Owner Summary
Click for Facility/Tank Ownership history
| Owner Number |
Owner Name |
Owner Status |
Purchase Date |
| U0039333 |
Wahe, Inc. |
Current Owner |
6/1/2018 |
| U0037946 |
Alpine Oil, LLC |
Former Owner |
2/1/2013 |
| U0028334 |
KRKH Investments, Inc. |
Former Owner |
12/20/2004 |
| U0014941 |
Texor Petroleum Company, Inc. |
Former Owner |
9/7/2004 |
| U0026531 |
DO NOT USE THIS OWNER ID - Casey's General Stores |
Former Owner |
8/27/1999 |
| U0026552 |
Speedway, LLC |
Former Owner |
1/1/1999 |
| U0009659 |
Marathon Petroleum Company LP |
Former Owner |
12/31/1967 |
| U0036810 |
Gasland Express, Inc. |
Former Owner |
|
Notice of Violations (Current)
NOV Number:
E0020252981
(Referred to Legal)
Issue Date:
11/7/2025
Expiration Date:
1/6/2026
View NOV Form
| Tanks |
Violations |
| 12 |
Overfill prevention equipment is missing and must be re-installed. - Tank overfill device/drop tube is missing. Replace with approved overfill device. Failed report 11/3/2025 |
| 12 |
Tank monitor does not appear to function properly and requires maintenance. - Tank “Probe Out” indicated on ATG. Repair/replace as necessary to clear ATG alarm. Failed report 11/3/2025 |
NOV Number:
E0020260056
(Referred to Legal)
Issue Date:
1/8/2026
Expiration Date:
3/9/2026
View NOV Form
| Tanks |
Violations |
| Facility |
Financial responsibility must be reported yearly - Financial Responsibility shall be declared annually; declaration form can be found at www.sfm.illinois.gov (in Search window, type UST Forms, Click Enter; click UST Applications and Forms; click on Financial Responsibility Report). Complete form online and submit electronically. |
NOV Number:
E0020261768
(Pending)
Issue Date:
7/9/2026
Expiration Date:
9/7/2026
View NOV Form
| Tanks |
Violations |
| 8, 9, 10, 11, 12 |
Failed to Empty the Tank to 1" or Less - Tank(s) is/are currently not in service and shall be pumped down to one inch or less of product. |
| 8, 9, 10, 11, 12 |
Submit Notification Form For Tank Status Change - Submit OSFM Notification Form placing all tanks in Temporarily Out of Use status. Notification form is available at www.sfm.illinois.gov |
IEMA Numbers Associated with the Facility
| IEMA Number |
Inspection Date |
Inspection Type |
Permit Number |
| 992-313 |
10/12/1999 |
Removal Log |
02861-1999REM |
LUST
Fund Eligibility and Deductibility Determinations
| IEMA Number |
Status |
OSFM Received Date |
OSFM Response Date |
Deductible |
Letter |
| 99-2313 |
Eligible |
9/17/2001
|
10/3/2001
|
$10,000
|
|
| 99-2248 |
Eligible |
9/17/2001
|
10/3/2001
|
$10,000
|
|
Tank Number 1
| Capacity: |
6000 |
|
Petroleum Use: |
|
| Product: |
Gasoline |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
10/12/1999 |
|
OSFM
First Notify Date: |
4/30/1986 |
|
Abandoned Material: |
|
| Current Age: |
26 |
|
Abandoned Date: |
|
| Install Date: |
|
|
Red Tag Issue Date: |
|
| Last Used Date: |
11/30/1998 |
|
Fee Due: |
$0.00 |
| Product Date: |
|
|
|
|
Equipment Information
No Equipment Listed
Additional Tests
No Tests Listed
Tank Number 2
| Capacity: |
6000 |
|
Petroleum Use: |
|
| Product: |
Gasoline |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
10/12/1999 |
|
OSFM
First Notify Date: |
4/30/1986 |
|
Abandoned Material: |
|
| Current Age: |
26 |
|
Abandoned Date: |
|
| Install Date: |
|
|
Red Tag Issue Date: |
|
| Last Used Date: |
11/30/1998 |
|
Fee Due: |
$0.00 |
| Product Date: |
|
|
|
|
Equipment Information
No Equipment Listed
Additional Tests
No Tests Listed
Tank Number 3
| Capacity: |
6000 |
|
Petroleum Use: |
|
| Product: |
Gasoline |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
10/12/1999 |
|
OSFM
First Notify Date: |
4/30/1986 |
|
Abandoned Material: |
|
| Current Age: |
26 |
|
Abandoned Date: |
|
| Install Date: |
|
|
Red Tag Issue Date: |
|
| Last Used Date: |
11/30/1998 |
|
Fee Due: |
$0.00 |
| Product Date: |
|
|
|
|
Equipment Information
No Equipment Listed
Additional Tests
No Tests Listed
Tank Number 4
| Capacity: |
6000 |
|
Petroleum Use: |
|
| Product: |
Gasoline |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
10/12/1999 |
|
OSFM
First Notify Date: |
4/30/1986 |
|
Abandoned Material: |
|
| Current Age: |
26 |
|
Abandoned Date: |
|
| Install Date: |
|
|
Red Tag Issue Date: |
