Division of Petroleum & Chemical Safety

 

Facility: 2043486 Tank: 2

Click for Facility/Tank Ownership history

Capacity: 15000
Product: Diesel Fuel
Status: Currently in use
Regulated Status Federal
OSFM First Notify Date: 4/5/2007
Current Age: 18
Install Date: 12/27/2006
Last Used Date:
Product Date: 12/27/2006
Petroleum Use: Back-up Generator
CERCLA Substance:
CAS Code:
Removed Date:
Abandoned Material:
Abandoned Date:
Red Tag Issue Date:
Fee Due: $0.00
UL Number

Equipment Information

Equipment Type Equipment Install Date Last Passing Test Date Test Expire Date Failed Test Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive 11/14/2006 N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection Northwest 3/11/2025 3/11/2026
Leak Detect - Piping Electronic Pressurized Line Leak Detection Southeast 3/11/2025 3/11/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 Plus 3/11/2025 3/11/2026
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 3/11/2025 3/11/2026
Overfill Prev Device Overfill Alarm 4/3/2023 4/3/2026
Overfill Prev Device Overfill Drop Tube Valve 11/14/2006 4/3/2023 4/3/2026
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX 11/14/2006 N/A N/A
Piping Single Wall STP/Tanktop Sump 12/20/2019 4/3/2023 4/3/2026
Leak Detect - Piping Sump Sensor 11/15/2022 3/11/2025 3/11/2026
Spill Contain Device Single Wall Spill Bucket 4/3/2023 4/3/2026
Tank Fiberglass Double Wall Containment Solutions 11/14/2006 N/A N/A

Latest Blended Fuel Compatibility Form

No Compatibility Forms Listed


Additional Tests

Equipment Type Equipment Test Type Test Result Test Date History
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test (Piping) Pass 3/11/2025 Show History