Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 1043101
Status: Active
Facility Name: Thorntons #364
Address: 102 West Etna Road Ottawa, IL 61350
County: LaSalle
Property Parcel: 14-35-411-002
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: BB000692
Green Tag Issue Date: 2/10/2026
Green Tag Expire Date: 12/31/2028
MFD Type: Self Service

Owner Details

Owner Name: Thorntons, LLC
Owner Address: 2600 James Thornton Way Louisville, KY 40245
Owner Status: Current Owner
Purchase Date: 2/11/2019
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 1/9/2027

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0039521 Thorntons, LLC Current Owner 2/11/2019
U0014995 Thornton's, Inc. - DO NOT USE THIS OWNER ID Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violations (Current)

NOV Number: E0020262292 (Pending)    Issue Date: 9/30/2026    Expiration Date: 11/29/2026    View NOV Form

Tanks Violations
Facility Each emergency stop shall be identified by a sign on all-weather materials stating "EMERGENCY STOP" in 2 inch red capital letters - Emergency stop sign on west corner of building is missing, replace.
2, 3, 4 Line leak detection equipment in alarm or failed test, must repair or replace. - There are five active alarms on the ATG, Q5 "GRS TST Needed ALM" Ln 4 "Line Out" Q4 "PLLD Shutdown" L 14 "Fuel Alarm" L 15 "Sensor Out Alarm"

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 12000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 5/31/2006 Abandoned Material:
Current Age: 20 Abandoned Date:
Install Date: 3/2/2006 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 3/2/2006

Equipment Information

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive Not applicable Not applicable
Corrosion Prot - Tank Fiberglass Non-Corrosive Not applicable Not applicable
Leak Detect - Piping Electronic Pressurized Line Leak Detection 3/19/2026 3/19/2027
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 Plus with CSLD 3/19/2026 3/19/2027
Leak Detect - Tank Hydrostatic Reservoir Interstitial Monitoring Sensors 3/19/2026 3/19/2027
Overfill Prev Device Overfill Drop Tube Valve 3/25/2025 3/25/2028
Piping Flexible Double Wall OPW Pisces Not applicable Not applicable
Piping Single Wall STP/Tanktop Sump 3/26/2024 3/26/2027
Leak Detect - Piping Sump Sensor with positive shutdown 3/26/2024 3/26/2027
Spill Contain Device Single Wall Spill Bucket 3/26/2024 3/26/2027
Tank Fiberglass Brine Filled Double Wall XERXES Not applicable Not applicable

Additional Tests

No Tests Listed




Tank Number 2

Capacity: 12000 Petroleum Use:
Product: E85 CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 5/31/2006 Abandoned Material:
Current Age: 20 Abandoned Date:
Install Date: 3/2/2006 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 3/2/2006

Equipment Information

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive Not applicable Not applicable
Corrosion Prot - Tank Fiberglass Non-Corrosive Not applicable Not applicable
Leak Detect - Piping Electronic Pressurized Line Leak Detection 3/19/2026 3/19/2027
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 Plus with CSLD 3/19/2026 3/19/2027
Leak Detect - Tank Hydrostatic Reservoir Interstitial Monitoring Sensors 3/19/2026 3/19/2027
Overfill Prev Device Overfill Drop Tube Valve 3/25/2025 3/25/2028
Piping Flexible Double Wall OPW Flexworks Not applicable Not applicable
Piping Single Wall STP/Tanktop Sump 3/26/2024 3/26/2027
Leak Detect - Piping Sump Sensor with positive shutdown 3/26/2024 3/26/2027
Spill Contain Device Double Wall Spill Bucket 3/26/2024 3/26/2027
Tank Fiberglass Brine Filled Double Wall XERXES Not applicable Not applicable

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall OPW Flexworks Precision Test (Piping) Pass 7/28/2022
Tank Fiberglass Brine Filled Double Wall XERXES Precision Test (Tank) Pass 7/28/2022



Tank Number 3

Capacity: 8000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 5/31/2006 Abandoned Material:
Current Age: 20 Abandoned Date:
Install Date: 3/2/2006 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 3/2/2006

Equipment Information

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive Not applicable Not applicable
Corrosion Prot - Tank Fiberglass Non-Corrosive Not applicable Not applicable
Leak Detect - Piping Electronic Pressurized Line Leak Detection 3/19/2026 3/19/2027
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 Plus with CSLD 3/19/2026 3/19/2027
Leak Detect - Tank Hydrostatic Reservoir Interstitial Monitoring Sensors 3/19/2026 3/19/2027
Overfill Prev Device Overfill Drop Tube Valve 3/25/2025 3/25/2028
Piping Flexible Double Wall OPW Pisces Not applicable Not applicable
Piping Single Wall STP/Tanktop Sump 3/26/2024 3/26/2027
Leak Detect - Piping Sump Sensor with positive shutdown 3/26/2024 3/26/2027
Spill Contain Device Double Wall Spill Bucket 3/26/2024 3/26/2027
Tank Fiberglass Brine Filled Double Wall XERXES Not applicable Not applicable

