17/2025 3/17/2028
Leak Detect - Piping Sump Sensor with positive shutdown 3/17/2025 3/17/2026



Name\ID 29/30

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/17/2019 9/17/2022
Leak Detect - Piping Sump Sensor with positive shutdown 3/17/2025 3/17/2026



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 3/17/2025 3/17/2028
Leak Detect - Piping Sump Sensor with positive shutdown 3/17/2025 3/17/2026



Name\ID 30

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 3/17/2025 3/17/2028
Leak Detect - Piping Sump Sensor with positive shutdown 3/17/2025 3/17/2026



Name\ID 30/31

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/17/2019 9/17/2022
Leak Detect - Piping Sump Sensor with positive shutdown 3/17/2025 3/17/2026



Name\ID 31

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 3/17/2025 3/17/2028
Leak Detect - Piping Sump Sensor with positive shutdown 3/17/2025 3/17/2026



Name\ID 32

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 3/17/2025 3/17/2028
Leak Detect - Piping Sump Sensor with positive shutdown 3/17/2025 3/17/2026



Name\ID 33

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 3/17/2025 3/17/2028
Leak Detect - Piping Sump Sensor with positive shutdown 3/17/2025 3/17/2026



Name\ID 34

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 3/17/2025 3/17/2028
Leak Detect - Piping Sump Sensor with positive shutdown 3/17/2025 3/17/2026



Name\ID 35

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 3/17/2025 3/17/2028
Leak Detect - Piping Sump Sensor with positive shutdown 3/17/2025 3/17/2026



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 3/17/2025 3/17/2028
Leak Detect - Piping Sump Sensor with positive shutdown 3/17/2025 3/17/2026



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 3/17/2025 3/17/2028
Leak Detect - Piping Sump Sensor with positive shutdown 3/17/2025 3/17/2026



Name\ID 9/10

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 3/17/2025 3/17/2028
Leak Detect - Piping Sump Sensor with positive shutdown 3/17/2025 3/17/2026

MFD Motorfuel Dispensing Forms

Facility Number Name City Received Date Letter
1046826 Thorntons #331 Roscoe 07/29/2019 Letter Form