Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 1033280
Status: Active
Facility Name: Sandwich Shell
Address: 222 W. Church St.
Sandwich, IL 60548
County: De Kalb
Property Parcel: 19-35-235-008
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Z001874
Green Tag Issue Date: 8/5/2024
Green Tag Expiration Date: 12/31/2026

Owner Details

Owner Name: HBPN, Inc.
Owner Address: 222 W. Church Street
Sandwich, IL 60548
Owner Status: Current Owner
Purchase Date: 6/6/2007
Type of Financial Responsibility: Certificate of Deposit
Financial Responsibility Reporting Due Date: 4/3/2026

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 8/5/2024 12/31/2026
Unattended Self Service 3/16/2018 12/31/2020

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0034452 HBPN, Inc. Current Owner 6/6/2007
U0025477 Fox Valley Oil Inc Former Owner 9/28/1994
U0000784 Arneson Oil Co Former Owner 12/31/1967

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violations (Current)

NOV Number: E0020251275 (Pending)    Issue Date: 5/15/2025    Expiration Date: 7/14/2025    View NOV Form

Tanks Violation
Facility Annual Emergency Stop Inspection not completed or inspection report not available.
1, 2 Document that emergency shut-off (shear valves) are in proper working order
Facility Financial responsibility must be reported yearly
Facility Miscellaneous - Path to ATG must be clear at all times.
Facility Missing copies of Annual Walkthrough Inspection Report.
Facility Missing copies of current testing certificates for operator training
Facility Submit Notification Form For Ownership Change

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 12000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 2/10/1997 Abandoned Material:
Current Age: 30 Abandoned Date:
Install Date: 10/30/1994 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 10/30/1994

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 2/5/2025 2/5/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS - 4c 2/5/2025 2/5/2026
Overfill Prev Device Ball Only Removed Ball Float Vent Valve N/A N/A
Overfill Prev Device Overfill Drop Tube Valve 2/27/2023 2/27/2026
Piping Flexible Double Wall N/A N/A
Piping Single Wall STP/Tanktop Sump 4/3/2023 4/3/2026
Leak Detect - Piping Sump Sensor 2/5/2025 2/5/2026
Spill Contain Device Single Wall Spill Bucket 4/3/2023 4/3/2026
Tank Fiberglass Double Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall Precision Test (Piping) Pass 2/5/2025



Tank Number 2

Capacity: 10000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 2/10/1997 Abandoned Material:
Current Age: 30 Abandoned Date:
Install Date: 10/30/1994 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 10/30/1994

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 2/5/2025 2/5/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS - 4c 2/5/2025 2/5/2026
Overfill Prev Device Ball Only Removed Ball Float Vent Valve N/A N/A
Overfill Prev Device Overfill Drop Tube Valve 2/27/2023 2/27/2026
Piping Flexible Double Wall N/A N/A
Piping Single Wall STP/Tanktop Sump 4/3/2023 4/3/2026
Leak Detect - Piping Sump Sensor 2/5/2025 2/5/2026
Spill Contain Device Single Wall Spill Bucket 4/3/2023 4/3/2026
Tank Fiberglass Double Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall Precision Test (Piping) Pass 2/5/2025

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A

MFD Motorfuel Dispensing Forms

No Forms Found