Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 1032955
Status: Active
Facility Name: Circle K #1397
Address: 2300 DeKalb Avenue
Sycamore, IL 60178
County: De Kalb
Property Parcel: 0801452006
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y002699
Green Tag Issue Date: 11/16/2023
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: Mac's Convenience Stores, LLC
Owner Address: 1100 Situs Court, Suite 100
Raleigh, NC 27606
Owner Status: Current Owner
Purchase Date: 10/10/2014
Type of Financial Responsibility: Guarantee
Financial Responsibility Reporting Due Date: 10/24/2025

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 11/16/2023 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0030949 Mac's Convenience Stores, LLC Current Owner 10/10/2014
U0018041 Tri Star Marketing, Inc. Former Owner 7/11/1994
U0013268 Tri-Star Marketing, Inc. Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violations (Current)

NOV Number: E0020250947 (Pending)    Issue Date: 4/9/2025    Expiration Date: 6/8/2025    View NOV Form

Tanks Violation
Facility A/B operator retraining required as a result of issuance of the Notice of Violation - Retrain the AB operator conducting the 30 day walk throughs.
1, 2, 3 Annual leak detection certification not completed (Required annually).
1, 2, 3 Miscellaneous - Locks are not functioning
Facility Missing copies of 30 day Walkthrough Inspection Report. - One inspection is apparently present for the year 2025. The present form has no dates and items not valid for this site have been maked as inspected (30 day DW spill bucket containment testing and impressed current record keeping). Complete valid 30 day inspections.
Facility Missing copies of current testing certificates for operator training - Ensure all C operators has a valid C Certification (from the entity who designed the OSFM approved course) not Circle K certificate.
Facility Missing list of designated Class A/B & C Operators - Update list for current employees.
1, 2, 3 Monthly line interstitial sensor records not available.
1, 2, 3 Required monthly tank leak test records not available.
1 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry.
1, 2, 3 Water in containment without required interstitial sensors - install cathodic protection on all exposed steel. - Dispensers 7/8 and 1/2 contain water.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 12000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 10/21/1994 Abandoned Material:
Current Age: 30 Abandoned Date:
Install Date: 9/6/1994 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 9/7/1994

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 2/26/2025 2/26/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 3/11/2024 2/26/2025
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 2/26/2025 2/26/2026
Overfill Prev Device Ball Only Removed Ball Float Vent Valve N/A N/A
Overfill Prev Device Overfill Drop Tube Valve 3/11/2024 3/11/2027
Piping Fiberglass Double Wall N/A N/A
Piping Flexible Double Wall OmegaFlex DoubleTrac N/A N/A
Piping Single Wall STP/Tanktop Sump 3/5/2025 3/5/2028
Leak Detect - Piping Sump Sensor 2/26/2025 2/26/2026
Spill Contain Device Double Wall Spill Bucket 3/11/2024 3/11/2027
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Precision Test (Piping) Pass 2/26/2025
Piping Fiberglass Double Wall A.O. Smith Precision Test (Piping) Pass 3/16/2023
Piping Flexible Double Wall OmegaFlex DoubleTrac Precision Test (Piping) Pass 2/26/2025



Tank Number 2

Capacity: 12000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 10/21/1994 Abandoned Material:
Current Age: 30 Abandoned Date:
Install Date: 9/6/1994 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 9/7/1994

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 2/26/2025 2/26/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 3/11/2024 2/26/2025
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 2/26/2025 2/26/2026
Overfill Prev Device Ball Only Removed Ball Float Vent Valve N/A N/A
Overfill Prev Device Overfill Drop Tube Valve 5/24/2024 5/24/2027
Piping Fiberglass Double Wall A.O. Smith N/A N/A
Piping Single Wall STP/Tanktop Sump 3/5/2025 3/5/2028
Leak Detect - Piping Sump Sensor 2/26/2025 2/26/2026
Spill Contain Device Double Wall Spill Bucket 3/11/2024 3/11/2027
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall A.O. Smith Precision Test (Piping) Pass 2/26/2025



Tank Number 3

Capacity: 20000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 10/21/1994 Abandoned Material:
Current Age: 30 Abandoned Date:
Install Date: 9/6/1994 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 9/7/1994

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 2/26/2025 2/26/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 3/11/2024 2/26/2025
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 2/26/2025 2/26/2026
Overfill Prev Device Ball Only Removed Ball Float Vent Valve N/A N/A
Overfill Prev Device Overfill Drop Tube Valve 4/17/2024 4/17/2027
Piping Fiberglass Double Wall A.O. Smith N/A N/A
Piping Single Wall STP/Tanktop Sump 3/5/2025 3/5/2028
Leak Detect - Piping Sump Sensor 3/16/2023 3/16/2024
Leak Detect - Piping Sump Sensor with positive shutdown 2/26/2025 2/26/2026
Spill Contain Device Double Wall Spill Bucket 4/17/2024 4/17/2027
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall A.O. Smith Precision Test (Piping) Pass 2/26/2025

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 11 /12

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 9/10

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A

MFD Motorfuel Dispensing Forms

No Forms Found