Division of Petroleum & Chemical Safety

 

Facility: 2047675 Tank: 3

Click for Facility/Tank Ownership history

Capacity: 6000
Product: E85
Status: Currently in use
Regulated Status Federal
OSFM First Notify Date: 8/19/2024
Current Age: 0
Install Date: 11/16/2023
Last Used Date:
Product Date: 8/12/2024
Petroleum Use:
CERCLA Substance:
CAS Code:
Removed Date:
Abandoned Material:
Abandoned Date:
Red Tag Issue Date:
Fee Due: $0.00
UL Number

Equipment Information

Equipment Type Equipment Install Date Last Passing Test Date Test Expire Date Failed Test Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 7/9/2024 8/12/2024 8/12/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 7/9/2024 8/12/2024 8/12/2025
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 7/9/2024 8/12/2024 8/12/2025
Overfill Prev Device Overfill Drop Tube Valve 8/12/2024 8/12/2024 8/12/2027
Piping Flexible Double Wall NUPI Smartflex 7/9/2024 N/A N/A
Piping Single Wall STP/Tanktop Sump 7/9/2024 8/12/2024 8/12/2027
Leak Detect - Piping Sump Sensor with positive shutdown 7/9/2024 8/12/2024 8/12/2025
Spill Contain Device Double Wall Spill Bucket 8/12/2024 8/12/2024 8/12/2027
Tank Fiberglass Double Wall Containment Solutions 11/16/2023 N/A N/A

Latest Blended Fuel Compatibility Form

File Name Status Status Date
CompatibilityFormSummary11072023-133457.pdf Approved 11/8/2023

Compatibility Form Attachments

File Name Description
Veeder Root E85 probe 577013-054.pdf ATG Probe
WAYNE MH1821-45-6 Ovation CertificateofCompliance.pdf Dispenser
OPW Belowground Product Compatibility Listing 071518.pdf Double Wall Spill Bucket
Veeder Root PLLD.pdf Electronic Pressurized Line Leak Detection
CSI alcohol compatibility statement 9-25-03.pdf Fiberglass Double Wall
NUPI UL LETTER - COMPATIBILITY.pdf Flexible Double Wall
Goodyear E85 Ethanol hose.pdf Hose
Veeder Root Sensor Compatibility Statement.pdf Non-Discriminating Interstitial Monitoring Sensors
OPW 11a-and-11b-automatic-nozzles.pdf Nozzle
OPW 71SOM_Overfill_Prevention_Valve.pdf Overfill Drop Tube Valve
Gasoila E-Seal.pdf PIPE DOPE
OPW 10_Plus_Series_Emergency_Shut-Off_Valves.pdf Shear Valve
Bravo Sump Compatibility Statement.pdf Single Wall STP/Tanktop Sump
NUPI UL LETTER - COMPATIBILITY.pdf SINGLE WALL UDC
FE Petro STP Compatibility Statement.pdf Submersible Turbine Pump
Veeder Root Sensor Compatibility Statement.pdf Sump Sensor with positive shutdown

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date History
Piping Flexible Double Wall NUPI Smartflex Precision Test (Piping) Pass 8/12/2024 Show History
Tank Fiberglass Double Wall Containment Solutions Precision Test (Tank) Pass 8/12/2024 Show History