2 |
Containment support components are cracked, deteriorated or missing. The cover and supporting components that are defective shall be replaced with factory manufactured components. - Tank 2 STP sump lid cracked and handle is broken, repair or replace.
Section 175.410 Submersible, Under-dispenser, Transition and Other Containment Sumps
a) All containment sumps must consist of a factory manufactured containment that is
liquid-tight on its sides, bottom and at any penetrations and is compatible with the
substance conveyed by the piping. Such containment shall also have a factory
manufactured protective cover and supporting components that are properly
maintained. If the protective cover or its supporting components are cracked,
deteriorated or missing, the cover and supporting components that are defective
shall be replaced. |