|
| Last Used Date: |
11/30/1998 |
|
Fee Due: |
$0.00 |
| Product Date: |
|
|
|
|
Equipment Information
No Equipment Listed
Additional Tests
No Tests Listed
Tank Number 5
| Capacity: |
6000 |
|
Petroleum Use: |
|
| Product: |
Gasoline |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
10/12/1999 |
|
OSFM
First Notify Date: |
4/30/1986 |
|
Abandoned Material: |
|
| Current Age: |
26 |
|
Abandoned Date: |
|
| Install Date: |
|
|
Red Tag Issue Date: |
|
| Last Used Date: |
11/30/1998 |
|
Fee Due: |
$0.00 |
| Product Date: |
|
|
|
|
Equipment Information
No Equipment Listed
Additional Tests
No Tests Listed
Tank Number 6
| Capacity: |
550 |
|
Petroleum Use: |
|
| Product: |
Used Oil |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
10/12/1999 |
|
OSFM
First Notify Date: |
4/30/1986 |
|
Abandoned Material: |
|
| Current Age: |
26 |
|
Abandoned Date: |
|
| Install Date: |
|
|
Red Tag Issue Date: |
|
| Last Used Date: |
11/30/1998 |
|
Fee Due: |
$0.00 |
| Product Date: |
|
|
|
|
Equipment Information
No Equipment Listed
Additional Tests
No Tests Listed
Tank Number 7
| Capacity: |
1000 |
|
Petroleum Use: |
Consumptive Use on Premises for Heating |
| Product: |
Heating Oil |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
State |
|
Removed Date: |
10/12/1999 |
|
OSFM
First Notify Date: |
12/5/1991 |
|
Abandoned Material: |
|
| Current Age: |
25 |
|
Abandoned Date: |
|
| Install Date: |
|
|
Red Tag Issue Date: |
|
| Last Used Date: |
11/30/1998 |
|
Fee Due: |
$0.00 |
| Product Date: |
|
|
|
|
Equipment Information
No Equipment Listed
Additional Tests
No Tests Listed
Tank Number 8
| Capacity: |
12000 |
|
Petroleum Use: |
Dispensing |
| Product: |
Gasoline - Regular |
|
CERCLA Substance: |
|
| Status: |
Out of service |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
8/30/1999 |
|
Abandoned Material: |
|
| Current Age: |
26 |
|
Abandoned Date: |
|
| Install Date: |
10/14/1999 |
|
Red Tag Issue Date: |
3/26/2026 |
| Last Used Date: |
7/9/2026 |
|
Fee Due: |
$0.00 |
| Product Date: |
12/6/1999 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Flexible Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Mechanical Pressurized Line Leak Detection |
11/3/2025 |
11/3/2026 |
|
Leak Detect - Piping
|
Siphon Bar |
Not applicable |
Not applicable |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 350R with CSLD |
11/3/2025 |
11/3/2026 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
11/3/2025 |
11/3/2028 |
|
Piping
|
Flexible Double Wall |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
Not applicable |
Not applicable |
Leak Detect - Piping
|
Piping Sump Sensors Not Regulated Not Required |
Not applicable |
Not applicable |
|
Spill Contain Device
|
Single Wall Spill Bucket |
11/3/2025 |
11/3/2028 |
|
Tank
|
Fiberglass Single Wall |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Leak Detect - Piping
|
Siphon Bar
|
Functional
|
Pass
|
7/2/2024
|
|
Piping
|
Flexible Double Wall
|
Precision Test (Piping)
|
Pass
|
11/3/2025
|
Tank Number 9
| Capacity: |
12000 |
|
Petroleum Use: |
Dispensing |
| Product: |
Gasoline - Regular |
|
CERCLA Substance: |
|
| Status: |
Out of service |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
8/30/1999 |
|
Abandoned Material: |
|
| Current Age: |
26 |
|
Abandoned Date: |
|
| Install Date: |
10/14/1999 |
|
Red Tag Issue Date: |
3/26/2026 |
| Last Used Date: |
7/9/2026 |
|
Fee Due: |
$0.00 |
| Product Date: |
12/6/1999 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Flexible Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Mechanical Pressurized Line Leak Detection |
11/3/2025 |
11/3/2026 |
|
Leak Detect - Piping
|
Siphon Bar |
Not applicable |
Not applicable |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 350R with CSLD |
11/3/2025 |
11/3/2026 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
11/3/2025 |
11/3/2028 |
|
Piping
|
Flexible Double Wall |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
Not applicable |
Not applicable |
Leak Detect - Piping
|
Piping Sump Sensors Not Regulated Not Required |
Not applicable |
Not applicable |
|
Spill Contain Device
|
Single Wall Spill Bucket |
11/3/2025 |
11/3/2028 |
|
Tank
|
