Owner Summary
Click for Facility/Tank Ownership history
| Owner Number |
Owner Name |
Owner Status |
Purchase Date |
| U0027497 |
IL Central Management Services |
Current Owner |
3/18/1998 |
| U0007245 |
Illinois Department of Central Management Services |
Former Owner |
12/31/1967 |
Notice of Violations (Current)
NOV Number:
E0020252514
(Referred to Legal)
Issue Date:
9/24/2025
Expiration Date:
11/23/2025
View NOV Form
| Tanks |
Violations |
| 3 |
Failed to Empty the Tank to 1" or Less - Per 175.810(a)(1), when placing tanks out of service, the tank and lines must be emptied immediately. The UST is considered empty when all materials have been removed to one inch or less. Upon my inspection on 6/25/25, I took a stick reading of each tank and tank #3 had 8 inches of product still in the tank. Product must be removed immediately |
| Facility |
Financial responsibility must be reported yearly - Per 176.220, tank owners/operators must submit and electronic Financial Responsibility (FR) Report form on an annual basis. FR must be maintained until the tanks are either removed or properly abandoned in place by a licensed UST decommissioning contractor. The last FR report form expired on 12/31/22. Here is the link to the electronic Financial Responsibility Report form: https://webapps.sfm.illinois.gov/USTPortal/Forms/FinancialResponsibility |
| 3 |
Submit Notification Form For Tank Status Change - Per 175.810(a)(3), tanks taken out of service (OOS) are required to notify the OSFM within 30 days of date of last use, on an electronic Notification for Underground Storage Tank form, declaring a tank status change. Tank #3 was taken OOS on 6/5/23. Here is the link to the electronic Notification for Underground Storage Tank form, so that you can file that change: https://webapps.sfm.illinois.gov/USTPortal/NotificationForm |
IEMA Numbers Associated with the Facility
| IEMA Number |
Inspection Date |
Inspection Type |
Permit Number |
| 98-1077 |
5/7/1998 |
Removal Log |
|
LUST
Fund Eligibility and Deductibility Determinations
No Applications Found
Tank Number 1
| Capacity: |
10000 |
|
Petroleum Use: |
|
| Product: |
Diesel Fuel |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
5/9/1998 |
|
OSFM
First Notify Date: |
3/17/1986 |
|
Abandoned Material: |
|
| Current Age: |
18 |
|
Abandoned Date: |
|
| Install Date: |
1/1/1980 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
5/7/1998 |
|
Fee Due: |
$0.00 |
| Product Date: |
1/1/1980 |
|
|
|
Equipment Information
No Equipment Listed
Additional Tests
No Tests Listed
Tank Number 2
| Capacity: |
10000 |
|
Petroleum Use: |
|
| Product: |
Gasoline |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
5/9/1998 |
|
OSFM
First Notify Date: |
3/17/1986 |
|
Abandoned Material: |
|
| Current Age: |
30 |
|
Abandoned Date: |
|
| Install Date: |
1/1/1968 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
5/7/1998 |
|
Fee Due: |
$0.00 |
| Product Date: |
1/1/1968 |
|
|
|
Equipment Information
No Equipment Listed
Additional Tests
No Tests Listed
Tank Number 3
| Capacity: |
10000 |
|
Petroleum Use: |
|
| Product: |
Diesel Fuel |
|
CERCLA Substance: |
|
| Status: |
Out of service |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
8/7/1998 |
|
Abandoned Material: |
|
| Current Age: |
28 |
|
Abandoned Date: |
|
| Install Date: |
3/18/1998 |
|
Red Tag Issue Date: |
10/31/2023 |
| Last Used Date: |
6/5/2023 |
|
Fee Due: |
$0.00 |
| Product Date: |
3/18/1998 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Mechanical Pressurized Line Leak Detection |
5/11/2021 |
5/11/2022 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Petro Vend Site Sentinel Model II |
