Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 1040284
Status: Active
Facility Name: Fas Mart #5222
Address: 3302 S. 11th Street Rockford, IL 61109
County: Winnebago
Property Parcel:
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: AA02078
Green Tag Issue Date: 7/8/2025
Green Tag Expiration Date: 12/31/2027

Owner Details

Owner Name: GPM Midwest, LLC
Owner Address: 8565 Magellan Pkwy, Ste. 400 Richmond, VA 23227
Owner Status: Current Owner
Purchase Date: 3/19/2015
Type of Financial Responsibility: Surety Bond
Financial Responsibility Reporting Due Date: 4/24/2026

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 7/8/2025 12/31/2027

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0037728 GPM Midwest, LLC Current Owner 3/19/2015
U0024842 First Ranger Petroleum, L.L.C. Former Owner 5/8/2001
U0033990 Road Ranger, LLC Former Owner

Permits (Unexpired)

Click for permit history
Permit Number Type Status OSFM Receive Date Issue Date Expiration Date Documents
01223-2025REM Removal Approved / Revised 9/18/2025 9/18/2025 3/18/2026 Documents
01218-2025UPG Upgrade Approved / Amended 9/18/2025 9/18/2025 3/18/2026 Documents

Notice of Violatlions (Current)

NOV Number: E0020252400 (Pending)    Issue Date: 9/16/2025    Expiration Date: 11/15/2025    View NOV Form

Tanks Violations
2 Line leak detection equipment in alarm or failed test, must repair or replace. - On 9/10/2025, contactor reported: "The Regular Line FAILS; a leak was found at the primary coupling. The coupling for east line that is badly rusted and delaminating. The entire STP is badly corroded and falling apart". Tank was red taged 9/16/2025.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 8000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 5/16/2001 Abandoned Material:
Current Age: 24 Abandoned Date:
Install Date: 3/13/2001 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 3/13/2001

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 12/3/2024 12/3/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 Plus with CSLD 12/3/2024 12/3/2025
Overfill Prev Device Overfill Alarm 12/3/2024 12/3/2027
Overfill Prev Device Overfill Drop Tube Valve 9/12/2023 9/12/2026
Piping Flexible Double Wall OPW Pisces N/A N/A
Piping Single Wall STP/Tanktop Sump 9/12/2023 9/12/2026
Leak Detect - Piping Sump Sensor 12/3/2024 12/3/2025
Spill Contain Device Single Wall Spill Bucket 9/12/2023 9/12/2026
Tank Fiberglass Single Wall Containment Solutions N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall OPW Pisces Precision Test (Piping) Pass 12/3/2024



Tank Number 2

Capacity: 20000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 5/16/2001 Abandoned Material:
Current Age: 24 Abandoned Date:
Install Date: 3/13/2001 Red Tag Issue Date: 9/16/2025
Last Used Date: Fee Due: $0.00
Product Date: 3/13/2001

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 12/3/2024 12/3/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 Plus with CSLD 12/3/2024 12/3/2025
Overfill Prev Device Overfill Alarm 12/3/2024 12/3/2027
Overfill Prev Device Overfill Drop Tube Valve 9/20/2023 9/20/2026
Piping Flexible Double Wall OPW Pisces N/A N/A
Piping Single Wall STP/Tanktop Sump 9/12/2023 9/10/2025
Leak Detect - Piping Sump Sensor 12/3/2024 12/3/2025
Spill Contain Device Single Wall Spill Bucket 9/12/2023 9/12/2026
Tank Fiberglass Single Wall Containment Solutions N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall OPW Pisces Precision Test (Piping) Fail 9/10/2025

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A



Name\ID 11/12

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A



Name\ID 13/14

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A



Name\ID 15/16

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A



Name\ID 9/10

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A

MFD Motorfuel Dispensing Forms

No Forms Found