Additional Tests

No Tests Listed




Tank Number 4

Capacity: 4000 Petroleum Use:
Product: E85 CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 5/31/2006 Abandoned Material:
Current Age: 20 Abandoned Date:
Install Date: 3/2/2006 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 3/2/2006

Equipment Information

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive Not applicable Not applicable
Corrosion Prot - Tank Fiberglass Non-Corrosive Not applicable Not applicable
Leak Detect - Piping Electronic Pressurized Line Leak Detection 3/19/2026 3/19/2027
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 Plus with CSLD 3/19/2026 3/19/2027
Leak Detect - Tank Hydrostatic Reservoir Interstitial Monitoring Sensors 3/19/2026 3/19/2027
Overfill Prev Device Overfill Drop Tube Valve 3/25/2025 3/25/2028
Piping Flexible Double Wall OPW Flexworks Not applicable Not applicable
Piping Single Wall STP/Tanktop Sump 3/26/2024 3/26/2027
Leak Detect - Piping Sump Sensor with positive shutdown 3/26/2024 3/26/2027
Spill Contain Device Double Wall Spill Bucket 3/26/2024 3/26/2027
Tank Fiberglass Brine Filled Double Wall XERXES Not applicable Not applicable

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall OPW Flexworks Precision Test (Piping) Pass 7/28/2022
Tank Fiberglass Brine Filled Double Wall XERXES Precision Test (Tank) Pass 7/28/2022



Tank Number 5

Capacity: 20000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 5/31/2006 Abandoned Material:
Current Age: 20 Abandoned Date:
Install Date: 3/2/2006 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 3/2/2006

Equipment Information

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive Not applicable Not applicable
Corrosion Prot - Tank Fiberglass Non-Corrosive Not applicable Not applicable
Leak Detect - Piping Electronic Pressurized Line Leak Detection 3/19/2026 3/19/2027
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 Plus with CSLD 3/19/2026 3/19/2027
Leak Detect - Tank Hydrostatic Reservoir Interstitial Monitoring Sensors 3/19/2026 3/19/2027
Overfill Prev Device Overfill Drop Tube Valve 3/25/2025 3/25/2028
Piping Flexible Double Wall OPW Pisces Not applicable Not applicable
Piping Single Wall STP/Tanktop Sump 3/26/2024 3/26/2027
Leak Detect - Piping Sump Sensor with positive shutdown 3/26/2024 3/26/2027
Spill Contain Device Double Wall Spill Bucket 3/26/2024 3/26/2027
Tank Fiberglass Brine Filled Double Wall XERXES Not applicable Not applicable

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall OPW Pisces Precision Test (Piping) Pass 6/25/2026
Tank Fiberglass Brine Filled Double Wall XERXES Precision Test (Tank) Pass 5/17/2019

Failed test = the latest test has failed.

Not applicable = a test does not apply to this equipment type or configuration.

No passing test found = a passing test is expected but was not found from the source data.


Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 3/26/2024 3/26/2027
Leak Detect - Piping Sump Sensor with positive shutdown 3/19/2026 3/19/2027



Name\ID 11/12

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 3/26/2024 3/26/2027
Leak Detect - Piping Sump Sensor with positive shutdown 3/19/2026 3/19/2027



Name\ID 13/14

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 3/26/2024 3/26/2027
Leak Detect - Piping Sump Sensor with positive shutdown 3/19/2026 3/19/2027



Name\ID 15/16

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 3/26/2024 3/26/2027
Leak Detect - Piping Sump Sensor with positive shutdown 3/19/2026 3/19/2027



Name\ID 17/18

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 3/26/2024 3/26/2027
Leak Detect - Piping Sump Sensor with positive shutdown 3/19/2026 3/19/2027



Name\ID 19/20

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 3/26/2024 3/26/2027
Leak Detect - Piping Sump Sensor with positive shutdown 3/19/2026 3/19/2027



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 3/26/2024 3/26/2027
Leak Detect - Piping Sump Sensor with positive shutdown 3/19/2026 3/19/2027



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 3/26/2024 3/26/2027
Leak Detect - Piping Sump Sensor with positive shutdown 3/19/2026 3/19/2027



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 3/26/2024 3/26/2027
Leak Detect - Piping Sump Sensor with positive shutdown 3/19/2026 3/19/2027



Name\ID 9/10

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 3/26/2024 3/26/2027
Leak Detect - Piping Sump Sensor with positive shutdown 3/19/2026 3/19/2027

Failed test = the latest test has failed.

Not applicable = a test does not apply to this equipment type or configuration.

No passing test found = a passing test is expected but was not found from the source data.


MFD Motorfuel Dispensing Forms

No Forms Found