Division of Petroleum & Chemical Safety

 

Facility: 2018605 Tank: 19

Click for Facility/Tank Ownership history

Capacity: 20000
Product: B-99
Status: Currently in use
Regulated Status Federal
OSFM First Notify Date: 4/7/2025
Current Age: 0
Install Date: 2/11/2025
Last Used Date:
Product Date: 3/24/2025
Petroleum Use:
CERCLA Substance:
CAS Code:
Removed Date:
Abandoned Material:
Abandoned Date:
Red Tag Issue Date:
Fee Due: $0.00
UL Number G39662874

Equipment Information

Equipment Type Equipment Install Date Last Passing Test Date Test Expire Date Failed Test Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 3/27/2025 3/27/2025 3/27/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 Plus 3/27/2025 3/27/2025 3/27/2026
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors With Monitor 3/27/2025 3/27/2025 3/27/2026
Overfill Prev Device Overfill Drop Tube Valve 3/27/2025 3/27/2025 3/27/2028
Piping Fiberglass Double Wall Ameron 3/27/2025 N/A N/A
Piping Fiberglass Single Wall Piping Ameron 4000 L single wall vent 3/27/2025 N/A N/A
Piping Single Wall STP/Tanktop Sump 2/27/2025 2/27/2025 2/27/2028
Leak Detect - Piping Sump Sensor with positive shutdown 3/27/2025 3/27/2025 3/27/2026
Piping Single Wall Transition Sump 2/27/2025 2/27/2025 2/27/2028
Leak Detect - Piping Sump Sensor with positive shutdown 3/27/2025 3/27/2025 3/27/2026
Spill Contain Device Double Wall Spill Bucket 2/27/2025 2/27/2025 2/27/2028
Tank Fiberglass Double Wall Containment Solutions 2/11/2025 N/A N/A

Latest Blended Fuel Compatibility Form

File Name Status Status Date
CompatibilityFormSummary01062025-143428.pdf Approved 1/6/2025

Compatibility Form Attachments

File Name Description
18-Veeder-Root Fuel Compatibility Letter - Executed - 2015-09-23.pdf ATG Probe
13-Encore UL Approval_BioDiesel.pdf Dispenser
OPW Compatibility BUCKET.pdf Double Wall Spill Bucket
16-Bravo_Fittings_AlternativeFuels_R3.pdf Entry Boot w Seal
Containment-Solutions compatibility Letter.pdf Fiberglass Double Wall
10-NOV.pdf Fiberglass Double Wall
304 Sensor.pdf Interstice Sensor
FE Leak.pdf Mechanical Pressurized Line Leak Detection
OPW Compatibility OPV.pdf Overfill Drop Tube Valve
11-GASOILA-TDS-hard-set.pdf Pipe Dope
15-Bravo_Sumps_AlternativeFuels_R3.pdf Single Wall STP/Tanktop Sump
15-Bravo_Sumps_AlternativeFuels_R3.pdf Single Wall Transition Sump
FFS-0796 Submersible Turbine Pumps Datasheet.pdf Submersible Turbine Pump
18-Veeder-Root Fuel Compatibility Letter - Executed - 2015-09-23.pdf Sump Sensor with positive shutdown

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date History
Piping Fiberglass Double Wall Ameron Precision Test (Piping) Pass 3/27/2025 Show History
Piping Fiberglass Single Wall Piping Ameron 4000 L single wall vent Precision Test (Piping) Pass 3/27/2025 Show History
Tank Fiberglass Double Wall Containment Solutions Precision Test (Tank) Pass 3/27/2025 Show History