Division of Petroleum & Chemical Safety

 
Pay Tank Fees Online Print Detail Page Export to Excel

Facility Details

Facility Number: 1037174
Status: Active
Facility Name: Stagecoach Fast Stop
Address: 160 E. Main Street Warren, IL 61087
County: Jo Daviess
Property Parcel: 43-21-001-716-06
Facility Type: Attended Self-Service/Unattended Self-Service
Owner Type: Private
Green Tag Decal: Z003791
Green Tag Issue Date: 6/11/2024
Green Tag Expire Date: 12/31/2026
MFD Type: Self Service; Unattended Self Service

Owner Details

Owner Name: FRMZ100, LLC
Owner Address: P.O. Box 631 Warren, IL 61087
Owner Status: Current Owner
Purchase Date: 2/8/2023
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 11/10/2026

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0040954 FRMZ100, LLC Current Owner 2/8/2023
U0034934 Arand Enterprises of Warren, Inc. Former Owner 6/12/2008
U0033068 Weeden Properties Former Owner 3/1/2004
U0027338 Koehler, Rick Former Owner 12/1/1998

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020261093 (Pending)    Issue Date: 4/22/2026    Expiration Date: 6/21/2026    View NOV Form

Tanks Violations
Facility Annual Fire Detection Test has not been performed - Annual fire detection &/or suppression system test shall be performed. Paperwork showing date of passing test shall be maintained on site with other annual testing documentation.

NOV Number: E0020261094 (Pending)    Issue Date: 4/22/2026    Expiration Date: 6/21/2026    View NOV Form

Tanks Violations
1, 2, 3 Annual electronic line leak detector test not completed. - Annual third party testing required on all line leak detectors.
Facility Annual Emergency Stop Inspection not completed or inspection report not available. - All emergency shutoff switches shall be tested annually to verify they shut down all STPs or dispensers. Perform test, complete form (form is available at www.sfm.illinois.gov) and maintain on site with other annual testing documentation
1, 2, 3 Annual leak detection certification not completed (Required annually). - Annual leak detection certification (ATG) not completed.
1, 2, 3 Flex connector sacrificial anode system not tested (required every 3 years) - Test anodes and replace as needed - Three-year third party testing required on sacrificial anode/cathodic protection system.
Facility Missing copies of 30 day Walkthrough Inspection Report. - 30-day Walkthrough Inspection shall be completed and documentation maintained on site.
Facility Missing copies of Annual Walkthrough Inspection Report. - Annual Walkthrough by a licensed contractor shall be conducted and documentation maintained on site
Facility Missing copies of current testing certificates for operator training - Copies of all current Class A/B testing certificates shall be maintained on file on site. Copies of all current Class C testing certificates shall be maintained on file on site
1, 2, 3 Overfill prevention equipment inspection(s) not completed (Required every 3 years). - Triennial inspection of overfill prevention device (overfill drop tube valve, overfill alarm, ball float valve) has not been completed.
1, 2, 3 Triennial spill prevention equipment testing not completed. - Triennial inspection of spill bucket(s) has not been completed.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 10000 Gasoline - Regular Currently in use Federal $0.00
2 5000 Gasoline - Premium Currently in use Federal $0.00
3 8000 Diesel Fuel Currently in use Federal $0.00

Dispenser Information

Name\ID Status
1/2 Active
3/4 Active
5 Active

MFD Motorfuel Dispensing Forms