Capacity: 10000
Product: E85
Status: Currently in use
Regulated Status Federal
OSFM First Notify Date: 10/15/2019
Current Age: 6
Install Date: 8/8/2019
Last Used Date:
Product Date:
Petroleum Use:
CERCLA Substance:
CAS Code:
Removed Date:
Abandoned Material:
Abandoned Date:
Red Tag Issue Date:
Fee Due: $0.00
UL Number B-84395160

Equipment Information

Equipment Type Equipment Install Date Last Passing Test Date Test Expire Date Failed Test Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 7/17/2025 7/17/2026
Leak Detect - Tank Hydrostatic Reservoir Interstitial Monitoring Sensors 7/17/2025 7/17/2026
Overfill Prev Device Overfill Drop Tube Valve 7/28/2025 7/28/2028
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 9/9/2019 8/6/2025 8/6/2028
Leak Detect - Piping Sump Sensor with positive shutdown 7/17/2025 7/17/2026
Spill Contain Device Double Wall Spill Bucket 9/9/2019 7/17/2025 7/17/2028
Tank Fiberglass Double Wall XERXES 8/8/2019 N/A N/A

Latest Blended Fuel Compatibility Form

File Name Status Status Date
CompatibilityFormSummary11142024-151210.pdf Approved 11/19/2024

Compatibility Form Attachments

File Name Description
Veeder Root Sensors.pdf ATG Probe
Cap and Ring E85 Compatibility.pdf Caps and Rings
Cap and Ring E85 Compatibility.pdf Caps and Rings
Defender spill bucket.pdf Double Wall Spill Bucket
Defender spill bucket.pdf Double Wall Spill Bucket
Veeder Root Sensors.pdf Electronic Pressurized Line Leak Detection
Veeder Root Sensors.pdf Electronic Pressurized Line Leak Detection
Ameron Piping.pdf Fiberglass Double Wall
Ameron Piping.pdf Fiberglass Double Wall
Xerxes.pdf Fiberglass Double Wall
Xerxes.pdf Fiberglass Double Wall
Fire flex flexes.pdf Flex Connector
Fire flex flexes.pdf Flex Connector
Gilbarco.pdf Gilbarco Dispensers
Gilbarco.pdf Gilbarco Dispensers
E85 sensors.pdf Hydrostatic Reservoir Interstitial Monitoring Sensors
Veeder Root Sensors.pdf Non-Discriminating Sump Sensor with positive shutdown in Single Wall STP/Tanktop Sump
Veeder Root Sensors.pdf Non-Discriminating Sump Sensor with positive shutdown in Single Wall STP/Tanktop Sump
Catlow.pdf Nozzles and hoses
Catlow.pdf Nozzles and hoses
OPW Drop tube Adapters Impact Valves.pdf Overfill Drop Tube Valve
OPW Drop tube Adapters Impact Valves.pdf Overfill Drop Tube Valve
Gasoila Pipe dope.pdf Pipe Dope
Gasoila Pipe dope.pdf Pipe Dope
OPW Drop tube Adapters Impact Valves.pdf Shear Valves
OPW Drop tube Adapters Impact Valves.pdf Shear Valves
Xerxes Containment Sump Upgrades (1).pdf Single Wall STP/Tanktop Sump
Xerxes Containment Sump Upgrades (1).pdf Single Wall STP/Tanktop Sump
Bravo Sumps.pdf Single wall UDC
Bravo Sumps.pdf Single wall UDC
Fe Petro Subs.pdf Submersible Pump
Fe Petro Subs.pdf Submersible Pump

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date History
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test (Piping) Pass 12/30/2019 Show History
Tank Fiberglass Double Wall XERXES Precision Test (Tank) Pass 12/30/2019 Show History