Division of Petroleum & Chemical Safety

 

Facility: 2007980 Tank: 9

Click for Facility/Tank Ownership history

Capacity: 20000
Product: B-99
Status: Currently in use
Regulated Status Federal
OSFM First Notify Date: 1/21/2026
Current Age: 0
Install Date: 11/20/2025
Last Used Date:
Product Date: 1/7/2026
Petroleum Use: None
CERCLA Substance:
CAS Code:
Removed Date:
Abandoned Material:
Abandoned Date:
Red Tag Issue Date:
Fee Due: $0.00
UL Number G39662866

Equipment Information

Equipment Type Equipment Install Date Last Passing Test Date Test Expire Date Failed Test Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 1/19/2026 1/19/2026 1/19/2027
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 Plus 1/19/2026 1/19/2026 1/19/2027
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors With Monitor 1/19/2026 1/19/2026 1/19/2027
Overfill Prev Device Overfill Drop Tube Valve 1/16/2026 1/16/2026 1/16/2029
Piping Blending Sump 1/19/2026 12/17/2025 12/17/2028
Leak Detect - Piping Sump Sensor with positive shutdown 1/19/2026 1/19/2026 1/19/2027
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX 1/20/2026 N/A N/A
Piping Single Wall STP/Tanktop Sump 1/19/2026 12/17/2025 12/17/2028
Leak Detect - Piping Sump Sensor with positive shutdown East 1/19/2026 1/19/2026 1/19/2027
Leak Detect - Piping Sump Sensor with positive shutdown West 1/19/2026 1/19/2026 1/19/2027
Piping Single Wall Transition Sump 12/17/2025 12/17/2025 12/17/2028
Spill Contain Device Double Wall Spill Bucket 12/17/2025 12/17/2025 12/17/2028
Tank Fiberglass Double Wall Containment Solutions 11/20/2025 N/A N/A

Latest Blended Fuel Compatibility Form

File Name Status Status Date
CompatibilityFormSummary10242025-101317.pdf Approved 10/24/2025

Compatibility Form Attachments

File Name Description
Veeder Root Probe Biodiesel Approval Letter.pdf ATG Probe
T-SS-1001N.pdf Ball Valves
PCI-BioDiesel.pdf Blending Sump
opw-1-2100-series-2018 (4).pdf Double Wall Spill Bucket
Containment Solutions Tanks and Sumps.pdf Fiberglass Double Wall
Ameron Piping.pdf Fiberglass Double Wall
Ameron Piping.pdf Fiberglass Single Wall Piping single wall vent
FFS-0391 MLD+ Mechanical Leak Detectors Datasheet.pdf Mechanical Pressurized Line Leak Detection
Veeder Root Sump & Interstitial Sensors.pdf Non-Discriminating Interstitial Monitoring Sensors With Monitor
OPW Compatibility Matrix.pdf Overfill Drop Tube Valve
Gasoila.pdf Pipe Dope
FFS-0796 Submersible Turbine Pumps Datasheet.pdf Seals
opw-10-plus-series-emergency-shut-off-valves-2018.pdf Shear Valve
Containment Solutions Tanks and Sumps.pdf Single Wall STP/Tanktop Sump
PCI-BioDiesel.pdf Single Wall Transition Sump
PCI-BioDiesel.pdf Single Wall UDC Sump
FFS-0796 Submersible Turbine Pumps Datasheet.pdf Submersible Turbine Pump
794380-321.pdf Sump Sensor with positive shutdown
794380-321.pdf Sump Sensor with positive shutdown
794380-321.pdf Sump Sensor with positive shutdown

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date History
Piping Blending Sump Precision Test (Piping) Pass 1/20/2026 Show History
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test (Piping) Pass 1/20/2026 Show History
Tank Fiberglass Double Wall Containment Solutions Precision Test (Tank) Pass 1/19/2026 Show History