1, 2, 3 |
Failed to Empty the Tank to 1" or Less - Per 175.810(a)(1), when placing tanks out of service, the tank and lines must be emptied immediately. The UST is considered empty when all materials have been removed to one inch or less. Upon an inspection dated 12/4/18, stick readings of each tank were taken and all three tanks had more than an inch of product. Tanks were red tagged this date. |
Facility |
Financial responsibility must be reported yearly - Per 176.220, tank owners/operators must submit an electronic Financial Responsibility Report form on an annual basis. Financial Responsibility must be maintained until the tank is removed or properly abandoned in place by a licensed UST decommissiong contractor. The form can be found at: https://webapps.sfm.illinois.gov/USTPortal/Forms/FinancialResponsibility. |
1, 2, 3 |
Remove tank(s) - Single-Walled, Over 30 Years Old and OOS Over One Year - Single walled tanks were taken out of service on 10/2/18, and are 30 years old. Per 175.810(e) tanks must be removed as they are now condemned. Here is a link to the licensed UST Decommissioning contractors, that can perform UST tank removals: https://webapps.sfm.illinois.gov/ustsearch/ContractorSearch.aspx |
Facility |
Submit Notification Form For Ownership Address Change - According to the Illinois Secretary of State office, the principal mailing address is 3811 W. Lawrence Ave., Chicago, IL 60625 |
1, 2, 3 |
Submit Notification Form For Tank Status Change - Per 175.810(a)(3), tanks taken out of service are required to notify the OSFM within 30 days of date of last use, on an electronic Notification for Underground Storage Tank form, declaring a tank status change. The tanks at this location were taken out of service on 10/2/18. Here is the link to the electronic Notification for Underground Storage Tank form, so that you can file that change: https://webapps.sfm.illinois.gov/USTPortal/NotificationForm |