Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 1027991
Status: Active
Facility Name: Circle K #1247
Address: 920 East Main Street
Streator, IL 61364
County: LaSalle
Property Parcel: 33-25-430-024
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y002283
Green Tag Issue Date: 4/18/2023
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: Mac's Convenience Stores, LLC
Owner Address: 1100 Situs Court, Suite 100
Raleigh, NC 27606
Owner Status: Current Owner / Operator
Purchase Date: 4/14/2005
Type of Financial Responsibility: Guarantee
Financial Responsibility Reporting Due Date: 10/24/2025

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 4/18/2023 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0030949 Mac's Convenience Stores, LLC Current Owner / Operator 4/14/2005
U0001977 Broadus Oil Corp Former Owner / Operator

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violations (Current)

NOV Number: E0020251087 (Pending)    Issue Date: 4/22/2025    Expiration Date: 6/21/2025    View NOV Form

Tanks Violation
1, 2, 3 Dispensers - hoses cracked, split or worn and require replacement - Hose is very weathered and cracked. Bag until replacement can be performed
Facility Missing copies of current testing certificates for operator training
Facility Missing list of designated Class A/B & C Operators
1, 2, 3 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry.

NOV Number: E0020251088 (Pending)    Issue Date: 4/22/2025    Expiration Date: 6/21/2025    View NOV Form

Tanks Violation
Facility Fire Extinguishers - Past due for annual testing

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
05-0498 Eligible 5/9/2005 6/21/2005 $10,000
Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 10000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 4/25/1990 Abandoned Material:
Current Age: 35 Abandoned Date:
Install Date: 1/1/1990 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 10/15/1989

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Flex Connector 10/7/2024 10/7/2027
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 1/7/2025 1/7/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 Plus with CSLD 1/7/2025 1/7/2026
Overfill Prev Device Overfill Drop Tube Valve 1/31/2024 1/31/2027
Piping Flex Connector Steel N/A N/A
Piping Fiberglass Single Wall Piping N/A N/A
Piping Not Installed STP/Tanktop Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A
Spill Contain Device Double Wall Spill Bucket 1/31/2024 1/31/2027
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Single Wall Piping Precision Test (Piping) Pass 1/7/2025



Tank Number 2

Capacity: 10000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 4/25/1990 Abandoned Material:
Current Age: 35 Abandoned Date:
Install Date: 1/1/1990 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 10/15/1989

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Flex Connector 10/7/2024 10/7/2027
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 1/7/2025 1/7/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 Plus with CSLD 1/7/2025 1/7/2026
Overfill Prev Device Overfill Drop Tube Valve 1/31/2024 1/31/2027
Piping Flex Connector Steel N/A N/A
Piping Fiberglass Single Wall Piping N/A N/A
Piping Not Installed STP/Tanktop Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A
Spill Contain Device Single Wall Spill Bucket 1/31/2024 1/31/2027
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Single Wall Piping Precision Test (Piping) Pass 1/7/2025



Tank Number 3

Capacity: 8000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 4/25/1990 Abandoned Material:
Current Age: 35 Abandoned Date:
Install Date: 1/1/1990 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 10/15/1989

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Flex Connector 10/7/2024 10/7/2027
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 1/7/2025 1/7/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 Plus with CSLD 1/7/2025 1/7/2026
Overfill Prev Device Overfill Drop Tube Valve 1/31/2024 1/31/2027
Piping Flex Connector Steel N/A N/A
Piping Fiberglass Single Wall Piping N/A N/A
Piping Not Installed STP/Tanktop Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A
Spill Contain Device Single Wall Spill Bucket 1/31/2024 1/31/2027
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Single Wall Piping Precision Test (Piping) Pass 1/7/2025

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A

MFD Motorfuel Dispensing Forms