Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 7047069
Status: Active
Facility Name: Road Ranger 279
Address: 1701 IL Route 148 Marion, IL 62959
County: Williamson
Property Parcel: 10-28-200-007
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Z001109
Green Tag Issue Date: 2/11/2025
Green Tag Expire Date: 12/31/2026
MFD Type: Self Service

Owner Details

Owner Name: Road Ranger, LLC
Owner Address: 1501 Woodfield Rd., Suite 300 S Schaumburg, IL 60173
Owner Status: Current Owner
Purchase Date: 9/25/2019
Type of Financial Responsibility: Self-Insurance
Financial Responsibility Reporting Due Date: 10/1/2026

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0033990 Road Ranger, LLC Current Owner 9/25/2019

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020260407 (Pending)    Issue Date: 2/20/2026    Expiration Date: 5/29/2026    View NOV Form

Tanks Violations
Facility Annual Emergency Stop Inspection not completed or inspection report not available.
4, 5 Line interstitial sensors have been raised and rendered inoperational. - Bio Shed sump sensor raised out of liquid. Remove liquid and lower sensor to bottom of containment.
4, 5 Line leak detection equipment in alarm or failed test, must repair or replace. - Mechanical line leak detectors failed annual testing.
Facility Missing copies of Annual Walkthrough Inspection Report.
Facility Missing copies of current testing certificates for operator training - Missing A/B Operator certificate for Paul Ramsey (Hinderliter Construction and Maint.) Expired A/B and C Certificates in binder, update certificates.
Facility Missing list of designated Class A/B & C Operators - Update list.
4, 5 Monthly line interstitial sensor records not available. - L2: South Diesel sump sensor missing from programming. Diesel Dispensers #17, #18, and #21 missing from programming (L20, L21, L24).
1 Overfill prevention equipment does not appear to function properly. - Failed inspection, repair and submit passing inspection.
1, 2, 4, 5 Shear valve inspection report not completed (Required during Annual Walkthrough Inspection).

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 12000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 11/4/2020 Abandoned Material:
Current Age: 5 Abandoned Date:
Install Date: 7/10/2020 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 10/23/2020

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 2/12/2026 2/12/2027
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors With Monitor 2/12/2026 2/12/2027
Overfill Prev Device Overfill Alarm 2/12/2026 2/12/2029
Overfill Prev Device Overfill Drop Tube Valve 11/6/2023 2/12/2026
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 2/12/2026 2/12/2029
Leak Detect - Piping Non-Discriminating Sump Sensor with positive shutdown
Leak Detect - Piping Sump Sensor with positive shutdown 2/12/2026 2/12/2027
Spill Contain Device Single Wall Spill Bucket 2/12/2026 2/12/2029
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test (Piping) Pass 2/5/2025
Tank Fiberglass Double Wall XERXES Precision Test (Tank) Pass 2/5/2025



Tank Number 2

Capacity: 20000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 11/4/2020 Abandoned Material:
Current Age: 5 Abandoned Date:
Install Date: 7/10/2020 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 10/23/2020

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 2/12/2026 2/12/2027
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 2/12/2026 2/12/2027
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors With Monitor 2/12/2026 2/12/2027
Overfill Prev Device Overfill Alarm 2/12/2026 2/12/2029
Overfill Prev Device Overfill Drop Tube Valve 2/12/2026 2/12/2029
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 2/12/2026 2/12/2029
Leak Detect - Piping Non-Discriminating Sump Sensor with positive shutdown 10/29/2020 10/29/2021
Leak Detect - Piping Sump Sensor with positive shutdown 2/12/2026 2/12/2027
Spill Contain Device Single Wall Spill Bucket 2/12/2026 2/12/2029
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test (Piping) Pass 2/5/2025
Tank Fiberglass Double Wall XERXES Precision Test (Tank) Pass 2/5/2025



Tank Number 3

Capacity: 20000 Petroleum Use:
Product: 100% Soy Oil (Non-Regulated) CERCLA Substance:
Status: Unknown CAS Code:
Regulated Status: Non-Regulated Removed Date:
OSFM First Notify Date: 11/4/2020 Abandoned Material:
Current Age: 5 Abandoned Date:
Install Date: 7/10/2020 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 10/23/2020

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 Plus
Overfill Prev Device Overfill Alarm
Overfill Prev Device Overfill Drop Tube Valve
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump
Leak Detect - Piping Sump Sensor with positive shutdown 10/26/2021 10/26/2022
Spill Contain Device Single Wall Spill Bucket
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 4

Capacity: 20000 Petroleum Use: None
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 11/4/2020 Abandoned Material:
Current Age: 5 Abandoned Date:
Install Date: 7/10/2020 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 10/23/2020

