Notice of Violatlions (Current)
NOV Number:
E0020253156
(Pending)
Issue Date:
11/25/2025
Expiration Date:
1/24/2026
View NOV Form
| Tanks |
Violations |
| 6 |
Annual line precision and mechanical line leak detector functional test not completed. - Annual third party testing required on all line leak detectors. TK 6 results not in Portal. |
| 4, 5, 6 |
Line interstitial sensor functional test not accomplished (Required annually). - Annual third party testing required on all line interstitial sensors. FAILED TEST 10/27/2025 |