Notice of Violations (Current)
NOV Number:
E0020261391
(Pending)
Issue Date:
5/27/2026
Expiration Date:
7/26/2026
View NOV Form
| Tanks |
Violations |
| 1, 2 |
Dispensers - hoses cracked, split or worn and require replacement |
| 1, 2, 3 |
Miscellaneous - Dispensers - the following are actively leaking and require immediate repair(bagged at inspection) |
| 1, 2 |
Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. |
| 1 |
Submit Notification Form for Product Change - RUL is E-15. |
| 1 |
The Blended Fuel Compatibility Form for products greater than E10 and B20 has not been submitted as required. |
IEMA Numbers Associated with the Facility
No IEMA Numbers Found
LUST
Fund Eligibility and Deductibility Determinations
No Applications Found
Tank Number 1
| Capacity: |
15000 |
|
Petroleum Use: |
|
| Product: |
E15 |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
9/20/2016 |
|
Abandoned Material: |
|
| Current Age: |
10 |
|
Abandoned Date: |
|
| Install Date: |
6/21/2016 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
6/21/2016 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Mechanical Pressurized Line Leak Detection |
9/3/2025 |
9/3/2026 |
|
Leak Detect - Piping
|
Mechanical Pressurized Line Leak Detection |
9/3/2025 |
9/3/2026 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 450 Plus with CSLD |
9/3/2025 |
9/3/2026 |
|
Leak Detect - Tank
|
Non-Discriminating Interstitial Monitoring Sensors |
9/3/2025 |
9/3/2026 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
9/4/2024 |
9/4/2027 |
|
Piping
|
Fiberglass Double Wall Ameron Dualoy 3000/LCX |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
9/4/2024 |
9/4/2027 |
Leak Detect - Piping
|
Sump Sensor with positive shutdown |
9/4/2024 |
9/4/2027 |
|
Piping
|
Single Wall STP/Tanktop Sump |
9/4/2024 |
9/4/2027 |
Leak Detect - Piping
|
Sump Sensor with positive shutdown |
9/4/2024 |
9/4/2027 |
|
Spill Contain Device
|
Double Wall Spill Bucket |
9/4/2024 |
9/4/2027 |
|
Tank
|
Fiberglass Double Wall XERXES |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Fiberglass Double Wall Ameron Dualoy 3000/LCX
|
Precision Test (Piping)
|
Pass
|
9/3/2025
|
Tank Number 2
| Capacity: |
10000 |
|
Petroleum Use: |
|
| Product: |
Gasoline - Premium |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
9/20/2016 |
|
Abandoned Material: |
|
| Current Age: |
10 |
|
Abandoned Date: |
|
| Install Date: |
6/21/2016 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
6/21/2016 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Mechanical Pressurized Line Leak Detection |
9/3/2025 |
9/3/2026 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 450 Plus with CSLD |
9/3/2025 |
9/3/2026 |
|
Leak Detect - Tank
|
Non-Discriminating Interstitial Monitoring Sensors |
9/3/2025 |
9/3/2026 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
9/4/2024 |
9/4/2027 |
|
Piping
|
Fiberglass Double Wall Ameron Dualoy 3000/LCX |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
9/4/2024 |
9/4/2027 |
Leak Detect - Piping
|
Sump Sensor with positive shutdown |
9/4/2024 |
9/4/2027 |
|
Spill Contain Device
|
Double Wall Spill Bucket |
9/4/2024 |
9/4/2027 |
|
Tank
|
Fiberglass Double Wall XERXES |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Fiberglass Double Wall Ameron Dualoy 3000/LCX
|
Precision Test (Piping)
|
Pass
|
9/3/2025
|
Tank Number 3
| Capacity: |
10000 |
|
Petroleum Use: |
|
| Product: |
Diesel Fuel |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
9/20/2016 |
|
Abandoned Material: |
|
| Current Age: |
10 |
|
Abandoned Date: |
|
| Install Date: |
6/21/2016 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
6/21/2016 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Mechanical Pressurized Line Leak Detection |
9/3/2025 |
9/3/2026 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 450 Plus with CSLD |
9/3/2025 |
9/3/2026 |
|
Leak Detect - Tank
|
Non-Discriminating Interstitial Monitoring Sensors |
9/3/2025 |
9/3/2026 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
9/4/2024 |
9/4/2027 |
|
Piping
|
Fiberglass Double Wall Ameron Dualoy 3000/LCX |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
9/4/2024 |
9/4/2027 |
Leak Detect - Piping
|
Sump Sensor with positive shutdown |
9/4/2024 |
9/4/2027 |
|
Spill Contain Device
|
Double Wall Spill Bucket |
9/4/2024 |
9/4/2027 |
|
Tank
|
Fiberglass Double Wall XERXES |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Fiberglass Double Wall Ameron Dualoy 3000/LCX
|
Precision Test (Piping)
|
Pass
|
9/3/2025
|
Tank Number 4
| Capacity: |
6000 |
|
Petroleum Use: |
|
| Product: |
Diesel Exhaust Fluid (Non-Regulated) |
|
CERCLA Substance: |
|
| Status: |
Unknown |
|
CAS Code: |
|
| Regulated Status: |
Non-Regulated |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
9/20/2016 |
|
Abandoned Material: |
|
| Current Age: |
10 |
|
Abandoned Date: |
|
| Install Date: |
6/21/2016 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
|
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Electronic Pressurized Line Leak Detection |
No passing test found |
No passing test found |
|
Leak Detect - Piping
|
Sump Sensor |
No passing test found |
No passing test found |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 450 |
No passing test found |
No passing test found |
|
Leak Detect - Tank
|
Non-Discriminating Interstitial Monitoring Sensors |
No passing test found |
No passing test found |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
No passing test found |
No passing test found |
|
Piping
|
Fiberglass Double Wall Ameron Dualoy 3000/LCX |
Not applicable |
Not applicable |
|
Piping
|
Flex Connector Steel |
Not applicable |
Not applicable |
|
Piping
|
Other Submersible Pump |
Not applicable |
Not applicable |
|
Piping
|
Fiberglass Secondary Containment Ameron |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
No passing test found |
No passing test found |
|
Spill Contain Device
|
Double Wall Spill Bucket |
No passing test found |
No passing test found |
|
Tank
|
Fiberglass Double Wall XERXES |
Not applicable |
Not applicable |
Additional Tests
No Tests Listed
Failed test = the latest test has failed.
Not applicable = a test does not apply to this equipment type or configuration.
No passing test found = a passing test is expected but was not found from the source data.
MFD
Motorfuel Dispensing Forms
No Forms Found