Notice of Violations (Current)
NOV Number:
E0020250267
(Pending)
Issue Date:
2/3/2025
Expiration Date:
4/4/2025
View NOV Form
Tanks |
Violation |
7 |
Tank monitor does not appear to function properly and requires maintenance. - ATG in alarm " Tank 3 high water" 1 inch of water is detected in the tank by the probe. Water finding paste did not confirm water in the tank. Reset probe to remove the alarm |