Division of Petroleum & Chemical Safety

 

Facility: 2044293 Tank: 4

Click for Facility/Tank Ownership history

Capacity: 8000
Product: E85
Status: Currently in use
Regulated Status Federal
OSFM First Notify Date: 3/15/2010
Current Age: 15
Install Date: 4/17/2009
Last Used Date:
Product Date: 1/22/2010
Petroleum Use:
CERCLA Substance:
CAS Code:
Removed Date:
Abandoned Material:
Abandoned Date:
Red Tag Issue Date:
Fee Due: $0.00
UL Number

Equipment Information

Equipment Type Equipment Install Date Last Passing Test Date Test Expire Date Failed Test Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 12/4/2024 12/4/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 4/22/2022 12/4/2024 12/4/2025
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 4/22/2022 12/4/2024 12/4/2025
Overfill Prev Device Overfill Drop Tube Valve 9/8/2020 12/21/2022 12/21/2025
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 12/4/2024 12/4/2027
Leak Detect - Piping Sump Sensor with positive shutdown 12/4/2024 12/4/2025
Spill Contain Device Single Wall Spill Bucket 12/4/2024 12/4/2027
Tank Fiberglass Double Wall XERXES N/A N/A
Vent, Riser, Fill Piping Steel risers N/A N/A

Latest Blended Fuel Compatibility Form

File Name Status Status Date
CompatibilityFormSummary04272022-093018.pdf Approved 4/27/2022

Compatibility Form Attachments

File Name Description
Veeder Root E85 probe 577013-054.pdf ATG Probe
FFS-0691 UL 2447 Listed Products.pdf Dispenser 19/20 UDC
FFS-0691 UL 2447 Listed Products.pdf Dispenser 7/8 UDC
Veeder Root PLLD.pdf Electronic Pressurized Line Leak Detection
Zerxes Tank Compatibility Statement.pdf Fiberglass Double Wall
Ameron Pipe Compatibility Statement.pdf Fiberglass Double Wall
Veeder Root Sensor Compatibility Statement.pdf Non-Discriminating Interstitial Monitoring Sensors
Veeder Root Sensor Compatibility Statement.pdf Non-Discriminating Sump Sensor in Single Wall STP/Tanktop Sump
OPW 71SOM_Overfill_Prevention_Valve.pdf Overfill Drop Tube Valve
OPW FCS Material Compatiblity Matrix 2018 revised 072018.pdf Single Wall Spill Bucket
ZCL-XERXES-Sump-Brochure-web-16.pdf Single Wall STP/Tanktop Sump
FE Petro STP Compatibility Statement.pdf Submersible Turbine Pump

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date History
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test (Piping) Pass 12/4/2024 Show History
Tank Fiberglass Double Wall XERXES Precision Test (Tank) Pass 5/23/2024 Show History