5/11/2021 |
5/11/2022 |
|
Leak Detect - Tank
|
Non-Discriminating Interstitial Monitoring Sensors |
11/4/2020 |
5/11/2021 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
9/16/2019 |
9/16/2022 |
|
Piping
|
Fiberglass Double Wall |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
1/8/2020 |
1/8/2023 |
Leak Detect - Piping
|
Sump Sensor |
1/8/2020 |
1/8/2023 |
|
Spill Contain Device
|
Single Wall Spill Bucket |
9/16/2019 |
9/16/2022 |
|
Tank
|
Fiberglass Double Wall Fluid Containment |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Fiberglass Double Wall
|
Precision Test (Piping)
|
Pass
|
5/11/2021
|
Tank Number 4
| Capacity: |
10000 |
|
Petroleum Use: |
|
| Product: |
Gasohol |
|
CERCLA Substance: |
|
| Status: |
Out of service |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
8/7/1998 |
|
Abandoned Material: |
|
| Current Age: |
28 |
|
Abandoned Date: |
|
| Install Date: |
3/18/1998 |
|
Red Tag Issue Date: |
10/31/2023 |
| Last Used Date: |
6/5/2023 |
|
Fee Due: |
$0.00 |
| Product Date: |
3/18/1998 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Mechanical Pressurized Line Leak Detection |
5/11/2021 |
5/11/2022 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Petro Vend Site Sentinel Model II |
5/11/2021 |
5/11/2022 |
|
Leak Detect - Tank
|
Non-Discriminating Interstitial Monitoring Sensors |
7/21/2020 |
5/11/2021 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
9/16/2019 |
9/16/2022 |
|
Piping
|
Fiberglass Double Wall |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
1/8/2020 |
1/8/2023 |
Leak Detect - Piping
|
Sump Sensor |
1/8/2020 |
1/8/2023 |
|
Spill Contain Device
|
Single Wall Spill Bucket |
9/16/2019 |
9/16/2022 |
|
Tank
|
Fiberglass Double Wall Fluid Containment |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Fiberglass Double Wall
|
Precision Test (Piping)
|
Pass
|
5/11/2021
|
Tank Number 5
| Capacity: |
100 |
|
Petroleum Use: |
None |
| Product: |
Fuel Oil |
|
CERCLA Substance: |
|
| Status: |
Entered in error |
|
CAS Code: |
|
| Regulated Status: |
Non-Regulated |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
|
|
Abandoned Material: |
|
| Current Age: |
|
|
Abandoned Date: |
|
| Install Date: |
|
|
Red Tag Issue Date: |
|
| Last Used Date: |
12/31/1973 |
|
Fee Due: |
$0.00 |
| Product Date: |
|
|
|
|
Equipment Information
No Equipment Listed
Additional Tests
No Tests Listed
Tank Number 6
| Capacity: |
2000 |
|
Petroleum Use: |
|
| Product: |
Gasoline |
|
CERCLA Substance: |
|
| Status: |
Entered in error |
|
CAS Code: |
|
| Regulated Status: |
Non-Regulated |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
|
|
Abandoned Material: |
|
| Current Age: |
|
|
Abandoned Date: |
|
| Install Date: |
|
|
Red Tag Issue Date: |
|
| Last Used Date: |
12/31/1973 |
|
Fee Due: |
$0.00 |
| Product Date: |
|
|
|
|
Equipment Information
No Equipment Listed
Additional Tests
No Tests Listed
Failed test = the latest test has failed.
Not applicable = a test does not apply to this equipment type or configuration.
No passing test found = a passing test is expected but was not found from the source data.
Dispenser Information
Name\ID 1/2
| Status: |
Active |
|
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Dispenser
|
Single Wall UDC Sump |
Not applicable
|
Not applicable
|
Leak Detect - Piping
|
Piping Sump Sensors Not Regulated Not Required |
Not applicable
|
Not applicable
|
Name\ID 3/4
| Status: |
Active |
|
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Dispenser
|
Single Wall UDC Sump |
Not applicable
|
Not applicable
|
Leak Detect - Piping
|
Piping Sump Sensors Not Regulated Not Required |
Not applicable
|
Not applicable
|