Fiberglass Single Wall |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Leak Detect - Piping
|
Siphon Bar
|
Functional
|
Pass
|
7/2/2024
|
|
Piping
|
Flexible Double Wall
|
Precision Test (Piping)
|
Pass
|
11/3/2025
|
Tank Number 10
| Capacity: |
10000 |
|
Petroleum Use: |
Dispensing |
| Product: |
Gasoline - Premium |
|
CERCLA Substance: |
|
| Status: |
Out of service |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
8/30/1999 |
|
Abandoned Material: |
|
| Current Age: |
26 |
|
Abandoned Date: |
|
| Install Date: |
10/14/1999 |
|
Red Tag Issue Date: |
3/26/2026 |
| Last Used Date: |
7/9/2026 |
|
Fee Due: |
$0.00 |
| Product Date: |
12/6/1999 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Flexible Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Mechanical Pressurized Line Leak Detection |
11/3/2025 |
11/3/2026 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 350R with CSLD |
11/3/2025 |
11/3/2026 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
6/1/2023 |
6/1/2026 |
|
Piping
|
Flexible Double Wall |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
Not applicable |
Not applicable |
Leak Detect - Piping
|
Piping Sump Sensors Not Regulated Not Required |
Not applicable |
Not applicable |
|
Spill Contain Device
|
Double Wall Spill Bucket |
6/1/2023 |
6/1/2026 |
|
Spill Contain Device
|
Single Wall Spill Bucket |
6/1/2023 |
6/1/2026 |
|
Tank
|
Fiberglass Single Wall |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Flexible Double Wall
|
Precision Test (Piping)
|
Pass
|
11/3/2025
|
Tank Number 11
| Capacity: |
4000 |
|
Petroleum Use: |
Dispensing |
| Product: |
Diesel Fuel |
|
CERCLA Substance: |
|
| Status: |
Out of service |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
8/30/1999 |
|
Abandoned Material: |
|
| Current Age: |
26 |
|
Abandoned Date: |
|
| Install Date: |
10/14/1999 |
|
Red Tag Issue Date: |
3/26/2026 |
| Last Used Date: |
7/9/2026 |
|
Fee Due: |
$0.00 |
| Product Date: |
12/6/1999 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Flexible Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Mechanical Pressurized Line Leak Detection |
11/3/2025 |
11/3/2026 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 350R with CSLD |
11/3/2025 |
11/3/2026 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
11/3/2025 |
11/3/2028 |
|
Piping
|
Flexible Double Wall |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
Not applicable |
Not applicable |
Leak Detect - Piping
|
Piping Sump Sensors Not Regulated Not Required |
Not applicable |
Not applicable |
|
Spill Contain Device
|
Double Wall Spill Bucket |
1/1/2025 |
1/1/2028 |
|
Tank
|
Fiberglass Single Wall |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Flexible Double Wall
|
Precision Test (Piping)
|
Pass
|
11/3/2025
|
Tank Number 12
| Capacity: |
4000 |
|
Petroleum Use: |
Dispensing |
| Product: |
Racing Fuel |
|
CERCLA Substance: |
|
| Status: |
Out of service |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
8/30/1999 |
|
Abandoned Material: |
|
| Current Age: |
26 |
|
Abandoned Date: |
|
| Install Date: |
10/14/1999 |
|
Red Tag Issue Date: |
11/7/2025 |
| Last Used Date: |
7/9/2026 |
|
Fee Due: |
$0.00 |
| Product Date: |
12/6/1999 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Flexible Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
European with No Test Req Suction |
Not applicable |
Not applicable |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 350R with CSLD |
7/2/2024 |
7/2/2025 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
4/17/2022 |
4/17/2025 |
|
Piping
|
Flexible Double Wall |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
Not applicable |
Not applicable |
Leak Detect - Piping
|
Piping Sump Sensors Not Regulated Not Required |
Not applicable |
Not applicable |
|
Spill Contain Device
|
Single Wall Spill Bucket |
11/3/2025 |
11/3/2028 |
|
Tank
|
Fiberglass Single Wall |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Flexible Double Wall
|
Precision Test (Piping)
|
Pass
|
4/14/2022
|
Failed test = the latest test has failed.
Not applicable = a test does not apply to this equipment type or configuration.
No passing test found = a passing test is expected but was not found from the source data.
MFD
Motorfuel Dispensing Forms
No Forms Found