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 2/5/2025 2/5/2026
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 2/5/2025 2/5/2026
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors With Monitor 2/12/2026 2/12/2027
Overfill Prev Device Overfill Alarm 2/12/2026 2/12/2029
Overfill Prev Device Overfill Drop Tube Valve 2/12/2026 2/12/2029
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 2/12/2026 2/12/2029
Leak Detect - Piping Non-Discriminating Sump Sensor with positive shutdown
Leak Detect - Piping Sump Sensor with positive shutdown 2/12/2026 2/12/2027
Spill Contain Device Single Wall Spill Bucket 2/12/2026 2/12/2029
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test (Piping) Pass 2/5/2025
Tank Fiberglass Double Wall XERXES Precision Test (Tank) Pass 2/5/2025



Tank Number 5

Capacity: 20000 Petroleum Use: None
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 11/4/2020 Abandoned Material:
Current Age: 5 Abandoned Date:
Install Date: 7/10/2020 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 10/23/2020

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 2/5/2025 2/5/2026
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 2/5/2025 2/5/2026
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors With Monitor 2/12/2026 2/12/2027
Overfill Prev Device Overfill Alarm 2/12/2026 2/12/2029
Overfill Prev Device Overfill Drop Tube Valve 2/12/2026 2/12/2029
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 2/12/2026 2/12/2029
Leak Detect - Piping Non-Discriminating Sump Sensor with positive shutdown 10/29/2020 10/29/2021
Leak Detect - Piping Sump Sensor with positive shutdown 2/12/2026 2/12/2027
Spill Contain Device Single Wall Spill Bucket 2/12/2026 2/12/2029
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test (Piping) Pass 2/5/2025
Tank Fiberglass Double Wall XERXES Precision Test (Tank) Pass 2/5/2025

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 2/12/2026 2/12/2029
Leak Detect - Piping Sump Sensor with positive shutdown 2/12/2026 2/12/2027



Name\ID 11/12

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 2/12/2026 2/12/2029
Leak Detect - Piping Sump Sensor with positive shutdown 2/12/2026 2/12/2027



Name\ID 13/14

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 2/12/2026 2/12/2029
Leak Detect - Piping Sump Sensor with positive shutdown 2/12/2026 2/12/2027



Name\ID 15/16

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 2/12/2026 2/12/2029
Leak Detect - Piping Sump Sensor with positive shutdown 2/12/2026 2/12/2027



Name\ID 17

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 2/12/2026 2/12/2029
Leak Detect - Piping Sump Sensor with positive shutdown 2/12/2026 2/12/2027



Name\ID 17 Satellite

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 2/12/2026 2/12/2029
Leak Detect - Piping Sump Sensor with positive shutdown 2/12/2026 2/12/2027



Name\ID 18

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 2/12/2026 2/12/2029
Leak Detect - Piping Sump Sensor with positive shutdown 2/12/2026 2/12/2027



Name\ID 19

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 2/12/2026 2/12/2029
Leak Detect - Piping Sump Sensor with positive shutdown 2/12/2026 2/12/2027



Name\ID 20

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 2/12/2026 2/12/2029
Leak Detect - Piping Sump Sensor with positive shutdown 2/12/2026 2/12/2027



Name\ID 21

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 2/12/2026 2/12/2029
Leak Detect - Piping Sump Sensor with positive shutdown 2/12/2026 2/12/2027



Name\ID 22

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 2/12/2026 2/12/2029
Leak Detect - Piping Sump Sensor with positive shutdown 2/12/2026 2/12/2027



Name\ID 23

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 2/12/2026 2/12/2029
Leak Detect - Piping Sump Sensor with positive shutdown 2/12/2026 2/12/2027



Name\ID 24

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 2/12/2026 2/12/2029
Leak Detect - Piping Sump Sensor with positive shutdown 2/12/2026 2/12/2027



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 2/12/2026 2/12/2029
Leak Detect - Piping Sump Sensor with positive shutdown 2/12/2026 2/12/2027



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 2/12/2026 2/12/2029
Leak Detect - Piping Sump Sensor with positive shutdown 2/12/2026 2/12/2027



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 2/12/2026 2/12/2029
Leak Detect - Piping Sump Sensor with positive shutdown 2/12/2026 2/12/2027



Name\ID 9/10

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 2/12/2026 2/12/2029
Leak Detect - Piping Sump Sensor with positive shutdown 2/12/2026 2/12/2027

MFD Motorfuel Dispensing Forms

Facility Number Name City Received Date Letter
7047069 Road Ranger 279 Marion 06/24/2020 Letter Form