Notice of Violatlions (Current)
NOV Number:
E0020252448
(Pending)
Issue Date:
9/18/2025
Expiration Date:
11/17/2025
View NOV Form
| Tanks |
Violations |
| Facility |
Annual Emergency Stop Inspection not completed or inspection report not available. |
| 1, 2, 3 |
Annual leak detection certification not completed (Required annually). |
| 1, 2, 3 |
Document that emergency shut-off (shear valves) are in proper working order |
| 1, 2, 3 |
Line interstitial sensor functional test not accomplished (Required annually). |
| 1, 2, 3 |
Mechanical line leak detector requires annual functional test. |
| Facility |
Missing copies of Annual Walkthrough Inspection Report. |
| Facility |
Missing copies of current testing certificates for operator training |
NOV Number:
E0020253076
(Pending)
Issue Date:
11/19/2025
Expiration Date:
1/18/2026
| Tanks |
Violations |
| 2 |
Line leak detection equipment in alarm or failed test, must repair or replace. - L2 fuel alarm os active |
| 1, 2, 3 |
Monthly line interstitial sensor records not available. - Passing Liquid test reports are not present. These reposrts are part of the 30 day walk though. Only 3 reports are present for 2025, all are inventory reports. |
| 1, 2, 3 |
Required monthly tank leak test records not available. - CSLD pass reports are not present for the 30 day walk though. 3 months of data are present for inventory, not tank tests. |
| 1, 2, 3 |
Tank monitor does not appear to function properly and requires maintenance. - Function button on the ATG are not functioning properly. Response is delayed. |