Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 1043362
Status: Active
Facility Name: Monroe Center Oasis
Address: 5534 N. Limestone Rd. Monroe Center, IL 61052
County: Ogle
Property Parcel: 12-20-201-002
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y002697
Green Tag Issue Date: 2/28/2024
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: Monroe Center Oasis, Inc.
Owner Address: 5534 N. Limestone Rd. Monroe Center, IL 61052
Owner Status: Current Owner
Purchase Date: 8/18/2006
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 11/12/2025

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 2/28/2024 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0036333 Monroe Center Oasis, Inc. Current Owner 8/18/2006
U0033607 Joe Lazar - Monroe Center Oasis Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020251603 (Pending)    Issue Date: 6/25/2025    Expiration Date: 8/24/2025    View NOV Form

Tanks Violations
1, 2, 3, 4, 5, 6 Containment support components are cracked, deteriorated or missing. The cover and supporting components that are defective shall be replaced with factory manufactured components. - Some STP lids are mising handles and are difficult to remove, several other lids are caved into the containmnet. Repair concrete and replace/repair outer lids.
1, 2, 4, 5 Dispensers - hoses cracked, split or worn and require replacement - Replace hoses
1, 2, 3, 4, 5, 6 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 20000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 4/4/2007 Abandoned Material:
Current Age: 19 Abandoned Date:
Install Date: 8/18/2006 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 12/24/2024 12/24/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 12/24/2024 12/24/2025
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 12/24/2024 12/24/2025
Overfill Prev Device Overfill Drop Tube Valve 10/6/2023 10/6/2026
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 7/10/2023 7/10/2026
Leak Detect - Piping Sump Sensor 12/24/2024 12/24/2025
Spill Contain Device Single Wall Spill Bucket 7/10/2023 7/10/2026
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test (Piping) Pass 12/24/2024



Tank Number 2

Capacity: 12000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 4/4/2007 Abandoned Material:
Current Age: 19 Abandoned Date:
Install Date: 8/18/2006 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 12/24/2024 12/24/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 12/24/2024 12/24/2025
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 12/24/2024 12/24/2025
Overfill Prev Device Overfill Drop Tube Valve 9/26/2023 9/26/2026
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 9/26/2023 9/26/2026
Leak Detect - Piping Sump Sensor 12/24/2024 12/24/2025
Spill Contain Device Single Wall Spill Bucket 7/10/2023 7/10/2026
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test (Piping) Pass 12/24/2024



Tank Number 3

Capacity: 8000 Petroleum Use:
Product: B-11 CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 4/4/2007 Abandoned Material:
Current Age: 19 Abandoned Date:
Install Date: 8/18/2006 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 12/24/2024 12/24/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 12/24/2024 12/24/2025
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 12/24/2024 12/24/2025
Overfill Prev Device Overfill Drop Tube Valve 9/26/2023 9/26/2026
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 9/26/2023 9/26/2026
Leak Detect - Piping Sump Sensor 12/24/2024 12/24/2025
Spill Contain Device Single Wall Spill Bucket 7/10/2023 7/10/2026
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test (Piping) Pass 12/24/2024



Tank Number 4

Capacity: 8000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 4/4/2007 Abandoned Material:
Current Age: 19 Abandoned Date:
Install Date: 8/18/2006 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 12/24/2024 12/24/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 12/24/2024 12/24/2025
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 12/24/2024 12/24/2025
Overfill Prev Device Overfill Drop Tube Valve 9/26/2023 9/26/2026
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 7/10/2023 7/10/2026
Leak Detect - Piping Sump Sensor 12/24/2024 12/24/2025
Spill Contain Device Single Wall Spill Bucket 7/10/2023 7/10/2026
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Single Wall STP/Tanktop Sump None Pass 11/19/2018
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test (Piping) Pass 12/24/2024



Tank Number 5

Capacity: 6000 Petroleum Use:
Product: Gasoline - Non Ethanol CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 4/4/2007 Abandoned Material:
Current Age: 19 Abandoned Date:
Install Date: 8/18/2006 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 12/24/2024 12/24/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 12/24/2024 12/24/2025
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 12/24/2024 12/24/2025
Overfill Prev Device Overfill Drop Tube Valve 9/26/2023 9/26/2026
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 7/10/2023 7/10/2026
Leak Detect - Piping Sump Sensor 12/24/2024 12/24/2025
Spill Contain Device Single Wall Spill Bucket 7/10/2023 7/10/2026
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test (Piping) Pass 12/24/2024



Tank Number 6

Capacity: 6000 Petroleum Use: None
Product: Racing Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 4/4/2007 Abandoned Material:
Current Age: 19 Abandoned Date:
Install Date: 8/18/2006 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 12/24/2024 12/24/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 12/24/2024 12/24/2025
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 12/24/2024 12/24/2025
Overfill Prev Device Overfill Drop Tube Valve 9/26/2023 9/26/2026
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 7/10/2023 7/10/2026
Leak Detect - Piping Sump Sensor 12/24/2024 12/24/2025
Spill Contain Device Single Wall Spill Bucket 7/10/2023 7/10/2026
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test (Piping) Pass 12/24/2024

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/26/2023 9/26/2026
Leak Detect - Piping Sump Sensor 12/24/2024 12/24/2025



Name\ID 11/12

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 7/10/2023 7/10/2026
Leak Detect - Piping Sump Sensor 12/24/2024 12/24/2025



Name\ID 13/14

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 7/10/2023 7/10/2026
Leak Detect - Piping Sump Sensor 12/24/2024 12/24/2025



Name\ID 14S/15

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 2/27/2024 2/27/2027
Leak Detect - Piping Sump Sensor 12/24/2024 12/24/2025



Name\ID 15S/16

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 2/27/2024 2/27/2027
Leak Detect - Piping Sump Sensor 12/24/2024 12/24/2025



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/26/2023 9/26/2026
Leak Detect - Piping Sump Sensor 12/24/2024 12/24/2025



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 7/10/2023 7/10/2026
Leak Detect - Piping Sump Sensor 12/24/2024 12/24/2025



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 7/10/2023 7/10/2026
Leak Detect - Piping Sump Sensor 12/24/2024 12/24/2025



Name\ID 9/10

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 7/10/2023 7/10/2026
Leak Detect - Piping Sump Sensor 12/24/2024 12/24/2025

MFD Motorfuel Dispensing Forms