Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 7044785
Status: Active
Facility Name: Walkers Bluff General Store
Address: 429 West Vermont Carterville, IL 62918
County: Williamson
Property Parcel: 06-15-304-001
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: AA03617
Green Tag Issue Date: 7/2/2025
Green Tag Expire Date: 12/31/2027
MFD Type: Self Service

Owner Details

Owner Name: Sundmann Land Holdings
Owner Address: 14400 Meridian Rd Carterville, IL 62918
Owner Status: Current Owner
Purchase Date:
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 2/2/2027

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0035900 Sundmann Land Holdings Current Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violations (Current)

NOV Number: E0020261528 (Pending)    Issue Date: 6/12/2026    Expiration Date: 8/11/2026    View NOV Form

Tanks Violations
1, 2 Annual electronic line leak detector test not completed.
Facility Annual Emergency Stop Inspection not completed or inspection report not available.
1, 2 Annual leak detection certification not completed (Required annually).
1, 2 Line interstitial sensor functional test not accomplished (Required annually).
Facility Missing copies of Annual Walkthrough Inspection Report.
1, 2 Shear valve inspection report not completed (Required during Annual Walkthrough Inspection).
1, 2 Tank interstitial sensor functional test not accomplished (Required annually).

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 2500 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 4/29/2011 Abandoned Material:
Current Age: 14 Abandoned Date:
Install Date: 11/12/2011 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 11/12/2011

Equipment Information

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive Not applicable Not applicable
Corrosion Prot - Tank Fiberglass Non-Corrosive Not applicable Not applicable
Leak Detect - Piping Electronic Pressurized Line Leak Detection 5/3/2025 5/3/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 Plus with CSLD 5/3/2025 5/3/2026
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 5/3/2025 5/3/2026
Overfill Prev Device Overfill Drop Tube Valve 9/13/2023 9/13/2026
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Not applicable Not applicable
Piping Single Wall STP/Tanktop Sump 9/13/2023 9/13/2026
Leak Detect - Piping Sump Sensor with positive shutdown 9/13/2023 9/13/2026
Spill Contain Device Single Wall Spill Bucket 9/13/2023 9/13/2026
Tank Fiberglass Double Wall XERXES Not applicable Not applicable

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test (Piping) Pass 10/7/2019
Tank Fiberglass Double Wall XERXES Precision Test (Tank) Pass 10/7/2019



Tank Number 2

Capacity: 1000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 4/29/2011 Abandoned Material:
Current Age: 14 Abandoned Date:
Install Date: 11/12/2011 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 11/12/2011

Equipment Information

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive Not applicable Not applicable
Corrosion Prot - Tank Fiberglass Non-Corrosive Not applicable Not applicable
Leak Detect - Piping Electronic Pressurized Line Leak Detection 5/3/2025 5/3/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 Plus with CSLD 5/3/2025 5/3/2026
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 7/1/2025 7/1/2026
Overfill Prev Device Overfill Drop Tube Valve 9/13/2023 9/13/2026
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Not applicable Not applicable
Piping Single Wall STP/Tanktop Sump 9/13/2023 9/13/2026
Leak Detect - Piping Sump Sensor with positive shutdown 9/13/2023 9/13/2026
Spill Contain Device Single Wall Spill Bucket 9/13/2023 9/13/2026
Tank Fiberglass Double Wall XERXES Not applicable Not applicable

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test (Piping) Pass 10/7/2019
Tank Fiberglass Double Wall XERXES Precision Test (Tank) Pass 10/7/2019

Failed test = the latest test has failed.

Not applicable = a test does not apply to this equipment type or configuration.

No passing test found = a passing test is expected but was not found from the source data.


Dispenser Information



Name\ID DIESEL

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/13/2023 9/13/2026
Leak Detect - Piping Sump Sensor with positive shutdown 5/3/2025 5/3/2026



Name\ID RUL

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/13/2023 9/13/2026
Leak Detect - Piping Sump Sensor with positive shutdown 5/3/2025 5/3/2026

Failed test = the latest test has failed.

Not applicable = a test does not apply to this equipment type or configuration.

No passing test found = a passing test is expected but was not found from the source data.


MFD Motorfuel Dispensing Forms

No Forms Found