Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 1045365
Status: Active
Facility Name: Casey's General Store #3272
Address: 105 Plank Rd. Sycamore, IL 60178
County: De Kalb
Property Parcel: 06-21-300-054
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y002656
Green Tag Issue Date: 5/3/2023
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: Casey's Retail Company
Owner Address: 3305 SE Delaware Ave. P.O. Box 3004 Ankeny, IA 50021
Owner Status: Current Owner
Purchase Date: 6/14/2013
Type of Financial Responsibility: Self-Insurance
Financial Responsibility Reporting Due Date: 1/29/2026

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 5/3/2023 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0002560 Casey's Retail Company Current Owner 6/14/2013

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020252114 (Pending)    Issue Date: 8/15/2025    Expiration Date: 10/14/2025    View NOV Form

Tanks Violations
Facility Facility Operation and Maintenance Plan not completed or available.
1, 2, 3 Line interstitial sensors have been raised and rendered inoperational. - Sensor is resting on its side and cannot function. Please in correct position, horizontal in the containment, Dispenser 15/16.
Facility Missing copies of current testing certificates for operator training
Facility Missing copy of emergency instructions or emergency procedures plan
Facility Missing list of designated Class A/B & C Operators

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 20000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 10/22/2013 Abandoned Material:
Current Age: 11 Abandoned Date:
Install Date: 6/14/2013 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 9/26/2013

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 3/5/2025 3/5/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 3/5/2025 3/5/2026
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 3/5/2025 3/5/2026
Overfill Prev Device Overfill Drop Tube Valve 3/29/2024 3/29/2027
Piping Flexible Double Wall A.P.T. Poly Tech P175SC N/A N/A
Piping Single Wall STP/Tanktop Sump 3/29/2024 3/29/2027
Leak Detect - Piping Sump Sensor with positive shutdown 3/5/2025 3/5/2026
Spill Contain Device Single Wall Spill Bucket 3/29/2024 3/29/2027
Tank Fiberglass Double Wall XERXES N/A N/A
Vent, Riser, Fill Piping Steel risers N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 2

Capacity: 12000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 10/22/2013 Abandoned Material:
Current Age: 11 Abandoned Date:
Install Date: 6/14/2013 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 9/26/2013

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 3/5/2025 3/5/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 3/5/2025 3/5/2026
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 3/5/2025 3/5/2026
Overfill Prev Device Overfill Drop Tube Valve 3/29/2024 3/29/2027
Piping Flexible Double Wall A.P.T. Poly Tech P175SC N/A N/A
Piping Single Wall STP/Tanktop Sump 3/29/2024 3/29/2027
Leak Detect - Piping Sump Sensor with positive shutdown 3/5/2025 3/5/2026
Spill Contain Device Single Wall Spill Bucket 3/29/2024 3/29/2027
Tank Fiberglass Double Wall XERXES N/A N/A
Vent, Riser, Fill Piping Steel risers N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 3

Capacity: 8000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 10/22/2013 Abandoned Material:
Current Age: 11 Abandoned Date:
Install Date: 6/14/2013 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 9/26/2013

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 3/5/2025 3/5/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 3/5/2025 3/5/2026
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 3/5/2025 3/5/2026
Overfill Prev Device Overfill Drop Tube Valve 3/29/2024 3/29/2027
Piping Flexible Double Wall A.P.T. Poly Tech P175SC N/A N/A
Piping Single Wall STP/Tanktop Sump 3/29/2024 3/29/2027
Leak Detect - Piping Sump Sensor with positive shutdown 3/5/2025 3/5/2026
Spill Contain Device Single Wall Spill Bucket 3/29/2024 3/29/2027
Tank Fiberglass Double Wall XERXES N/A N/A
Vent, Riser, Fill Piping Steel risers N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 3/29/2024 3/29/2027
Leak Detect - Piping Sump Sensor with positive shutdown 3/5/2025 3/5/2026



Name\ID 11/12

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 3/29/2024 3/29/2027
Leak Detect - Piping Sump Sensor with positive shutdown 3/5/2025 3/5/2026



Name\ID 13/14

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 3/29/2024 3/29/2027
Leak Detect - Piping Sump Sensor with positive shutdown 3/5/2025 3/5/2026



Name\ID 16/16

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 3/29/2024 3/29/2027
Leak Detect - Piping Sump Sensor with positive shutdown 3/5/2025 3/5/2026



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 3/29/2024 3/29/2027
Leak Detect - Piping Sump Sensor with positive shutdown 3/5/2025 3/5/2026



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 3/29/2024 3/29/2027
Leak Detect - Piping Sump Sensor with positive shutdown 3/5/2025 3/5/2026



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 3/29/2024 3/29/2027
Leak Detect - Piping Sump Sensor with positive shutdown 3/5/2025 3/5/2026



Name\ID 9/10

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 3/29/2024 3/29/2027
Leak Detect - Piping Sump Sensor with positive shutdown 3/5/2025 3/5/2026

MFD Motorfuel Dispensing Forms

No Forms Found