Division of Petroleum & Chemical Safety

 

Facility: 2025797 Tank: 5

Click for Facility/Tank Ownership history

Capacity: 25000
Product: Diesel Fuel
Status: Currently in use
Regulated Status Federal
OSFM First Notify Date: 7/18/2016
Current Age: 9
Install Date: 10/22/2015
Last Used Date:
Product Date:
Petroleum Use: Back-up Generator
CERCLA Substance:
CAS Code:
Removed Date:
Abandoned Material:
Abandoned Date:
Red Tag Issue Date:
Fee Due: $0.00
UL Number

Equipment Information

Equipment Type Equipment Install Date Last Passing Test Date Test Expire Date Failed Test Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection West 12/27/2024 12/27/2025
Leak Detect - Piping Electronic Pressurized Line Leak Detection East 12/27/2024 12/27/2025
Leak Detect - Tank Hydrostatic Reservoir Interstitial Monitoring Sensors with monitor 12/27/2024 12/27/2025
Overfill Prev Device Overfill Alarm 12/27/2024 12/27/2027
Overfill Prev Device Overfill Drop Tube Valve 12/27/2024 12/27/2027
Piping Flexible Double Wall OmegaFlex DoubleTrac N/A N/A
Piping Double Wall STP/Tanktop Sump South 12/27/2024 12/27/2027
Leak Detect - Piping Sump Sensor 12/27/2024 12/27/2025
Piping Double Wall STP/Tanktop Sump North 12/27/2024 12/27/2027
Leak Detect - Piping Sump Sensor 12/27/2024 12/27/2025
Piping Single Wall Transition Sump Westmoreland North 12/27/2024 12/27/2027
Leak Detect - Piping Sump Sensor 12/27/2024 12/27/2025
Piping Single Wall Transition Sump Westmoreland South 1/26/2023 12/27/2024 12/27/2027
Leak Detect - Piping Sump Sensor 12/27/2024 12/27/2025
Piping Single Wall Transition Sump Building North 12/27/2024 12/27/2027
Leak Detect - Piping Sump Sensor 12/27/2024 12/27/2025
Piping Single Wall Transition Sump Building South 12/27/2024 12/27/2027
Leak Detect - Piping Sump Sensor 12/27/2024 12/27/2025
Spill Contain Device Single Wall Spill Bucket 12/27/2024 12/27/2027
Tank Fiberglass Brine Filled Double Wall XERXES N/A N/A

Latest Blended Fuel Compatibility Form

No Compatibility Forms Listed


Additional Tests

Equipment Type Equipment Test Type Test Result Test Date History
Piping Flexible Double Wall OmegaFlex DoubleTrac Precision Test (Piping) Pass 12/27/2024 Show History