Notice of Violations (Current)
NOV Number:
E0020261713
(Pending)
Issue Date:
7/1/2026
Expiration Date:
8/30/2026
View NOV Form
| Tanks |
Violations |
| 1, 2, 3, 4 |
Overfill prevention equipment inspection(s) not completed (Required every 3 years). - .
Triennial inspection of overfill prevention device (overfill drop tube valve, overfill alarm, ball float valve) has not been completed. |
| Facility |
Submit Notification Form For Ownership Address Change - Notification Form is available at www.sfm.illinois.gov
This Form is required to be submitted within 30 days of an ownership change. |
| 1, 2, 3, 4 |
Triennial spill prevention equipment testing not completed. - Triennial inspection of spill bucket(s) has not been completed. |
| 1, 2, 3, 4 |
Triennial testing for qualifying piping containment sump not completed (Required every 3 years). - Triennial testing for qualifying STP piping containment sump(s) not completed.
Triennial testing for qualifying dispenser containment sump(s) not completed. |
IEMA Numbers Associated with the Facility
No IEMA Numbers Found
LUST
Fund Eligibility and Deductibility Determinations
No Applications Found
Tank Number 1
| Capacity: |
15000 |
|
Petroleum Use: |
|
| Product: |
Gasoline - Regular |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
6/13/2017 |
|
Abandoned Material: |
|
| Current Age: |
9 |
|
Abandoned Date: |
|
| Install Date: |
3/22/2017 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
5/16/2017 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Electronic Pressurized Line Leak Detection |
10/29/2025 |
10/29/2026 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 450 Plus with CSLD |
10/29/2025 |
10/29/2026 |
|
Leak Detect - Tank
|
Non-Discriminating Interstitial Monitoring Sensors |
10/29/2025 |
10/29/2026 |
|
Manway At Grade
|
Accessible Manway Accessible at Grade |
Not applicable |
Not applicable |
|
Overfill Prev Device
|
Overfill Alarm |
6/16/2023 |
6/16/2026 |
|
Piping
|
Fiberglass Double Wall Ameron Dualoy 3000/LCX |
Not applicable |
Not applicable |
|
Piping
|
Double Wall STP/Tanktop Sump |
6/16/2023 |
6/16/2026 |
Leak Detect - Piping
|
Sump Sensor with positive shutdown |
6/16/2023 |
6/16/2026 |
|
Spill Contain Device
|
Single Wall Spill Bucket |
6/16/2023 |
6/16/2026 |
|
Tank
|
Fiberglass Double Wall XERXES |
Not applicable |
Not applicable |
|
Vent, Riser, Fill Piping
|
Steel risers |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Fiberglass Double Wall Ameron Dualoy 3000/LCX
|
Precision Test (Piping)
|
Pass
|
10/29/2025
|
Tank Number 2
| Capacity: |
8000 |
|
Petroleum Use: |
|
| Product: |
Gasoline - Mid-grade |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
6/13/2017 |
|
Abandoned Material: |
|
| Current Age: |
9 |
|
Abandoned Date: |
|
| Install Date: |
3/22/2017 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
5/16/2017 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Electronic Pressurized Line Leak Detection |
10/29/2025 |
10/29/2026 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 450 Plus with CSLD |
10/29/2025 |
10/29/2026 |
|
Leak Detect - Tank
|
Non-Discriminating Interstitial Monitoring Sensors |
10/29/2025 |
10/29/2026 |
|
Manway At Grade
|
Accessible Manway Accessible at Grade |
Not applicable |
Not applicable |
|
Overfill Prev Device
|
Overfill Alarm |
6/16/2023 |
6/16/2026 |
|
Piping
|
Fiberglass Double Wall Ameron Dualoy 3000/LCX |
Not applicable |
Not applicable |
|
Piping
|
Double Wall STP/Tanktop Sump |
6/16/2023 |
6/16/2026 |
Leak Detect - Piping
|
