Notice of Violations (Current)
NOV Number:
E0020242002
(Referred to Legal)
Issue Date:
7/17/2024
Expiration Date:
9/15/2024
View NOV Form
Tanks |
Violation |
3 |
Line interstitial sensor functional test not accomplished (Required annually). - Annual third party testing required on all line interstitial sensors. TRANSITION SUMP |
3 |
Overfill prevention equipment inspection(s) not completed (Required every 3 years). - Triennial inspection of overfill prevention device (overfill drop tube valve, overfill alarm, ball float valve) has not been completed TESTING NEEDED ON OVERFILL ALARM |
3 |
Triennial testing for qualifying piping containment sump not completed (Required every 3 years). -
Triennial testing for qualifying dispenser containment sump(s) failed test. Repair/replace as necessary to pass retesting of sump(s). , DISPENSER 3/4 SUMP |