Division of Petroleum & Chemical Safety

 
Pay Tank Fees Online Print Detail Page Export to Excel

Facility Details

Facility Number: 1009857
Status: Active
Facility Name: Rochelle Shell
Address: 505 W. Highway 38
Rochelle, IL 61068
County: Ogle
Property Parcel: 24-24-126-052
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y003249
Green Tag Issue Date: 12/5/2023
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: Amisa, Inc.
Owner Address: 1400 Dekalb Ave
De Kalb, IL 60178
Owner Status: Current Owner
Purchase Date: 10/22/2009
Type of Financial Responsibility: Designated Savings Account
Financial Responsibility Reporting Due Date: 12/5/2025

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 12/5/2023 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0035635 Amisa, Inc. Current Owner 10/22/2009
U0008040 Johnson Oil Company Former Owner 4/26/2007
U0004864 Etna Oil Co., Inc. Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violations (Current)

NOV Number: E0020250933 (Pending)    Issue Date: 4/8/2025    Expiration Date: 6/7/2025    View NOV Form

Tanks Violation
Facility A/B operator retraining required as a result of issuance of the Notice of Violation
Facility Facility Operation and Maintenance Plan not completed or available.
Facility Financial responsibility must be reported yearly - Applies to new owner/operator. This is done online at : https://webapps.sfm.illinois.gov/USTPortal/forms/FinancialResponsibility
5, 6 Line interstitial sensors have been raised and rendered inoperational. - STP sensors on Tank 5 and 6 are raised. Remove water and place sensors in correct location.
Facility Miscellaneous - Section 175.410 Submersible, Under-dispenser, Transition and Other Containment Sumps a) All containment sumps must consist of a factory manufactured containment that is liquid-tight on its sides, bottom and at any penetrations and is compatible with the substance conveyed by the piping. Such containment shall also have a factory manufactured protective cover and supporting components that are properly maintained. If the protective cover or its supporting components are cracked, deteriorated or missing, the cover and supporting components that are defective shall be replaced. T4 (RUL) lid is missing handle, T 4 (RUL) inner lid has deteriored and can no longer function to keep loquid out of the containment.
Facility Missing copies of 30 day Walkthrough Inspection Report.
Facility Missing copy of emergency instructions or emergency procedures plan
Facility Missing list of designated Class A/B & C Operators
4, 5, 6 Required monthly tank interstitial sensor records not available.
4, 5, 6 Water in containment with required interstitial sensors - Remove water and repair containments to prevent water ingress. - STPs Tanks 5 and 6. Dispensers 1/2, 3/4, 7,8. Note, sensors in UDC are not in the lowest point of the containment.

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
n/a 8/18/2009 Removal Log 00697-2009REM

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
07-0503 Eligible 6/7/2007 7/9/2007 $10,000
Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 10000 Gasoline Removed Federal $0.00 08/18/2009 - REM
2 10000 Gasoline Removed Federal $0.00 08/18/2009 - REM
3 10000 Gasoline Removed Federal $0.00 08/18/2009 - REM
4 12000 Gasoline - Regular Currently in use Federal $0.00
5 6000 Gasoline - Premium Currently in use Federal $0.00
6 6000 Diesel Fuel Currently in use Federal $0.00

Dispenser Information

Name\ID Status
1/2 InActive
3/4 Active
5/6 Active
7/8 Active
1/2 Active

MFD Motorfuel Dispensing Forms

No Forms Found