Sump Sensor with positive shutdown |
6/16/2023 |
6/16/2026 |
|
Spill Contain Device
|
Single Wall Spill Bucket |
6/16/2023 |
6/16/2026 |
|
Tank
|
Fiberglass Double Wall XERXES |
Not applicable |
Not applicable |
|
Vent, Riser, Fill Piping
|
Steel risers |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Fiberglass Double Wall Ameron Dualoy 3000/LCX
|
Precision Test (Piping)
|
Pass
|
10/29/2025
|
Tank Number 3
| Capacity: |
8000 |
|
Petroleum Use: |
|
| Product: |
Gasoline - Premium |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
6/13/2017 |
|
Abandoned Material: |
|
| Current Age: |
9 |
|
Abandoned Date: |
|
| Install Date: |
3/22/2017 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
5/16/2017 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Electronic Pressurized Line Leak Detection |
10/29/2025 |
10/29/2026 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 450 Plus with CSLD |
10/29/2025 |
10/29/2026 |
|
Leak Detect - Tank
|
Non-Discriminating Interstitial Monitoring Sensors |
10/29/2025 |
10/29/2026 |
|
Manway At Grade
|
Accessible Manway Accessible at Grade |
Not applicable |
Not applicable |
|
Overfill Prev Device
|
Overfill Alarm |
6/16/2023 |
6/16/2026 |
|
Piping
|
Fiberglass Double Wall Ameron Dualoy 3000/LCX |
Not applicable |
Not applicable |
|
Piping
|
Double Wall STP/Tanktop Sump |
6/16/2023 |
6/16/2026 |
Leak Detect - Piping
|
Sump Sensor with positive shutdown |
6/16/2023 |
6/16/2026 |
|
Spill Contain Device
|
Single Wall Spill Bucket |
6/16/2023 |
6/16/2026 |
|
Tank
|
Fiberglass Double Wall XERXES |
Not applicable |
Not applicable |
|
Vent, Riser, Fill Piping
|
Steel risers |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Fiberglass Double Wall Ameron Dualoy 3000/LCX
|
Precision Test (Piping)
|
Pass
|
10/29/2025
|
Tank Number 4
| Capacity: |
8000 |
|
Petroleum Use: |
|
| Product: |
Diesel Fuel |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
6/13/2017 |
|
Abandoned Material: |
|
| Current Age: |
9 |
|
Abandoned Date: |
|
| Install Date: |
3/22/2017 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
5/16/2017 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Electronic Pressurized Line Leak Detection |
10/29/2025 |
10/29/2026 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 450 Plus with CSLD |
10/29/2025 |
10/29/2026 |
|
Leak Detect - Tank
|
Non-Discriminating Interstitial Monitoring Sensors |
10/29/2025 |
10/29/2026 |
|
Manway At Grade
|
Accessible Manway Accessible at Grade |
Not applicable |
Not applicable |
|
Overfill Prev Device
|
Overfill Alarm |
6/16/2023 |
6/16/2026 |
|
Piping
|
Fiberglass Double Wall Ameron Dualoy 3000/LCX |
Not applicable |
Not applicable |
|
Piping
|
Double Wall STP/Tanktop Sump |
6/16/2023 |
6/16/2026 |
Leak Detect - Piping
|
Sump Sensor with positive shutdown |
6/16/2023 |
6/16/2026 |
|
Spill Contain Device
|
Single Wall Spill Bucket |
6/16/2023 |
6/16/2026 |
|
Tank
|
Fiberglass Double Wall XERXES |
Not applicable |
Not applicable |
|
Vent, Riser, Fill Piping
|
Steel risers |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Fiberglass Double Wall Ameron Dualoy 3000/LCX
|
Precision Test (Piping)
|
Pass
|
10/29/2025
|
Failed test = the latest test has failed.
Not applicable = a test does not apply to this equipment type or configuration.
No passing test found = a passing test is expected but was not found from the source data.
MFD
Motorfuel Dispensing Forms
| Facility Number |
Name |
City |
Received Date |
Letter |
|
1046332
|
La Chiquita Food Market
|
Rockford
|
06/13/2017
|
Letter
Form
|