Division of Petroleum & Chemical Safety

 
Pay Tank Fees Online Print Detail Page Export to Excel

Facility Details

Facility Number: 1032955
Status: Active
Facility Name: Circle K #1397
Address: 2300 DeKalb Avenue
Sycamore, IL 60178
County: De Kalb
Property Parcel: 0801452006
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y002699
Green Tag Issue Date: 11/16/2023
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: Mac's Convenience Stores, LLC
Owner Address: 1100 Situs Court, Suite 100
Raleigh, NC 27606
Owner Status: Current Owner
Purchase Date: 10/10/2014
Type of Financial Responsibility: Guarantee
Financial Responsibility Reporting Due Date: 10/24/2025

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 11/16/2023 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0030949 Mac's Convenience Stores, LLC Current Owner 10/10/2014
U0018041 Tri Star Marketing, Inc. Former Owner 7/11/1994
U0013268 Tri-Star Marketing, Inc. Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violations (Current)

NOV Number: E0020250947 (Pending)    Issue Date: 4/9/2025    Expiration Date: 6/8/2025    View NOV Form

Tanks Violation
Facility A/B operator retraining required as a result of issuance of the Notice of Violation - Retrain the AB operator conducting the 30 day walk throughs.
1, 2, 3 Annual leak detection certification not completed (Required annually).
1, 2, 3 Miscellaneous - Locks are not functioning
Facility Missing copies of 30 day Walkthrough Inspection Report. - One inspection is apparently present for the year 2025. The present form has no dates and items not valid for this site have been maked as inspected (30 day DW spill bucket containment testing and impressed current record keeping). Complete valid 30 day inspections.
Facility Missing copies of current testing certificates for operator training - Ensure all C operators has a valid C Certification (from the entity who designed the OSFM approved course) not Circle K certificate.
Facility Missing list of designated Class A/B & C Operators - Update list for current employees.
1, 2, 3 Monthly line interstitial sensor records not available.
1, 2, 3 Required monthly tank leak test records not available.
1 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry.
1, 2, 3 Water in containment without required interstitial sensors - install cathodic protection on all exposed steel. - Dispensers 7/8 and 1/2 contain water.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 12000 Gasoline - Premium Currently in use Federal $0.00
2 12000 Gasoline - Regular Currently in use Federal $0.00
3 20000 Gasoline - Regular Currently in use Federal $0.00

Dispenser Information

Name\ID Status
1/2 Active
11 /12 Active
3/4 Active
5/6 Active
7/8 Active
9/10 Active

MFD Motorfuel Dispensing Forms

No Forms Found