Division of Petroleum & Chemical Safety

 
Pay Tank Fees Online Print Detail Page Export to Excel

Facility Details

Facility Number: 1005924
Status: Active
Facility Name: Thriving Thistle Market
Address: 300 West Hickory Apple River, IL 61001
County: Jo Daviess
Property Parcel:
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y001272
Green Tag Issue Date: 3/20/2023
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: Geoff Stocks
Owner Address: 4845 N. Hacker Rd. Apple River, IL 61001
Owner Status: Current Owner
Purchase Date: 10/1/2016
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 3/20/2024

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 3/20/2023 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0038551 Stocks, Geoff Current Owner 10/1/2016
U0035661 Optimum Ventures, LLC Former Owner 12/27/2012
U0014314 Ron Sproule Oil Company Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020251973 (Pending)    Issue Date: 8/6/2025    Expiration Date: 10/5/2025    View NOV Form

Tanks Violations
Facility Annual Emergency Stop Inspection not completed or inspection report not available. - All emergency shutoff switches shall be tested annually to verify they shut down all STPs or dispensers. Perform test, complete form (form is available at www.sfm.illinois.gov) and maintain on site with other annual testing documentation.
6 Annual leak detection certification not completed (Required annually). - Annual leak detection certification (ATG) not completed.
6 Annual leak detection certification not completed (Required annually). - Annual third party testing required on all line leak detectors.
7 Annual leak detection certification not completed (Required annually). - Annual leak detection certification (ATG) not completed.
7 Annual leak detection certification not completed (Required annually). - Annual third party testing required on all line leak detectors.
8 Annual leak detection certification not completed (Required annually). - Annual leak detection certification (ATG) not completed.
8 Annual leak detection certification not completed (Required annually). - Annual third party testing required on all line leak detectors.
Facility Financial responsibility must be reported yearly - Financial Responsibility shall be declared annually; declaration form can be found at www.sfm.illinois.gov (in Search window, type UST Forms, Click Enter; click UST Applications and Forms; click on Financial Responsibility Report). Complete form online and submit electronically.
6, 7, 8 Line interstitial sensor functional test not accomplished (Required annually). - Annual third party testing required on all line interstitial sensors.
Facility Missing copies of 30 day Walkthrough Inspection Report. - 30-day Walkthrough Inspection shall be completed and documentation maintained on site.
Facility Missing copies of Annual Walkthrough Inspection Report. - Annual Walkthrough by a licensed contractor shall be conducted and documentation maintained on site.
Facility Missing copies of current testing certificates for operator training - Financial Responsibility shall be declared annually; declaration form can be found at www.sfm.illinois.gov (in Search window, type UST Forms, Click Enter; click UST Applications and Forms; click on Financial Responsibility Report). Complete form online and submit electronically.
6, 7, 8 Overfill prevention equipment inspection(s) not completed (Required every 3 years). - Triennial inspection of overfill prevention device (overfill drop tube valve, overfill alarm, ball float valve) has not been completed
6, 7, 8 Triennial spill prevention equipment testing not completed. - Triennial inspection of spill bucket(s) has not been completed.
6, 7, 8 Triennial testing for qualifying piping containment sump not completed (Required every 3 years). - Triennial testing for qualifying STP piping containment sump(s) not completed. Triennial testing for qualifying dispenser containment sump(s) not completed.

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
14-1272 12/15/2014 Removal Log 01107-2014REM
91-1022 4/16/1991 Removal Log

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
14-1272 Eligible 1/5/2015 2/17/2015 $5,000
Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 2000 Bio-Diesel Removed Federal $0.00 12/15/2014 - REM
2 4000 Gasoline Removed Federal $0.00 12/15/2014 - REM
3 560 Kerosene Removed Federal $0.00 12/15/2014 - REM
4 1000 Diesel Fuel Removed Federal $0.00 05/01/1991 - REM
5 2000 Gasoline Removed Federal $0.00 05/01/1991 - REM
6 6000 Gasoline - Regular Currently in use Federal $0.00
7 3000 Gasoline - Non Ethanol Currently in use Federal $0.00
8 3000 Diesel Fuel Currently in use Federal $0.00

Dispenser Information

Name\ID Status
1/2 Active

MFD Motorfuel Dispensing Forms

Facility Number Name City Received Date Letter
1005924 Thriving Thistle Market Apple River 01/04/2017 Letter Form