Notice of Violatlions (Current)
NOV Number:
E0020261028
(Pending)
Issue Date:
4/16/2026
Expiration Date:
6/15/2026
View NOV Form
| Tanks |
Violations |
| 1, 2, 3 |
Dispensers - hoses cracked, split or worn and require replacement |
| Facility |
Missing copies of 30 day Walkthrough Inspection Report. |
| 1, 4 |
Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. |
| 1, 4 |
Water in containment without required sensors – install cathodic protection on all exposed steel piping or make containment watertight. By 10/13/28, all containments must be watertight and any CP installed in containments must be removed. - STP's |