Notice of Violatlions (Current)
NOV Number:
E0020252284
(Pending)
Issue Date:
9/2/2025
Expiration Date:
11/1/2025
View NOV Form
| Tanks |
Violations |
| 8, 9, 10, 11, 12 |
Annual leak detection certification not completed (Required annually). - Annual leak detection certification (ATG) not completed. |
| 8, 9, 10, 11, 12 |
Annual line precision and mechanical line leak detector functional test not completed. - Annual third party testing required on all line leak detectors. |
| 8, 9, 11, 12 |
Overfill prevention equipment inspection(s) not completed (Required every 3 years). - Triennial inspection of overfill prevention device (overfill drop tube valve, overfill alarm, ball float valve) has not been completed. |
| 8, 9, 12 |
Spill prevention equipment failed triennial testing. Must be repaired or replaced. - Triennial inspection of spill bucket(s) has not been completed. |
NOV Number:
E0020252981
(Pending)
Issue Date:
11/7/2025
Expiration Date:
1/6/2026
View NOV Form
| Tanks |
Violations |
| 12 |
Overfill prevention equipment is missing and must be re-installed. - Tank overfill device/drop tube is missing. Replace with approved overfill device. Failed report 11/3/2025 |
| 12 |
Tank monitor does not appear to function properly and requires maintenance. - Tank “Probe Out” indicated on ATG. Repair/replace as necessary to clear ATG alarm. Failed report 11/3/2025 |